User Manual
CAUTION: SYSTEM FAILURE
If below error codes appear, please turn off the system and
contact an Authorized Service Provider.
Number
Cause
1
Indoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error
2
Indoor and outdoor unit communication malfunction
3
Indoor fan speed malfunction
4
Indoor room temperature sensor error
5
Evaporator coil temperature sensor error
6
Refrigerant leak detection system malfunction
7
Water level alarm malfunction
8
Dual indoor unit (twin model only) communication malfunction
9
Other twin model malfunction
10
Overload protection
11
Outdoor temperature sensor error
12
Outdoor condenser pipe sensor error
13
Discharge air temperature sensor error
14
Outdoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error
15
Outdoor fan speed (DC fan motor only) malfunction
16
Inverter module IPM protection
17
High/Low voltage protection
18
Compressor top overheating protection
19
Outdoor low temperature protection
20
Compressor drive error
21
Mode confl ict
22
Compressor low-pressure protection
23
Outdoor IGBT sensor error
24
Indoor unit communication malfunction
Table 3
Bosch Thermotechnology Corp. | 06.2019
Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump | 13
Operation indicator
Timer indicator
fl ashes
1
Off
2
Off
4
Off
5
Off
6
Off
7
Off
8
Off
9
Off
10
Off
1
On
2
On
3
On
4
On
5
On
6
On
1
Flash
2
Flash
3
Flash
4
Flash
5
Flash
6
Flash
7
Flash
8
Flash
11
On
Error Code
E0
E1
E3
E4
E5
EC
EE
E8
E9
F0
F1
F2
F3
F4
F5
P0
P1
P2
P3
P4
P5
P6
P7
FA
Data subject to change
- Manuals
- Brands
- Bosch Manuals
- Air Conditioner
- Climate 5000
- Service manual
-
Contents
-
Table of Contents
-
Troubleshooting
-
Bookmarks
Quick Links
SERVICE MANUAL
CLIMATE 5000 RAC SINGLE SPLIT (R32)
Related Manuals for Bosch CLIMATE 5000
Summary of Contents for Bosch CLIMATE 5000
-
Page 1
SERVICE MANUAL CLIMATE 5000 RAC SINGLE SPLIT (R32) -
Page 2: Table Of Contents
Temperature Sensor Resistance Value Table for TP ..58 3.1.13 8°C Heating (Optional) ……….. 11 Pressure On Service Port (R32) ……59 3.1.14 Self clean (Optional) ……….11 CAUTION Risk of fire/flammable material CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 3: Safety Instructions
Work in confined spaces shall be avoided. The area around the working space shall be sectioned off. Ensure that the area is free of flammable material. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 4: Checking For Leakage
This process shall be repeated until no CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 5: Charging Procedures
1.2.19 Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is important that all refrigerants are removed or recovered correctly according standards. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 6: Specifications
485 Wire-controller Connected SENSOR Wire-controller FOR SETTING NETADDRESS (CCM Comm.Bus) ENC3+F1 (MULTI-FUNCTION CONTROL BOARD) ——This symbol indicates the CODE element is optional,the actual NETADDRESS shape shall prevail. FACTORY SETTING Fig. 1. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 7: Outdoor Unit
OPTIONAL MAIN CRANKCASE HEATER BLUE OR BOARD WHITE OPTIONAL BLUE OR WHITE WHITE HEATER OPTIONAL BLUE BLUE BLACK BLACK CN 7 COMPRESSOR ELECTRONIC EXPANSION DC-FAN VALVE OPTIONAL OPTIONAL DC-FAN Fig. 2. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 8
NOTE: As Ihe standby control needs, the cross section area of cable connected to W, 1,2 must be selected to suit the maximum system current. The maximum system current is equal to thesum of indoor unit TO INDOOR UNIT POWER SUPPLY Fig. 3. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 9: Product Features
• When more than one temperature sensor is malfunctioning, the air conditioner ceases operation. • When the current exceeds the preset value, the current protection function activates and the compressor ceases operation. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 10: Heating Mode
• T3 value stays 2K above parameter TCDE for 80 seconds. than 17°C) every hour. After 2 hours, the set temperature stops • Unit runs for 15 minutes consecutively in defrosting mode. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 11: Auto-Restart Function
• To enter information inquiry status, complete the following proce- dure within ten seconds: • Press LED 3 times. • Press SWING 3 times. • If you are successful, you will hear beeps for two seconds. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 12
Causes of compressor 0-99 For a detailed explana- stop tion, contact technical support. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 13
Product Features Displayed code Explanation Displayed value Meaning Additional Notes Reserved 0-FF 2-28 5-20 5-25 Table 7. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 14: Maintenance And Disassembly
Wait for 5 minutes then check whether the gauge needle moves after turning off the vacuum pump. If the gauge needle moves a. Check whether the vacuum pressure gauge indicates -1 bar backward, check whether there is gas leakage. (-14.5 Psi). CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 15: Refrigerant Recharge
9. When the electronic scale displays the correct weight (refer to the gauge and the pressure of the low side to confirm), turn off the air conditioner, then disconnect the charge hose immediately from the gas valve service port. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 16: Re-Installation
7. Disconnect the charge set and mount the caps of service port and liquid / gas valves. 8. Use a torque wrench to tighten the caps to a torque of 18 N.m. 9. Check for gas leakage. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 17
Wait for 5 minutes then check whether the gauge needle moves after turning off the vacuum pump. If the gauge needle moves backward, check whether there is gas leakage. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 18
6. Disconnect the charge hose from the vacuum pump. 7. Mount the caps of service port and liquid / gas valves. 8. Use a torque wrench to tighten the caps to a torque of 18 N.m. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 19
1. Mechanical connectors used indoors shall comply with local regulations. 2. When mechanical connectors are re-used indoors, sealing parts shall be renewed. When flared joints are re-used indoors, the flare part shall be re-fabricated. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 20: Disassembly
6) Disconnect the connector for display board (see fig. 15). Filter Fig. 12. 3) Open the horizontal louver and push the hook towards left to open it (see fig. 13). Horizontal Louver Hook Fig. 13. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 21
Open the screw caps(2) and the remove the screws (see fig. 16). 9) Release the 4 hooks. Fig. 16. 10) Release the seven hooks in the back (see fig. 17). Fig. 15. Hooks Fig. 17. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 22
(see fig. 19). Electronic Box Cover Fixing Screw Fixing Screw Electronic Box Fig. 19. 2) Pull out the room temperature sensor (T1) and the coil temperature sensor (T2) (see fig. 20). Fig. 21. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 23
3) Remove the two screws on the evaporator located at the base of the bearing side (see fig. 26). Capacitor of Fan Motor Fig. 23. NOTICE: This section is for reference only. Actual unit appearance may vary. Screws Fig. 26. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 24
3) Remove the fixing screw (see fig. 30). 4) Pull out the fan motor and fan assembly from the side. Fixing Screw Fig. 30. NOTICE: This section is for reference only. Actual unit appearance may vary. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 25: Outdoor Unit
3) Remove the screws of the top cover and then remove the top cover (3 screws). One of the screws is located underneath the big handle (see fig. 33). Top Cover Fig. 33. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 26
Fig. 34. 5) Remove the screws of dust cover (1 screw) (see fig. 35). Fig. 36. NOTICE: Dust Cover This section is for reference only. Actual unit appearance may vary. Fig. 35. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 27
3) Remove the screws of the top cover and then remove the top cover (3 screws). One of the screws is located underneath the big handle (see fig. 38). Top Cover Dust Cover Fig. 40. Fig. 38. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 28
3) Remove the screws of the top cover and then remove the top cover (3 screws). One of the screws is located underneath the big handle (see fig. 43). Top Cover Fig. 43. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 29
5) Remove the screws of water collecting cover and then remove the dust cover (1 screw) (see fig. 45). Fig. 46. Dust Cover NOTICE: This section is for reference only. Actual unit appearance may vary. Fig. 45. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 30
3) Remove the screws of the top cover. (2 screws) (see fig. 48). AC Fan DC Fan Fig. 50. 6) Remove the fixing screws of the fan motor (4 screws) (see fig. 51). Fig. 48. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 31
3) Unfix the hooks and then open the electronic control box cover (4 hooks) (see fig. 53). Fig. 51. NOTICE: This section is for reference only. Actual unit appearance may vary. Hook Fig. 53. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 32
Electronic Expansion Valve Fig. 56. NOTICE: This section is for reference only. Actual unit appearance may vary. Fig. 55. NOTICE: This section is for reference only. Actual unit appearance may vary. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 33
Fig. 58. Electronic Expansion Valve NOTICE: This section is for reference only. Actual unit appearance may vary. Fig. 57. NOTICE: This section is for reference only. Actual unit appearance may vary. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 34
(see fig. 59). cover (see fig. 60). 2) Remove the four-way valve assembly with pliers. Terminal Cover Fig. 60. Fig. 59. NOTICE: This section is for reference only. Actual unit appearance may vary. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 35
3) Remove the hex nuts and washers securing the compressor, located on the bottom plate (see fig. 62). Fig. 63. NOTICE: This section is for reference only. Actual unit appearance may vary. Fig. 62. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 36: Troubleshooting
The terminals are located on the bottom surface of the outdoor PCB. Discharging position Plug of soldering iron (Discharging period 10 seconds or more) Fig. 65. NOTICE: This picture is for reference only. Actual appearances may vary. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 37: General Troubleshooting
Test the unit using the remote control. If the unit does not respond to the remote controller, replace the PCB of the indoor unit. If the unit responds, replace the display board. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 38: Error Diagnosis And Troubleshooting
Low suction pressure Page 42-43 Unit runs continuously but insufficient Page 42-43 cooling Too cool Page 42-43 Compressor is noisy Page 42-43 Horizontal louver can not revolve Page 42-43 Table 11. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 39: Quick Maintenance By Error Code
Compressor ✗ ✗ ✗ ✗ ✓ ✗ ✗ ✓ IPM board ✗ ✗ ✗ ✗ ✓ ✓ ✗ ✓ Outdoor unit ✗ ✗ ✗ ✗ ✗ ✗ ✗ ✗ Table 13. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 40
✩ ✩ ✩ ✩ frequently Unit runs continuously but insuffi- ✩ ✩ ✩ ✩ ✩ ✩ ✩ ✩ cient cooling(heating) Unit is noisy ✩ ✩ Test method / remedy Table 14. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 41
✩ Unit runs continuously but insufficient cooling ✩ ✩ ✩ Too cool ✩ ✩ Compressor is noisy Horizontal louver can not revolve ✩ ✩ ✩ Test method / remedy Table 15. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 42
Unit runs continuously but insufficient cooling ✩ ✩ ✩ ✩ ✩ ✩ ✩ ✩ Too cool Compressor is noisy ✩ ✩ ✩ ✩ ✩ Horizontal louver can not revolve Test method / remedy Table 16. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 43: Troubleshooting By Error Code
P and UVWN; UVW and N. Digital tester Normal resistance value Digital tester Normal resistance value (+)Red (-)Black ∞ (+)Red (-)Black ∞ (Several MW) (Several MW) (+)Red Table 18. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 44: E0/F4 (Eeprom Parameter Error)
The location of the EEPROM chip on the indoor and outdoor PCB is shown in the following two images: EEPROM Chip Fig. 69. EEPROM Chip NOTICE: Fig. 68. These images are for reference only. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 45: E1 (Indoor And Outdoor Unit Communication Error)
Check the reactor. Is the error resolved? Replace the Is it normal? reactor Replace the outdoor PCB. Replace the outdoor PCB. Power on. Is the error resolved? Replace the indoor PCB. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 46: E2 (Zero Crossing Detection Error Diagnosis And Solution)
Check the connections and power supply. Correct the connections. Turn on the unit when the Is it normal? power supply is good. Indoor main PCB is defective. Replace indoor main PCB. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 47: E3/F5 (Fan Speed Is Operating Outside Of The Normal Range)
Check the wiring of fan motor. Is it improperly Ensure proper connections wired? Measure the voltage for the fan motor from the PCB. Is it within normal Replace the indoor/outdoor PCB parameters? Replace the fan motor CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 48
100V(208~240V power supply) or 50V(115V power supply), the PCB may be defect and need to be replaced. Input Terminal Black White White Black Fig. 72. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 49: E4/E5/F1/F2/F3 (Open Circuit Or Short Circuit Of Temperature Sensor Diagnosis And Solution)
PCB. Is it properly wired? Ensure proper connections. Measure the resistance value of the sensor. Is it within acceptable parameters? Replace the Sensor. Replace indoor or outdoor PCB Fig. 73. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 50: E7 (Indoor Pcb /Display Board Communication Error)
Check the wirings and connection. Are all the connections Correct the connection or replace good? the Wirings. Replace the indoor main PCB. Is the error extinguished? Replace the Display board. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 51: Ec (Refrigerant Leakage Detection Diagnosis And Solution)
Replace the indoor Is it securely attached? Check system for leakages. Repair the leakage and recharge the Are any leakages present? refrigerant. Check System for blockages and clear blockages if present. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 52: F0 (Overload Current Protection Diagnosis And Solution)
Check the connections and wires. Are they properly Ensure proper connections or replace connected? the wires. Check the reactor. Replace outdoor PCB. Is it in working range? Replace the outdoor unit. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 53: P0 (Ipm Malfunction Or High Current Protection Diagnosis And Solution)
Please refer to the solution of the “Fan Speed is Out of Is the function OK? Control”malfunction. Check the compressor resistance values. Are the values within Replace the compressor. acceptable ranges? Replace the outdoor PCB. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 54: P1 (High / Low Voltage Protection Diagnosis And Solution)
The voltage between P and N is: — During standby: DC 310V,340V or 380V Replace the IPM board. — During start-up: 220V~400V Check the reactor. Replace outdoor PCB. Is it in working range? Replace the reactor. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 55: P2 (High Temperature Protection Of Ipm Module Diagnosis And Solution)
• Connection problems Troubleshooting and repair: Check the fastening screws on the PCB and IPM radiator. Are they fixed tightly? Replace the outdoor control PCB. Tighten the screws and apply silicon grease. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 56: P4 (Inverter Compressor Drive Error Diagnosis And Solution)
Check the outdoor fan and the outdoor unit ventilation. Does it function Please refer to “Fan Speed properly? Malfunction” Check the compressor resistance values. Are they within Replace the compressor. acceptable ranges? Replace the outdoor PCB. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 57: Appendix
0.26408 17.8005 3.07075 0.77709 0.25757 16.9341 2.95896 0.75373 0.25125 16.1156 2.84421 0.73119 0.24512 15.3418 2.73823 0.70944 0.23916 14.6181 2.63682 0.68844 0.23338 13.918 2.53973 0.66818 0.22776 13.2631 2.44677 0.64862 0.22231 Table 20. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 58: Temperature Sensor Resistance Value Table For Tp
19.69 1.632 104.6 18.96 4.849 99.69 18.26 4.703 95.05 17.58 4.562 90.66 16.94 4.426 86.49 16.32 4.294 82.54 15.73 4.167 78.79 15.16 4.045 75.24 14.62 3.927 71.86 14.09 3.812 Table 21. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 59: Pressure On Service Port (R32)
1.14 80/67 0.72 0.73 0.87 0.97 0.95 0.91 0.93 0.98 1.14 1.21 90/73 0.79 0.80 0.98 1.07 1.05 0.97 1.02 1.08 1.26 1.33 Table 24. 70/59 75/63 80/67 90/73 Fig. 74. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08)
-
Page 60
(8.33/6.11) (2.78/0.56) (-2.78/-5) (-8.33/-10.56) (-17/-19) (-27/-28) 3.09 2.91 2.58 2.33 2.12 1.89 1.68 3.32 3.06 2.71 2.59 2.38 2.09 1.94 3.45 3.21 2.84 2.68 2.54 2.19 2.04 Table 27. Fig. 75. CLIMATE 5000 RAC SINGLE SPLIT (R32) – 6720894076 (2019/08) -
Page 64
Bosch Thermotechnik GmbH Junkersstrasse 20-24 D-73249 Wernau www.bosch-thermotechnology.com…
This manual is also suitable for:
R32
1508174394Bosch_Climate_5000_VRF_en BOSCH CLIMATE 5000 AAS-009-1CS pdf | FreeUserManuals.com
1508173792Bosch_Climate_5000_VRF_en BOSCH CLIMATE 5000 AA SERIES pdf | FreeUserManuals.com
1508174190Bosch_Climate_5000_VRF_en BOSCH CLIMATE 5000 AAS-009-0CS pdf | FreeUserManuals.com
1508174916Bosch_Climate_5000_VRF_en BOSCH CLIMATE 5000 AAS-012-1CS pdf | FreeUserManuals.com
1508174733Bosch_Climate_5000_VRF_en BOSCH CLIMATE 5000 AAS-012-0CS pdf | FreeUserManuals.com
User Manual: BOSCH CLIMATE 5000 AAS-024-1CS pdf | FreeUserManuals.com
Open the PDF directly: View PDF .
Page Count: 112
Bosch Climate 5000 VRF Air Conditioning General Catalogue Heat Pump & Heat Recovery VRF Systems 2 | Commercial Air Conditioners Also a powerful partner in the world of air conditioning: Bosch. Discover new opportunities: Bosch is now offering not only heating, hot water and ventilation solutions, but also VRF (Variable Refrigerant Flow) systems for efficient air conditioning in commercial buildings. This opens up attractive prospects for you and even greater benefits from the expertise of Bosch. Ideal room climate at the touch of a button Thanks to variable refrigerant flow technology, the new Bosch VRF air conditioning systems are convenient and save valuable energy at the same time. They adapt their performance to current demand and therefore also work with outstanding efficiency under partial load. The systems consist of outdoor units and several inside units and can be utilised for both cooling and heating. These new solutions from Bosch therefore play a decisive role in ensuring that people in all areas of large buildings enjoy a comfortable climate, independent of the seasons of the year. Efficiency from a single provider The future: made by Bosch If you are looking for an industrial boiler, a combined Bosch enjoys a worldwide reputation for heat and power system or high-efficiency VRF air highest-quality products and services. Global conditioning, Bosch has a multitude of solutions to organisation and production standards guarantee meet your precise needs. But that’s not all: Bosch also uncontested approval and problem-free operation realises customised package solutions with perfectly of your largescale systems from Bosch. Thanks to harmonised components and technology from one single the enormous importance and long tradition of provider. This means that you can comprehensively innovation, you benefit from the unique, pioneering exploit all existing efficiency potentials. The result: spirit of Bosch engineering and technology. Advanced your energy costs are permanently kept at a low level technology and the high quality of your new VRF system and you make a sustainable contribution to protecting from Bosch thus ensure long-term fulfilment of its users’ the environment. expectations. Commercial Air Conditioners | 3 4 | Bosch Climate 5000 VRF Bosch Climate 5000 VRF DCI Series – DC Inverter Heat Pump ▶ Heat Pump (Cooling + Heating) VRF air conditioning system ▶ Up to 64 indoor units can be operated in one system ▶ Extensive capacity range from 8 HP to 72 HP in 2 HP increasements, meets all customer requirements concerning small to large buildings SDCI Series – All DC Inverter Heat Pump ▶ Heat Pump (Cooling + Heating) VRF air conditioning system ▶ All DC inverter technology with all DC inverter compressors and all DC fan motors makes high energy efficiency ▶ Up to 64 indoor units can be operated in one system ▶ Extensive capacity range from 8 HP to 72 HP in 2 HP increasements, meets all customer needs Bosch Climate 5000 VRF | 5 RDCI Series – All DC Inverter Heat Recovery ▶ Simultaneous cooling and heating operation in one system ▶ Up to 64 indoor units can be operated in one system ▶ Extensive capacity range from 8 HP to 64 HP in 2 HP increasements, meets all customer requirement concerning small to large buildings ▶ Heat recovery is achieved by transfeering extract heat from indoor units in cooling mode to areas requiring heating ▶ The SBOX equipment switches the system between cooling and heating modes MDCI Series – Mini VRF Heat Pump ▶ Heat Pump (Cooling + Heating) VRF air conditioning system ▶ All DC inverter technology with all DC inverter compressors and all DC fan motors makes high energy efficiency ▶ Maximum 12 indoor units can be operated in one system ▶ Extensive capacity range from 8 kW to 26 kW, suitable for small offices, villas, shops, etc. 6 | Product Lineup Product Lineup DCI Series – DC Inverter Heat Pump VRF Capacity Range HP 8 10 12 14 16 18 kW 25.2 28.0 33.5 40.0 45.0 50.0 Appearance SDCI Series – All DC Inverter Heat Pump VRF Capacity Range HP 8 10 12 14 16 18 kW 25.2 28.0 33.5 40.0 45.0 50.0 Appearance RDCI Series – All DC Inverter Heat Recovery VRF Capacity Range HP 8 10 12 14 16 kW 25.2 28.0 33.5 40.0 45.0 Appearance MDCI Series – Mini VRF Heat Pump Capacity Range Appearance kW 8 10.5 12 14 16 18 20 22 26 Contents | 7 Contents 8 Overview 13 DCI Series – DC Inverter Heat Pump VRF 27 SDCI Series – All DC Inverter Heat Pump VRF 37 RDCI Series – All DC Inverter Heat Recovery VRF 47 MDCI Series – Mini VRF Heat Pump 58 Indoor Units Lineup 78 Control Systems 90 Central Control Software 100 System Selection & Design 101 Heat Recovery Ventilation Units (HRV) 106 Joints 8 | Overview Overview Bosch Climate 5000 VRF has many key technologies which results in high improved performance. You will find main technologies in the further pages which gives excellent cooling/heating performance, comfort, reliability and easy installation. Overview | 9 High efficiency DC inverter compressor Bosch Climate 5000 VRF air conditioning system offers high class energy efficiency for cooling and heating by utilizing brushless DC compressor control, innovative designed heat exchanger and several high performance other parts. High efficiency DC inverter scroll compressor reduces power consumption by 25 %. New structure enhances mid-frequency performance Specially designed scroll profile for R-410A More compact, weight reduced by 50 % Advanced permanent magnet DC motor improves low-frequency band performance Centralizing winding Efficiency-Rotor Speed Curve Powerful magnets provide high torque and efficiency and achieve 70 % reduction in volume. Distributing winding Compressor efficiency New DC motor-centralized winding Common DC motor-distributing winding Rotor speed(s-1) 20 40 60 80 100 Smooth 180° sine wave DC inverter Adopting the 180° Sine Wave Inverter to smooth motor rotation greatly improves operating efficiency compared with traditional sawtooth wave. 180° 180° High efficiency DC fan motor According to the running load and system pressure, the system controls the speed of DC fan to achieve the Motor Speed (RPM) minimum energy consumption and best performance. DC motor 1000 DC inverter stepless adjustment 800 AC inverter multistep adjustment 600 400 200 - System Pressure + 10 | Overview Optimized fan grille Optimized fan blade shape with new air outlet grille enhanced air flow volume which greatly improves fan performance and decreases noise. Also, a higher external static pressure has been achieved up to 60 Pa. New profile fan blade A new blade with sharp edges and a slight curve increases the airflow rate and lowers vibration and airflow resistance. Multi solenoid valves control technology Multi solenoid valves control technology in one system. All the solenoid valves equipped in the unit ensure temperature-control precisely, system running steadily and economic to provide a comfortable environment. Cycle duty operation In one combination, any of the outdoor units can run as the master unit and master unit can cycle in a period, to realize the equal lifespan among the outdoor units. As a result the system lifespan extends significantly. Priority 1 2 3 4 Priority 4 1 2 3 Priority 3 4 1 2 Priority 2 3 4 1 Overview | 11 Backup operation In a multiple system, if one module is failed, other modules can be backup instead of the failed one for continuing operation. Running state Stand by state Fault or stop state Start backup operation Precise oil control technology 5 stage oil control technology ensures every outdoor unit & compressor’s oil always keep in the safe level, 2nd stage 4th stage completely solve the compressor oil lack problem. 1st stage: compressor internal oil separate 2nd stage: high efficiency oil separator (separation efficiency up to 99 %) 3rd 5th stage stage: oil balance technology between compressors 4th stage: oil balance technology between modules 1st stage 5th stage: intelligent system oil return program Anti corrosion treatment Special anti corrosion treatment of the heat exchanger provides 5 to 6 times greater resistance against acid rain and salt The plastic grille protects against salt. All panel parts are corrosion resistant to protect against extreme ambient conditions. corrosion. Corrosion resistant heat-exchanger fins. All screws are anti-rust. All PCB parts in the unit are coated with double-sided moisture proof paint. The outer side of the control box metal cover is spray-painted. 3rd stage 12 | Overview Double EXV control technology Double EXV Control Technology in one system, each EXV part achieves 480 pulse to adjust flow precisely. Ensure the temperature-control precisely and steadily to provide a comfortable envrionment. Intelligent soft start technology DC inverter compressor soft start function reduces Starting current Direct start Y-△ start Start by inverter (%) 600 500 strike to the electric network. This kind of highperformance and low sound scroll compressor operates at a faster rate when starting, reducing 400 Comparison of start by inverter and by traditional methods 300 start-up time. It also helps the unit to quickly adjust the room temperature to the set level. 200 100 1 2 3 4 5 6 (Sec) Quick warm-up & cool-down design Fluctuation of room temperature By utilizing the benefits of the inverter compressor, the system can reach full load quickly and shorten 1 the warm-up and cool-down times to provide an △2 immediate and comfortable air solution. Less temperature fluctuation will create a better living environment. Cooling operation Compact design for effective use of space Easy to transport Compact size and light weight design minimizes the installation footprint, reduces the installation floor load, and is easier for transportation. For some projects the units can even be transported through the elevator or forklift, reduce access problem at the jobsite. DCI Series | 13 DCI Series Bosch DCI Series VRF offers flexible system design for all building types and high rise buildings. System offers capacity up to 72 HP by combining maximum 4 outdoor units, with 2 HP as an increasement. 14 | DCI Series Lineup Model Capacity Range HP 8 10 12 14 16 18 kW 25.2 28.0 33.5 40.0 45.0 50.0 Appearance Combination Table Model No. of Outdoor Units No. of Compressors 8 HP 1 1 10 HP 1 1 12 HP 1 2 14 HP 1 2 16 HP 1 2 Outdoor Unit Combination 8 HP 18 HP 1 2 20 HP 2 2 10 HP 12 HP 14 HP 1 1 1 1 1 2 22 HP 2 3 1 2 3 1 26 HP 2 3 1 28 HP 2 3 1 1 1 1 30 HP 2 4 1 32 HP 2 4 1 34 HP 2 4 2 4 18 HP 1 24 HP 36 HP 16 HP 38 HP 3 4 2 40 HP 3 5 1 27 16 28 31.5 37.5 20 33.5 23 40 45 26 45 50 29 50 56 33 56 63 36 61.5 69 39 68 76.5 43 73 81.5 78 87.5 50 85 95 1 53 90 101 1 56 95 106 2 59 100 112 1 63 106 119 64 113 126.5 42 HP 3 5 1 2 44 HP 3 5 1 1 1 1 2 1 1 2 64 46 HP 3 5 48 HP 3 6 1 50 HP 3 6 1 52 HP 3 6 54 HP 3 6 1 56 HP 4 6 2 58 HP 4 7 1 1 1 60 HP 4 7 1 62 HP 4 7 1 1 64 HP 4 7 66 HP 4 8 1 68 HP 4 8 1 70 HP 4 8 72 HP 4 8 Notes: Capacities are based on the following conditions: Cooling: Indoor temperature 27° C DB/19° C WB; Outdoor temperature 35° C DB/24° C WB Heating: Indoor temperature 20° C DB/15° C WB; Outdoor temperature 7° C DB/6° C WB Piping length: Piping length 7.5 m, level difference of zero. The above models combination are factory-recommended models. Heating 25.2 46 1 1 Cooling 13 1 1 1 Capacity Maximum No. of Connectable Indoor Units 64 118 131.5 64 123 137.5 64 128 143.5 64 135 151 140 157 2 64 145 162 3 64 150 168 2 64 156 175 1 1 64 163 182.5 2 64 168 188.5 1 2 64 173 193.5 3 64 178 199.5 1 2 64 185 207 3 64 190 213 1 3 64 195 218 4 64 200 224 DCI Series | 15 Features Wide Application Range Large capacity for big sized building The outdoor units capacity range from 8 HP up to 72 HP in 2 HP increasement. Maximum 64 indoor units with capacity up to 130 % of total outdoor units can be connected as one refrigeration system. 8, 10 HP 12, 14, 16 HP 18 HP 20, 22, 24, 26, 28, 30, 32, 34, 36 HP 38, 40, 42, 44, 46, 48, 50, 52, 54 HP 56, 58, 60, 62, 64, 66, 68, 70, 72 HP 59 60 53 55 50 46 45 39 40 33 35 30 26 25 20 20 15 13 10 72HP 70HP 68HP 66HP 64HP 62HP 60HP 58HP 56HP 54HP 52HP 50HP 48HP 46HP 44HP 42HP 40HP 38HP 36HP 34HP 32HP 30HP 28HP 26HP 24HP 22HP 20HP 18HP 16HP 14HP 0 8HP 5 12HP suitable for large buildings and projects. 64 65 10HP The high number of connectable units is 70 Number of connectable indoor unit More connectable indoor units 16 | DCI Series Wide operation range COOLING MODE -5°C 48°C Outdoor Temperature HEATING MODE -20°C 24°C Outdoor Temperature - 20 - 10 0 10 20 30 40 50 Outdoor temp. °C(D.B.) DCI Series system operates stable at extreme temperatures ranging from -20° C to 48° C. Long piping length Permitted value (m) Total pipe length* (Actual) Piping length Level difference Maximum piping (L) 175 Equivalent length 200 Equivalent piping length from the farthest IDU to the first indoor branch joint Level difference between IDU~ODU 1000 Actual length 40/90* Outdoor unit up 70 Outdoor unit down 110 Level difference between IDU~IDU Level difference between IDU~ODU 70/110 m Item 90 m perfect for large projects. Maximum piping actual length 175 m of 1,000 m and level difference of 110 m, making it 30 * Total pipe length is equal to two times pipe length plus pipe length. * When the farthest pipe length is more than 40 m, it needs to meet the specific condition according to the installation part of the technical manual. The first indoor unit branch Level difference between IDU~IDU 30 m The solution supports an incredible piping length IDU = Indoor unit ODU = Outdoor unit Extra high static pressure – Max. 60 Pa and air volume increased by 10 % 60 Pa The high static pressure propeller and optimized fan guard can adapt to various installation environments. 60 Pa is available for the 12 HP model, 40 Pa is available for other models. As a standard 0–20 Pa is set by default. DCI Series | 17 Higher Reliability Cycle duty operation In one combination, any outdoor unit can run as the master outdoor unit to equalize the life span of all units. Priority 1 2 3 4 Priority 1 2 3 4 Priority 1 2 3 4 Priority 1 2 3 4 Backup operation In a multiple system, when the master unit failed, any single unit can be set as the master unit, then the remaining units can keep on working. Running state Stand by state Start backup operation Fault or stop state High efficiency oil balance and oil return technology 5 stage oil control technology ensures every outdoor 2nd stage 4th stage unit & compressor’s oil always keep in the safe level, completely solve the compressor oil lack problem. 1st stage: compressor internal oil separate 2nd stage: high efficiency oil separator 5th stage (separation efficiency up to 99 %) 3rd stage: oil balance technology between compressors 4th stage: oil balance technology between modules 5th stage: intelligent system oil return program 1st stage 3rd stage 18 | DCI Series High Efficiency DCI Series with high efficiency DC compressors, all DC motors and high efficient heat exchanger. The cooling EER up to 4.29 and the heating COP up to 4.39 in the 8 HP category EER COP 4.39 4.29 3.89 8 HP 10 HP 4.14 4.17 4.02 3.91 3.93 10 HP 12 HP 14 HP 16 HP 18 HP 3.7 12 HP 3.25 3.21 3.29 14 HP 16 HP 18 HP 8 HP High performance heat exchanger The new designed window fins enlarge the heat-exchanging area, decrease the air resistance, save more power and enhance heat New design Original design exchange performance. Hydrophilic fins and inner-threaded copper High efficiency inner-thread pipe, enhance heat transfer. pipes optimize heat exchange efficiency. Hydrophilic fins Normal fins 12° C sub cooling Innovative designed outdoor unit high efficiency heat ex- When the outdoor temperature is 35° C, the refrigerant changer, one time can reach up to 12° C subcooling degree, can be cooled to 37.1° C, thus achieving high efficiency reduces the system resistance and improves reliability. heat exchange with only 2.1° C temperature difference. Original design Gas Liquid 37.1°C New design Gas Liquid 43°C 75°C Gas Gas Gas-Liquid Liquid Liquid Increase the hot liquid rate in the condenser Improve the heat-exchange efficiency Common Design 75°C Sub-cooling Technology DCI Series | 19 High Comfort Intelligent soft start technology Starting current Direct start Y-△ start Start by inverter (%) 600 DC inverter compressor soft start function reduces strike to 500 the electric network. This kind of high-performance and low 400 sound scroll compressor operates at a faster rate when start- 300 ing, reducing start-up time. It also helps the unit to quickly 200 adjust the room temperature to the set level. Comparison of start by inverter and by traditional methods 100 1 2 3 4 5 6 (Sec) Quick warm-up & cool-down design Fluctuation of room temperature Utilizing the scroll compressor benefits, 1 △2 DCI Series system can reach full load quickly and shorten warm-up or cooldown time for an immediately. Cooling operation Night silent operation mode ▶ Model 2→X: 8 hours, Y: 10 hours the PCB board allows the unit to be ▶ Model 3→X: 6 hours, Y: 12 hours ▶ Model 4→X: 8 hours, Y: 8 hours set to different time options during Non Peak and Peak operation time optimizing the units noise output. Extra silent operation mode can reduce sound level further, minimum 46.8 dB(A). Night silent operation Capacity % ▶ Model 1→X: 6 hours, Y: 10 hours 100 Load % This feature which is easily set on 50 Peak value of ambient temp. 10hrs peak temperature during daytime, and it will go back to normal operation after Y hours. Noise dB 8hrs will be activated X hours after the Night silent Mode noisc Max.-10dB(10Hp) Start 08:00 22:00 End 08:00 Notes: This function can be activated by setting at site. Temperature(load) curve shown in the graph is just an example. Intelligent defrosting Heating capacity 14:00 Usual defrosting Intelligent defrosting raises heat capacity Intelligent defrosting program to judge the defrosting time according to the systems' real requirement, reduce the heating loss by unnecessary defrosting t min Δt and make the indoor side more comfortable. Every time defrosting last only 4 min. due to the use of Time specialized defrosting valve. 20 | DCI Series Easy Installation and Service Easier Installation and Service Easy to transport Compact size and light weight design minimizes the installation footprint, reduces the installation floor load, and is easier for transportation. For some projects the units can even be transported through the elevator or forklift. Easy Maintenance Newly designed rotating control box is so excellent that it can rotate in a wide angle. It is convenient for inspection and maintenance of the pipeline system and greatly reduces the time of dismount the electric control box. Wide * Rotating Control box is available for 18 HP model which with G-shape Condenser. Ro ta ti n gA ng le Reserved checking window on electric control box for convenient spot checking and status enquiry. Compressor is located near the access panel, Self-diagnosis function helps service which simplifies checks and enables valve engineers locate faults quickly and easily. or compressors parts to be replaced easily. Various locking modes In VIP priority or vote priority mode, the address of the VIP unit should be set as 63. If there is no named 63 unit, it will respond to vote priority. Heating priority mode (default) Cooling priority mode Priority mode (VIP priority or Vote priority) Only respond to Heating mode Only respond to Cooling mode DCI Series | 21 Simple signal line connection Centralized controllers can be connected from indoor side or outdoor side (XYE terminals) at will. Only one group of communication wire of PQE, achieved both of communication for indoor & outdoor unit. It’s more convenient for communicaP QE X Y E P QE tion wiring. X Y E P QE P QE P QE P QE P QE P QE P QE Auto addressing ON Outdoor unit can distribute address for each indoor unit automatically. Wireless and wired controllers can enquire and modify each indoor unit’s address. Integrated solution for control and management Intelligent Manager of Bosch, designed specifically PC to control VRF systems, is based around a centralized format and dedicated to the complete control and monitoring of all the system’s functions. It can be used as Laptop LAN K1 K2 E M-Net Ammeter Switch Tablet X Y E Max. 1000 m a flexible multi-purpose system and applied to a variety of needs, according to the scale, purpose and control method of each building. Indoor Outdoor 22 | DCI Series Technologies High efficiency DC inverter compressor DCI Series achieves the industry’s New structure enhances mid-frequency performance Specially designed scroll profile for R-410A top class energy efficiency of cooling and heating by utilizing the brushless reluctance DC compressor control, More compact, weight reduced by 50 % DC fan motor, and improved perfor- Advanced permanent magnet DC motor improves low-frequency band performance mance heat exchanger. High efficiency DC inverter compressor reduces power consumption by 25 %. Powerful magnets provide high torque and efficiency and achieve 70 % reduction in volume. Efficiency-Rotor Speed Curve Centralizing winding Compressor efficiency Distributing winding New DC motor-centralized winding Common DC motor-distributing winding Rotor speed(s-1) 20 40 60 80 100 Smooth 180° sine wave DC inverter Smooth the rotation of the compressor motor, improve the compressor operation efficiency sharply. 180° Sine Wave DC Inverter Common Sawtooth Wave Effectively control the harmonic current and electromagnetic noise, and fully pass the international EMC test. 180° Fan grille Optimized fan blade shape with new air outlet grille enhanced air flow volume which greatly improves fan performance and decreases noise. Also, a higher external static pressure has been achieved optionally from 20 Pa to 40 Pa. (60 Pa is available for 12 HP) 180° DCI Series | 23 New profile fan blade A new blade with sharp edges and a slight curve increases the airflow rate and lowers vibration and airflow resistance. All DC fan motors According to the running load and system pressure, the system controls the speed of DC fan to achieve the Motor Speed (RPM) minimum energy consumption and best performance. DC motor 1000 DC inverter stepless adjustment 800 AC inverter multistep adjustment 600 400 200 - Multi-EXV control technology Multi-EXV Control Technology in one system, each EXV part achieves 480 pulse to adjust flow precisely. Ensure the temperature-controlling precisely and steadily to give a comfortable envrionment. System Pressure + 24 | DCI Series Dimensions 8, 10 HP 8, 10 HP Unit: mm Position illustration of screw bolts (Unit: mm) 960 765 1615 736 830 15×23 long u-shape hole 765 960 12, 14, 16, 18 HP 12, 14, 16, 18 HP Unit: mm Position illustration of screw bolts (Unit: mm) 1250 1615 1120 765 736 15×23 long u-shape hole 765 1250 DCI Series | 25 Outdoor Unit Specifications DCI Series DCI 8/25-3, DCI 10/28-3, DCI 12/33-3 Model DCI 8/25-3 Power supply Cooling Heating Connectable indoor unit V/Ph/Hz Capacity kW 25.2 28.0 33.5 kW 5.88 7.20 9.05 EER kW/kW 4.29 3.89 3.70 Capacity kW 27.0 31.5 37.5 8.99 Power input kW 6.15 7.61 COP kW/kW 4.39 4.14 4.17 Total capacity % 50 – 130 50 – 130 50 – 130 13 16 20 57 57 59 mm Ф9.53 Ф9.53 Ф12.7 Gas pipe mm Ф22.2 Ф22.2 Ф25.4 Oil balance pipe mm Ф6 Ф6 Ф6 DC DC DC+DC Max. quantity dB(A) Liquid pipe Type Quantity Fan motor W 420 420 420 Pa 0 – 20 (default) 0 – 20 (default) 0 – 20 (default) Pa 20 – 40 (customized) 20 – 40 (customized) 20 – 60 (customized) 1 1 1 31.59 31.59 11.8 Capacity kW Crankcase heater W Oil charge ml Quantity Capacity kW Crankcase heater W Oil type Oil charge ml Type Factory charging kg 27.6×2 27.6×2 27.6×2 FVC68D FVC68D FVC68D 500 500 500 – – 1 – – 17.1 – – 27.6 – – FVC68D – – 500 R-410A R-410A R-410A 9 9 11 4.4/2.6 4.4/2.6 4.4/2.6 960×1615×765 960×1615×765 1250×1615×765 1025×1790×830 1025×1790×830 1305×1790×820 200 200 268 kg 215 215 288 Cooling °C -5-48 -5-48 -5-48 Heating °C -20-24 -20-24 -20-24 Design pressure (High/Low) MPa Net dimension (W×H×D) mm Packing size (W×H×D) mm Net weight kg Gross weight Operating temperature range 1+1 15,100 Motor output Oil type Refrigerant 1 11,500 m³/h Quantity Fixed scroll compressor 1 11,500 Air flow rate ESP DC inverter compressor DCI 12/33-3 Power input Sound pressure level Pipe connections DCI 10/28-3 380-415/3/50 Notes: Capacities are based on the following conditions: Cooling: Indoor temperature 27° C DB/19° C WB; Outdoor temperature 35° C DB/24° C WB. Heating: Indoor temperature 20° C DB/15° C WB; Outdoor temperature 7° C DB/6° C WB. Piping length: Piping length is 7.5 m, level difference is zero. Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90 m. When the total equivalent liquid length is more than 90 m, please refer to technical manual to choose the connection piping diameter. Sound values are measured in a semi-anechoic room, at a position 1 m in front of the unit and 1.3 m above the floor. 26 | DCI Series Outdoor Unit Specifications DCI Series DCI 14/40-3, DCI 16/45-3, DCI 18/50-3 Model DCI 14/40-3 Power supply Cooling Heating Connectable indoor unit V/Ph/Hz Capacity kW 40.0 45.0 50.0 kW 12.31 14.02 15.20 EER kW/kW 3.25 3.21 3.29 Capacity kW 45.0 50.0 56.0 11.19 12.79 14.25 4.02 3.91 3.93 50 – 130 50 – 130 50 – 130 23 26 29 60 60 61 mm Ф12.7 Ф12.7 Ф15.9 Gas pipe mm Ф25.4 Ф28.6 Ф28.6 Oil balance pipe mm Ф6 Ф6 Ф6 DC+DC DC+DC DC+DC Power input kW COP kW/kW Total capacity % Max. quantity dB(A) Liquid pipe Type Quantity Fan motor 1+1 15,250 Motor output W 900 900 940 Pa 0 – 20 (default) 0 – 20 (default) 0 – 20 (default) Pa 20 – 40 (customized) 20 – 40 (customized) 20 – 40 (customized) 1 1 1 31.59 31.59 11.8 Capacity kW Crankcase heater W Oil type Oil charge ml Quantity Capacity kW Crankcase heater W Oil type Oil charge Refrigerant 1+1 15,100 m³/h Quantity Fixed scroll compressor 1+1 15,100 Air flow rate ESP DC inverter compressor DCI 18/50-3 Power input Sound pressure level Pipe connections DCI 16/45-3 380-415/3/50 ml Type kg 27.6×2 27.6×2 FVC68D FVC68D 500 500 500 1 1 1 13.39 13.39 20.9 27.6 27.6 27.6 FVC68D FVC68D FVC68D 500 500 500 R-410A R-410A R-410A 13 13 16 Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6 4.4/2.6 Net dimension (W×H×D) mm 1250×1615×765 1250×1615×765 1250×1615×765 Packing size (W×H×D) mm 1305×1790×820 1305×1790×820 1305×1790×820 Net weight kg 280 280 300 Gross weight kg 300 300 320 Cooling °C -5-48 -5-48 -5-48 Heating °C -20-24 -20-24 -20-24 Operating temperature range Factory charging 27.6×2 FVC68D Notes: Capacities are based on the following conditions: Cooling: Indoor temperature 27° C DB/19° C WB; Outdoor temperature 35° C DB/24° C WB. Heating: Indoor temperature 20° C DB/15° C WB; Outdoor temperature 7° C DB/6° C WB. Piping length: Piping length is 7.5 m, level difference is zero. Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90 m. When the total equivalent liquid length is more than 90 m, please refer to technical manual to choose the connection piping diameter. Sound values are measured in a semi-anechoic room, at a position 1 m in front of the unit and 1.3 m above the floor. SDCI Series | 27 SDCI Series SDCI outdoor units achieve world’s largest capacity of 72 HP with the industry’s top class energy efficiency of cooling and heating. It supports an incredible piping length of 1,000 m and a longer level difference of 110 m, making it perfect for big-sized and high-rise buildings for wide application. 28 | SDCI Series Recommended Combination Table Model No. of Outdoor Units No. of Compressors 8 HP 1 1 10 HP 1 1 12 HP 1 2 14 HP 1 2 16 HP 1 2 Outdoor Unit Combination 8 HP 18 HP 1 2 20 HP 2 2 10 HP 12 HP 14 HP 1 1 1 1 1 2 22 HP 2 3 1 2 3 1 26 HP 2 3 1 28 HP 2 3 1 1 1 1 30 HP 2 4 1 32 HP 2 4 1 34 HP 2 4 2 4 38 HP 3 4 2 3 5 1 42 HP 3 5 44 HP 3 5 1 1 46 HP 3 5 3 6 1 50 HP 3 6 1 52 HP 3 6 3 6 56 HP 4 6 2 58 HP 4 7 1 1 1 60 HP 4 7 1 62 HP 4 7 1 1 64 HP 4 7 66 HP 4 8 1 68 HP 4 8 1 70 HP 4 8 72 HP 4 8 Notes: Capacities are based on the following conditions: Cooling: Indoor temperature 27° C DB/19° C WB; Outdoor temperature 35° C DB/24° C WB. Heating: Indoor temperature 20° C DB/15° C WB; Outdoor temperature 7° C DB/6° C WB. Piping length: Piping length is 7.5 m, level difference is zero. The above combination models are factory-recommended models. 27 16 28 31.5 37.5 20 33.5 23 40 45 26 45 50 29 50 56 33 56 63 36 61.5 69 39 68 76.5 73 81.5 78 87.5 50 85 95 1 53 90 101 1 56 95 106 2 59 100 112 1 63 106 119 64 113 126.5 64 120 135 64 123 137.5 64 128 143.5 64 135 151 140 157 1 1 2 1 1 2 64 1 Heating 25.2 43 3 48 HP Cooling 13 46 1 1 Capacity (kW) 1 1 1 40 HP 54 HP 18 HP 1 24 HP 36 HP 16 HP Maximum No. of Connectable Indoor Units 2 64 145 162 3 64 150 168 2 64 156 175 1 1 64 163 182.5 2 64 168 188.5 1 2 64 173 193.5 3 64 178 199.5 1 2 64 185 207 3 64 190 213 1 3 64 195 218 4 64 200 224 SDCI Series | 29 Features Wide Application Range Wide range of outdoor units The outdoor units capacity range from 8 HP up to 72 HP in 2 HP increasement. Maximum 64 indoor units with capacity up to 130 % of total outdoor units can be connected in one refrigeration system. 8, 10 HP 12, 14, 16 HP 18 HP 20, 22, 24, 26, 28, 30, 32, 34, 36 HP 38, 40, 42, 44, 46, 48, 50, 52, 54 HP 56, 58, 60, 62, 64, 66, 68, 70, 72 HP 53 55 50 46 45 39 40 33 35 30 26 25 20 20 15 13 10 72HP 70HP 68HP 66HP 64HP 62HP 60HP 58HP 56HP 54HP 52HP 50HP 48HP 46HP 44HP 42HP 40HP 38HP 36HP 34HP 32HP 30HP 28HP 26HP 24HP 22HP 20HP 18HP 16HP 0 14HP 5 8HP and projects. 59 60 12HP units is suitable for large buildings 64 65 10HP The large quantity of connectable 70 Number of connectable indoor unit Large connectable indoor units quantity 30 | SDCI Series Wide operation range COOLING MODE -5°C 48°C Outdoor Temperature HEATING MODE -20°C 24°C Outdoor Temperature - 20 - 10 0 10 20 30 40 50 Outdoor temp. °C(D.B.) SDCI series system operates stably at extreme temperatures ranging from -20° C to 48° C. Long piping length 175 Equivalent length 200 Equivalent piping length from the farthest IDU to the first indoor branch joint Level difference Level difference between IDU~ODU 1000* Actual length 40/90** Outdoor unit up 70 Outdoor unit down 110 Level difference between IDU~IDU 30 * Total pipe length is equal to two times pipe length plus pipe length. ** When the piping length from the farthest IDU to the first indoor branch joint is more than 40 m, it needs to meet specific conditions according to the installation part of the technical manual to achieve 90 m. Level difference between IDU~IDU 30 m Piping length Maximum piping (L) Level difference between IDU~ODU 110 m Total pipe length*(Actual) 90 m Permitted value (m) Longest actual piping length 175 m Item IDU = Indoor unit ODU = Outdoor unit High external static pressure 60 Pa Maximum 60 Pa external static pressure can be customized for the outdoor unit, flexible to build-in installation. A standard 0 – 20 Pa external static pressure is equipped by default for all outdoor units. Outdoor units ESP can be customized at site (12 HP is 60 HP, other models 40 HP). SDCI Series | 31 High Efficiency High COP/EER values The cooling EER up to 4.29 and the heating COP up to 4.39 in the 8 HP category. EER COP 4.29 8 HP 4.39 3.97 10 HP 3.81 12 HP 3.54 3.4 3.38 14 HP 16 HP 18 HP 8 HP 4.17 4.17 4.02 3.91 3.89 10 HP 12 HP 14 HP 16 HP 18 HP All DC inverter technology All DC inverter compressors All DC inverter compressors make the capacity output better distributed, and always work at 60 – 140 Hz which is the most efficient range. It makes the efficiency more than 30 % higher than the normal. New structure enhances mid-frequency performance Specially designed scroll profile for R-410A More compact, weight reduced by 50 % Advanced permanent magnet DC motor improves low-frequency band performance All DC fan motors According to the running load and system pressure, the system controls the speed of DC fan to achieve the Motor Speed (RPM) minimum energy consumption and best performance. DC motor 1000 DC inverter stepless adjustment 800 AC inverter multistep adjustment 600 400 200 - System Pressure + 32 | SDCI Series High performance heat exchanger Windage & air flow Original design Relative windage resistance New design Reduce 28 % 0.8 0.6 0.4 Original design 0.2 New design 0 0 200 400 600 800 1000 Relative frosting rate High efficiency inner-threaded pipe, enhance heat transfer. Hydrophilic fins + inner-threaded pipes Relative windage resistance Frost contrast Reduce 30 % 0.8 Original design 0.6 0.4 New design 0.2 0 0 200 400 600 800 1000 Relative frosting rate ▶ The new designed window fins enlarge the heat-exchanging area, decrease the air resistance, save more power and enhance heat exchange performance. ▶ Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency. Original design Gas Liquid 37.1°C New design Gas 43°C Liquid 75°C Gas Gas Gas-Liquid Liquid Liquid Common Design Increase the hot liquid rate in the condenser Improve the heat-exchange efficiency ▶ Innovative designed high efficiency heat exchanger, which can reach up to 12° C subcooling degree, reduces the system resistance and improves reliability. ▶ When the outdoor temperature is 35° C, the refrigerant can be cooled down to 37.1° C, thus achieving high heat-exchanging efficiency with only 2.1° C temperature difference. 75°C Sub-cooling Technology SDCI Series | 33 High Comfort choice of silent mode during the night. Super silent operation mode can reduce sound level further, minimum 45 dB(A). ▶ Model 2→X: 8 hours, Y: 10 hours ▶ Model 3→X: 6 hours, Y: 12 hours ▶ Model 4→X: 8 hours, Y: 8 hours Capacity % High comfort outdoor unit’s multi- ▶ Model 1→X: 6 hours, Y: 10 hours 100 Load % Night silent operation mode 50 Peak value of ambient temp. 10hrs Noise dB 8hrs Night silent operation will be activated X hours after the peak temperature during daytime, and it will go back to normal operation after Y hours. Night silent Mode noisc Max.-10dB(10Hp) Start 08:00 14:00 End 22:00 08:00 Notes: This function can be activated by setting at site. Temperature(load) curve shown in the graph is just an example. Intelligent defrosting technology Intelligent defrosting program will judge the defrosting time according to the system real requirement, reduce the heating loss by unnecessary defrosting and make the indoor side more comfortable. Defrosting time can be shortened to 4 min. due to Heating capacity Intelligent defrosting Usual defrosting t min the specialized defrosting valve. Δt Time Easy Installation and Service Simple signal line connection Centralised controllers can be connected from indoor side or outdoor side (XYE terminals) at will. Only one group of communication wire of PQE, achieved both of communication for indoor & outdoor unit. It’s more convenient for communication wiring. P QE X Y E X Y E P QE P QE P QE Auto addressing Outdoor unit can distribute address for each indoor unit automatically. Wireless and wired controllers can enquire and modify each indoor unit’s address. ON P QE 34 | SDCI Series Outdoor Unit Specifications SDCI Series Model SDCI 8/25-3 Power supply Cooling Heating Connectable indoor unit V/Ph/Hz Capacity kW 25.2 28.0 33.5 kW 5.88 7.05 8.79 EER kW/kW 4.29 3.89 3.81 Capacity kW 27 31.5 37.5 8.99 Power input kW 6.15 7.55 COP kW/kW 4.39 4.17 4.17 Total capacity % 50 – 130 50 – 130 50 – 130 13 16 20 57 57 59 mm Ф9.53 Ф9.53 Ф12.7 Gas pipe mm Ф22.2 Ф22.2 Ф25.4 Oil balance pipe mm Ф6 Ф6 Ф6 DC DC DC 1 1 2 11,242 11,242 13,000 Max. quantity dB(A) Liquid pipe Type Quantity Fan motor Air flow rate m³/h Motor output W 750 750 560+380 Pa 0 – 20 (default) 0 – 20 (default) 0 – 20 (default) Pa 20 – 40 (customized) 20 – 40 (customized) 20 – 60 (customized) 1 1 2 31.59 31.59 31.59+11.80 ESP Quantity DC inverter compressor Capacity kW Crankcase heater W Oil type Oil charge Refrigerant SDCI 12/33-3 Power input Sound pressure level Pipe connections SDCI 10/28-3 380-415/3/50 ml Type Factory charging kg 27.6×2 27.6×2 27.6×4 FVC68D FVC68D FVC68D 500 500 500+500 R-410A R-410A R-410A 10 10 12 4.4/2.6 4.4/2.6 4.4/2.6 Design pressure (High/Low) MPa Net dimension (W×H×D) mm 960×1,615×765 960×1,615×765 1,250×1,615×765 Packing size (W×H×D) mm 1,025×1,790×830 1,025×1,790×830 1,305×1,790×820 Net weight kg 212 212 288 Gross weight kg 227 227 308 Cooling °C -5-48 -5-48 -5-48 Heating °C -20-24 -20-24 -20-24 Operating temperature range Notes: Capacities are based on the following conditions: Cooling: Indoor temperature 27° C DB/19° C WB; Outdoor temperature 35° C DB/24° C WB. Heating: Indoor temperature 20° C DB/15° C WB; Outdoor temperature 7° C DB/6° C WB. Piping length: Piping length is 7.5 m, level difference is zero. Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90 m. When the total equivalent liquid length is more than 90 m, please refer to technical manual to choose the connection piping diameter. Sound values are measured in a semi-anechoic room, at a position 1 m in front of the unit and 1.3 m above the floor. SDCI Series | 35 Outdoor Unit Specifications SDCI Series Model SDCI 14/40-3 Power supply Cooling Heating Connectable indoor unit V/Ph/Hz Capacity kW 40.0 45.0 50.0 kW 11.30 13.25 14.79 EER kW/kW 3.54 3.40 3.38 Capacity kW 45.0 50.0 56.0 11.19 12.79 14.40 4.02 3.91 3.89 50 – 130 50 – 130 50 – 130 23 26 29 61 62 62 mm Ф12.7 Ф12.7 Ф15.9 Gas pipe mm Ф25.4 Ф28.6 Ф28.6 Oil balance pipe mm Ф6 Ф6 Ф6 DC DC DC 2 2 2 15,620 15,620 15,620 Power input kW COP kW/kW Total capacity % Max. quantity dB(A) Liquid pipe Type Quantity Fan motor Air flow rate m³/h Motor output W 560+380 560+380 560+380 Pa 0 – 20 (default) 0 – 20 (default) 0 – 20 (default) Pa 20 – 40 (customized) 20 – 40 (customized) 20 – 40 (customized) 2 2 2 31.59+11.80 31.59+11.80 31.59+11.80 ESP Quantity DC inverter compressor Capacity kW Crankcase heater W Oil type Oil charge Refrigerant SDCI 18/50-3 Power input Sound pressure level Pipe connections SDCI 16/45-3 380-415/3/50 ml Type Factory charging kg 27.6×4 27.6×4 27.6×4 FVC68D FVC68D FVC68D 500+500 500+500 500+500 R-410A R-410A R-410A 15 15 17 Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6 4.4/2.6 Net dimension (W×H×D) mm 1,250×1,615×765 1,250×1,615×765 1,250×1,615×765 Packing size (W×H×D) mm 1,305×1,790×820 1,305×1,790×820 1,305×1,790×820 Net weight kg 288 288 310 Gross weight kg 308 308 330 Cooling °C -5-48 -5-48 -5-48 Heating °C -20-24 -20-24 -20-24 Operating temperature range Notes: Capacities are based on the following conditions: Cooling: Indoor temperature 27° C DB/19° C WB; Outdoor temperature 35° C DB/24° C WB. Heating: Indoor temperature 20° C DB/15° C WB; Outdoor temperature 7° C DB/6° C WB. Piping length: Piping length is 7.5 m, level difference is zero. Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90 m. When the total equivalent liquid length is more than 90 m, please refer to technical manual to choose the connection piping diameter. Sound values are measured in a semi-anechoic room, at a position 1 m in front of the unit and 1.3 m above the floor. 36 | SDCI Series Dimensions Body dimension 12, 14, 16, 18 HP Unit: mm Unit: mm 1615 1615 8, 10 HP 960 765 765 1250 Installation dimension Unit: mm Screw bolt position 1250 1120 Solid ground or roofing Concrete basement h=200 736 Rubber shocking proof mat 765 Φ10 Expansion bolt 200 15×23long U-shape hole RDCI Series | 37 RDCI Series The all DC inverter heat recovery series, which offers simultaneous cooling and heating operation in one system. The energy by-product from cooling or heating is transferred to where it is required by using the balanced heat exchanger function, which saves up to 50 % in costs compared with a conventional heat pump system. Offers simultaneous cooling and heating operation in one system 38 | RDCI Series Recommended Combination Table Model No. of Outdoor Units No. of Compressors 8 HP 1 1 10 HP 1 1 Outdoor Unit Combination 8 HP 12 HP 1 1 14 HP 1 2 16 HP 1 2 10 HP 12 HP 14 HP 16 HP 1 1 1 1 1 1 Capacity (kW) Maximum No. of Connectable Indoor Units Cooling Heating 13 25.2 27 16 28 31.5 37.5 20 33.5 23 40 45 26 45 50 18 HP 2 2 1 29 53.2 58.5 20 HP 2 2 2 33 56 63 22 HP 2 2 1 36 61.5 69 24 HP 2 3 1 39 68 76.5 1 81.5 1 1 26 HP 2 3 28 HP 2 4 2 30 HP 2 4 1 32 HP 2 4 34 HP 3 4 1 2 2 36 HP 3 4 2 38 HP 3 4 1 1 1 1 40 HP 3 5 42 HP 3 6 3 44 HP 3 6 2 1 46 HP 3 6 48 HP 3 6 1 1 1 43 73 46 80 90 50 85 95 53 90 100 56 96 108 1 59 101 113 1 63 106.5 119 126.5 1 1 64 113 64 120 135 64 125 140 2 64 130 145 3 64 135 150 158.5 50 HP 4 6 1 2 64 143.2 52 HP 4 6 2 2 64 146 163 54 HP 4 6 1 2 64 151.5 169 1 1 56 HP 4 7 1 2 64 158 176.5 58 HP 4 8 3 1 64 165 185 60 HP 4 8 2 2 64 170 190 62 HP 4 8 1 3 64 175 195 64 HP 4 8 4 64 180 200 Notes: Capacities are based on the following conditions: Cooling: Indoor temperature 27° C DB/19° C WB; Outdoor temperature 35° C DB/24° C WB. Heating: Indoor temperature 20° C DB/15° C WB; Outdoor temperature 7° C DB/6° C WB. Piping length: Piping length is 7.5 m, level difference is zero. The above combination models are factory-recommended models. RDCI Series | 39 Features Wide Application Range Wide range of outdoor units The outdoor units’ capacity range from 8 HP up to 64 HP in 2 HP increasement. Maximum 64 indoor units with capacity up to 130 % of total outdoor units can be connected as one refrigeration system. 8, 10, 12, 14, 16 HP 18 – 32 HP 34 – 48 HP 50 – 64 HP Long piping length Permitted value (m) Actual total piping length Longest piping Piping length Level difference 1000* Actual length 175 Equivalent length 200 Equivalent piping length from the farthest IDU to the first indoor branch joint 40/90** Equivalent piping length from SBOX to its downstream indoor unit 40 Level difference between indoor and outdoor units Outdoor unit up 70 Outdoor unit down 110 Level difference between indoor units 30 * Total pipe length is equal to two times pipe length plus pipe length. ** When the piping length from the farthest IDU to the first indoor branch joint is more than 40 m, it needs to meet specific conditions according to the installation part of the technical manual to achieve 90 m. IDU = Indoor unit ODU = Outdoor unit Level difference between IDU~IDU 30 m Item 90 m it perfect for large projects. Longest actual piping length 175 m of 1,000 m and level difference of 110 m, making Level difference between IDU~ODU 110 m The solution supports an incredible piping length 40 | RDCI Series Wide operation temperature range Cooling Mode -5°C 48°C Heating Mode -20°C 24°C Simultaneous Cooling and Heating Mode -5°C -20 -10 24°C 0 10 20 30 40 50 Outdoor temperature (°C DB) RDCI series system operates stable at extreme temperatures ranging from -20° C to 48° C. High external static pressure 60 Pa Maximum 60 Pa external static pressure can be customized for the outdoor unit, flexible to build-in installation. A standard 0 – 20 Pa external static pressure is equipped by default for all outdoor units. 20 – 40 Pa external static pressure can be customized for 14, 16 HP outdoor units, and 20 – 60 Pa can be customized for 8, 10, 12 HP outdoor unit. High Efficiency High EER Heat recovery is achieved by diverting exhaust heat from indoor units in cooling mode to areas requiring heating, maximising energy efficiency, reducing electricity costs and leading to high partload efficiencies (up to 7.0 in the 8 HP category). EER 7.0 7.0 8 HP, up to 7.0 10 HP, up to 6.8 12 HP, up to 6.7 14 HP, up to 6.5 16 HP, up to 6.5 EER 6.0 5.0 4.0 3.0 100 % cooling 75 % cooling 25 % heating 50 % cooling 50 % heating 25 % cooling 75 % heating 100 % heating EER in simultaneous cooling and heating mode are based on the following condition: Outdoor temperature 7° C DB/6° C WB, indoor temperature 27° C DB/19° C WB for cooling, indoor temperature 20° C DB for heating. RDCI Series | 41 All DC inverter technology All DC inverter compressors All DC inverter compressors make the capacity output better distri- New structure enhances mid-frequency performance Specially designed scroll profile for R-410A buted, and always work at 60 – 140 Hz More compact, weight reduced by 50 % which is the most efficient range. It Advanced permanent magnet DC motor improves the low frequency band performance makes the efficiency more than 30 % higher than the normal. All DC fan motors Motor Speed (RPM) According to the running load and system pressure, the system controls the speed of DC fan to achieve the minimum energy consumption and best performance. DC motor 1000 DC inverter stepless adjustment 800 AC inverter multistep adjustment 600 400 200 System Pressure - Heat recovery, more efficiency Simultaneous heating and cooling in different zones, more energy saving by heat recovery from one space to another which saves up to 50 % in costs compared with a conventional heat pump system. Cooling Heating Power consumption No power consumption for heat recovery Simultaneous Cooling and Heating Operation 2-pipe system 3-pipe system Heating capacity automatic adjustment Two parts condenser individual design, the unit can distribute a part of evaporator to be as condensing area according to the heating load requirement to improve the utilization rate of the condenser. Cooling 14 kW Partial Using Cooling 14 kW Cooling 14 kW Cooling 14 kW Heating 14 kW Heating 14 kW + 42 | RDCI Series High Comfort Cooling and heating simultaneously Simultaneous cooling and heating achieved by new designed SBOX equipment. The outdoor unit controls the operation mode of each group indoor unit to achieve simultaneous heating and cooling in one system under the SBOX equipment which cooling adopts solenoid valve to precise control cooling heating heating Max- 4 Indoor Units Max- 4 Indoor Units refrigerant flow rate. The indoor units connect to the same SBOX can realize simultaneous cooling and heating operation. cooling cooling heating Max- 4 Indoor Units heating heating cooling heating heating Max- 4 Indoor Units heating cooling heating Max- 4 Indoor Units cooling cooling Max- 4 Indoor Units Auto mode control In this mode, the indoor unit can change the operation mode, to control the indoor side temperature at a constant temperature demanded. Setting temperature Ts Temperature Indoor temperature Ti Unit change to cooling mode at daytime, when indoor temperature is higher than setting temperature, and Ti>Ts Cooling mode change to heating mode at nighttime, when indoor temperature is lower Ti<Ts Heating mode than setting temp. Mode change automatically Continuous heating during defrost operation Each heat exchanger is defrosted by using heat Outdoor Unit Heat Exchanger 1 Outdoor Unit Heat Exchanger 1 Outdoor Unit Heat Exchanger 1 transferred from one heat Heat exchanger to the other in the outdoor unit. Defrost has no impact on the indoor unit on heating mode. Heat Heat Exchanger 2 Heating Heat Exchanger 2 Defrosting heat exchanger 1 Heat Exchanger 2 Defrosting heat exchanger 2 RDCI Series | 43 Easy Installation and Service Remote addressing Addressing indoor units are able to be done just by pressing the button of the controller. No need to set the address by the DIP switch one by one. Wired controller and wireless controller can enquire and modify every indoor units address. Remote addressing Remote addressing Simple communication wiring Centralised controller can connect from indoor side or outdoor side (XYE terminals) at will. Only one group of communication wire of PQE, X, Y, E achieved both of communication for indoor & H1, H2, E outdoor unit and network. It’s more convenient for communication wiring. P, Q, E P, Q, E P, Q, E P, Q, E P, Q, E P, Q, E P, Q, E P, Q, E Professional structure design for easy maintainence The check window reserved on electric control box provides a convenient spot checking and status enquiry. With the 4 bits digital tube LED display, it is very convenient to show the data of the system, such as pressure, compressor frequency, error code, discharge temperature etc., which can make the maintenance, installation and commissioning easier. Compressor is near the outside, and there is simple pipe system for convenient main- Rotating electric control box tenance. The newly designed rotating control box is so excellent that it can rotate in a wide angle. It is convenient for the inspection and maintenance of the pipeline system and greatly reduced the time of dismount the electric control box. Outer layout compressor and simple pipe system P, Q, E P, Q, E P, Q, E 44 | RDCI Series Outdoor Unit Specifications RDCI Series Model RDCI 8/25-3 Power supply Cooling Heating Connectable indoor unit kW 25.2 28.0 33.5 40.0 45.0 5.73 6.67 8.07 11.30 13.24 EER kW/kW 4.40 4.20 4.15 3.54 3.40 Capacity kW 27.0 31.5 37.5 45.0 50.0 12.79 Power input kW 6.00 7.33 8.72 11.19 COP kW/kW 4.50 4.30 4.30 4.02 3.91 Total capacity % 50 – 130 50 – 130 50 – 130 50 – 130 50 – 130 13 16 20 23 26 57 57 58 60 60 Max. quantity dB(A) Liquid pipe mm Ф9.53 Ф12.7 Ф12.7 Ф15.9 Ф15.9 Low pressure gas pipe mm Ф22.2 Ф22.2 Ф25.4 Ф28.6 Ф28.6 High pressure gas pipe mm Ф19.1 Ф19.1 Ф19.1 Ф22.2 Ф22.2 High pressure gas balance pipe mm Ф19.1 Ф19.1 Ф19.1 Ф19.1 Ф19.1 Oil balance pipe mm Ф6 Ф6 Ф6 Ф6 Ф6 DC DC DC DC DC 2 2 2 2 2 12,000 12,000 13,000 15,000 15,000 Air flow rate m³/h Motor output W 420 420 420 750 750 Pa 0 – 20 (default) 0 – 20 (default) 0 – 20 (default) 0 – 20 (default) 0 – 20 (default) Pa 20 – 60 (customized) 20 – 60 (customized) 20 – 60 (customized) 20 – 40 (customized) 20 – 40 (customized) 1 1 1 2 2 Capacity kW 31.59 31.59 31.59 31.59+11.80 31.59+11.80 Crankcase heater W ESP Quantity Oil type Oil charge Refrigerant RDCI 16/45-3 kW Quantity DC inverter compressor RDCI 14/40-3 380-415/3/50 Capacity Type Fan motor RDCI 12/33-3 Power input Sound pressure level Pipe connections RDCI 10/28-3 V/Ph/Hz ml Type Factory charging kg 30×2 30×2 30×2 30×4 30×4 FVC68D FVC68D FVC68D FVC68D FVC68D 500 500 500 500+500 500+500 R-410A R-410A R-410A R-410A R-410A 10 10 10 13 13 Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 Net dimension (W×H×D) mm 1,250×1,615 ×765 1,250×1,615 ×765 1,250×1,615 ×765 1,250×1,615 ×765 1,250×1,615 ×765 Packing size (W×H×D) mm 1,305×1,790 ×820 1,305×1,790 ×820 1,305×1,790 ×820 1,305×1,790 ×820 1,305×1,790 ×820 Net weight kg 255 255 255 303 303 Gross weight kg 273 273 273 322 322 Cooling °C -5-48 -5-48 -5-48 -5-48 -5-48 Heating °C -20-24 -20-24 -20-24 -20-24 -20-24 Simultaneous cooling and heating °C -5~24 -5~24 -5~24 -5~24 -5~24 Operating temperature range Notes: Capacities are based on the following conditions: Cooling: Indoor temperature 27° C DB/19° C WB; Outdoor temperature 35° C DB/24° C WB. Heating: Indoor temperature 20° C DB/15° C WB; Outdoor temperature 7° C DB/6° C WB. Piping length: Piping length is 7.5 m, level difference is zero. Connection piping diameter is based on the condition that the total equivalent liquid length is less than 90 m. When the total equivalent liquid length is more than 90 m, please refer to technical manual to choose the connection piping diameter. Sound values are measured in a semi-anechoic room, at a position 1 m in front of the unit and 1.3 m above the floor. RDCI Series | 45 SBOX Specifications SBOX Unit which can be connected multiple indoor units Model SBOX01-1 SBOX02-1 SBOX04-1 Max. indoor unit groups 1 2 4 6 Max. number of each group indoor units 4 4 4 4 4×6=24 Max. number of all downstream indoor units SBOX06-1 4×1=4 4×2=8 4×4=16 Max. capacity of each group indoor units kW 16 16 16 16 Total capacity of all downstream indoor units kW ≤16 ≤28 ≤45 ≤45 Connect to outdoor unit Piping connections Connect to indoor unit Liquid pipe mm Ф9.53 Ф12.7 Ф15.9 Ф15.9 High pressure gas pipe mm Ф15.9 Ф19.1 Ф22.2 Ф22.2 Low pressure gas pipe mm Ф19.1 Ф25.4 Ф31.8 Ф31.8 Liquid pipe mm Ф9.53 Ф9.53 Ф9.53 Ф9.53 mm Ф15.9 Ф15.9 Ф15.9 Ф15.9 33 33 33 40 Gas pipe Sound pressure level dB(A) Net dimension (W×H×D) mm 630×225×600 630×225×600 960×225×600 960×225×600 1055×325×685 Packing size (W×H×D) mm 725×325×685 725×325×685 1055×325×685 Net weight kg 18 19.5 31 35 Gross weight kg 25 27 40 44.5 SBOX Unit which can be connected only one indoor unit Model SBOX02E-1 Max. number of all downstream indoor units Capacity of downstream indoor unit Connect to outdoor unit Piping connections Connect to indoor unit kW SBOX04E-1 1 1 20 ~ 28 40 ~ 56 Liquid pipe mm Ф12.7 Ф15.9 High pressure gas pipe mm Ф19.1 Ф22.2 Low pressure gas pipe mm Ф25.4 Ф31.8 Liquid pipe mm Ф9.53 Ф9.53 mm Ф15.9 Ф15.9 Gas pipe Sound pressure level dB(A) 33 Net dimension (W×H×D) 33 mm 630×225×600 960×225×600 725×325×685 1055×325×685 Packing size (W×H×D) mm Net weight kg 19.5 31 Gross weight kg 27 40 Notes: Sound values are measured in a semi-anechoic room, at a position 1 m below the SBOX in mode switch condition. It is not recommended to install in the place where high noise performance is required. 46 | RDCI Series Dimensions Body dimension Unit: mm 1615 765 1250 HP 8/10 HP 12 HP 14/16 Liquid pipe Piping Ф12.7 Ф12.7 Ф15.9 Low pressure gas pipe Ф22.2 Ф25.4 Ф28.6 High pressure gas pipe Ф19.1 Ф19.1 Ф22.2 High pressure gas balance pipe Ф19.1 Ф19.1 Ф19.1 Ф6 Ф6 Ф6 Oil balance pipe 290 245 205 205 230 170 250 200 Oil balance pipe Liquid pipe High pressure gas pipe Low pressure gas pipe R section view R: Pipe connection High pressure gas balance pipe Installation dimension Unit: mm Unit: mm Screw bolt position 1250 1120 Solid ground or roofing Concrete basement h=200 736 Rubber shocking proof mat 765 Φ10 Expansion bolt 200 15×23long U-shape hole MDCI Series | 47 MDCI Series Full DC Inverter Mini VRF with DC inverter compressor and DC fan motor delivers a highly efficient solution for small commercial buildings. Four to twelve rooms require only one outdoor unit, and individual control is enabled in each room. NEW Fashion Design DC R-410A Inverter 48 | MDCI Series Features Wide Application Range Wide range of outdoor units The outdoor units capacity range from 8 kW to 26 kW which is ideal for small offices, villas, apartments and shops, making it perfect for commercial and residential application. 8/10 kW 12/14/16/18 kW 20/22/26 kW Flexible indoor units connection Mini VRF with intelligent control gives you independent zoning control with maximum flexibility. A single outdoor unit supports up to twelve indoor units, freeing up considerable space outside. Use your backyard more wisely with much more space available created by less number of outdoor units. ▶ ▶ ▶ ▶ ▶ Max. 12 indoor units for a 26 kW outdoor unit installation Max. 11 indoor units for a 22 kW outdoor unit installation Max. 10 indoor units for a 20 kW outdoor unit installation Max. 9 indoor units for a 18 kW outdoor unit installation Max. 7 indoor units for a 16 kW outdoor unit installation ▶ ▶ ▶ ▶ Max. Max. Max. Max. 6 6 5 4 indoor indoor indoor indoor units units units units for for for for a a a a 14 kW outdoor unit installation 12 kW outdoor unit installation 10 kW outdoor unit installation 8 kW outdoor unit installation Wide operation temperature range Mini VRF system operates stable at extreme temperaCOOLING MODE ture range from -15° C to 43° C. -15°C 43°C HEATING MODE -15°C -20 27°C -10 0 10 20 30 40 50 °C(D.B.) Outdoor temp. MDCI Series | 49 Flexible piping design The Mini VRF provides a total piping length possibility of Actual total piping length*1 Piping length Level difference Longest piping 20/22/ 26 kW 100 100 120 Actual length 45 60 60 Equivalent length 50 70 70 20 20 20 Outdoor unit up 30 30 30 Outdoor unit down 20 20 20 8 8 8 Equivalent piping length from the farthest IDU to the first indoor branch joint Level difference between indoor and outdoor units 12/14/ 16/18 kW Level difference between indoor units *1 Total pipe length is equal to all the liquid pipe or all the gas pipe length. The longest piping length is 70 m Permitted value (m) 8/10 kW The first branch joint to the farthest IDU is 20 m unit can be up to 8 m. The IDU to the nearest branch joint is 15 m Level difference between IDU and ODU is 30 m indoor units of 30 m. The height difference between indoors Level difference between IDUs is 8 m 100 m, a maximum height difference between outdoor and IDU = Indoor Unit ODU = Outdoor Unit High Efficiency High COP and EER values EER COP 3.9 8 kW 3.92 4.02 3.78 3.54 3.43 3.3 3.28 3.29 3.42 10 kW 12 kW 14 kW 16 kW 18 kW 20 kW 22 kW 24 kW 8 kW 3.97 4.15 3.8 3.7 3.8 3.56 4.19 3.61 10 kW 12 kW 14 kW 16 kW 18 kW 20 kW 22 kW 26 kW High performance heat exchanger Reduce air resistance New design Original design High efficiency inner-threaded pipe, enhance heat transfer. Hydrophilic fins + inner-threaded pipes ▶ The new designed window fins enlarge the heat-exchanging area, decrease the air resistance, save more power and enhance heat exchange performance. ▶ Hydrophilic film fins and inner-threaded copper pipes optimize heat exchange efficiency. ▶ The specially coated blue fins enhance durability and protect against corrosion from air, water and other corrosive agents, assures a longer coil service life. 50 | MDCI Series Easy Installation and Service Easy installation Easy to transport Easy installation: No special area is required for outdoor units. Easy transportaion: All outdoor units can be transported by elevator, which greatly simplifies installation and reduces time and labor. The Mini VRF indoor and outdoor units are almost as easy to install as residential air conditioning systems, making them ideal for small offices and shops. Space saving design The Mini VRF units are slimmer and more compact, resulting in significant savings in installation space. In some large residential and light commercial areas, such as villas, restaurants, usually it needs more than one indoor unit, which in turn requires multiple outdoor units. Auto addressing Addresses of indoor units can be set automatically by outdoor units. Wireless controller can inquire and modify every indoor units address. Outdoor unit can distribute address for indoor unit. Shield signal wire MDCI Series | 51 More convenience in installation A four-direction space is available for connecting pipes and wiring in various installation sites. Back side Front side Right side Back side Bottom side Right side Front side Bottom side More convenient piping connector – branch box (MBB04) Easier and safer installation thanks to a branch box that simplifies piping work and the adoption of screw connection. Both left and right pipe flare connecting from outdoor unit to branch box is reserved, which greatly simplifies field installation. Two sets of pipe size converter are packed with branch box to transfer the pipe size from Φ6.35 mm to Φ9.53 mm and from Φ12.7 mm to Φ15.9 mm. Low noise The branch box linear design regulates the flow of refrigerant and reduces the noise. By locating the branch box in the ceiling or outside, noise generated by the branch box can be kept clear of living spaces, thus makes noise level to a minimum. Brazing-free quick installation All the piping leading to and from the branch box is connected using screw joints, which can be installed quickly and easily. Indoor installation The branch box can be installed in the ceiling rather than outside. Removing the side and bottom covers provides easy access for maintaining inner components such as circuit boards. New piping connection design 52 | MDCI Series Advanced Technologies Full DC inverter technology At the heart of our system is a highly intelligent inverter driven compressor. This advanced technology enables the output of the outdoor unit to be modulated by the cooling or heating demands of the zone that it controls. This advanced system ensures precise temperature regulation and highly efficient energy usage. Highly Efficient DC Motor: ▶ Creative motor core design ▶ High density neodymium magnet ▶ Concentrated type stator ▶ Wider operating frequency range Better Balance and Extremely Low Vibration: ▶ Twin eccentric cams ▶ 2 balance weights Highly Stable Moving Parts: ▶ Optimal material matching rollers and vanes ▶ Optimize compressor drive technology ▶ Highly robust bearings ▶ Compact structure Compressor (Twin Rotary) structure Motor Speed (RPM) High efficiency DC fan motor saved power up to 50 %. 1000 DC inverter stepless adjustment 800 AC inverter multistep adjustment 600 400 200 - System Pressure + Noise reducing design Optimally designed fan shape and air discharge grille increases air volume and reduces running noise. Newly Designed Fan Guard Powerful Large Propeller MDCI Series | 53 Outdoor Unit Specifications MDCI Series – Mini VRF Heat Pump Model Power supply Cooling Heating Connectable indoor unit V/Ph/Hz MDCI16-1/ MDCI16-3 MDCI18-3 220-240/1/50 220-240/1/50 220-240/1/50 380-415/3/50 220-240/1/50 380-415/3/50 220-240/1/50 380-415/3/50 220-240/1/50 380-415/3/50 8 10.5 12.3 14 15.5 17.5 kW 2.05 2.68 3.25 3.95 4.52 5.30 EER kW/kW 3.90 3.92 3.78 3.54 3.43 3.30 Capacity kW 9 11.5 13.2 15.4 17.0 19.0 Input kW 2.24 2.90 3.47 4.16 4.77 5.00 COP kW/kW 4.02 3.97 3.80 3.70 3.56 3.80 Total capacity % 45 – 130 45 – 130 45 – 130 45 – 130 45 – 130 45 – 130 Max. quantity dB(A) 4 5 6 6 7 9 56 57 57 57 57 59 Liquid pipe mm Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Gas pipe mm Ф15.9 Ф15.9 Ф15.9 Ф15.9 Ф19.1 Ф19.1 DC DC DC DC DC DC 1 1 2 2 2 2 5,500 5,500 6,000 6,000 6,000 6,800 170 170 85x2 85x2 85x2 85x2 1 1 1 1 1 1 Quantity Air flow rate m³/h Motor output W Capacity kW 7 7 10 10 14 14 Crankcase heater W 25 25 25 25 25 25 FV50S FV50S FV50S FV50S FV50S FV50S ml 670+200 670+200 870+630 870+630 1400+250 1400+250 R-410A R-410A R-410A R-410A R-410A R-410A 2.8 2.95 3.3 3.9 3.9 4.5 Oil type Oil charge Type Refrigerant MDCI14-1/ MDCI14-3 kW Quantity Compressor MDCI12-1/ MDCI12-3 Input Type Fan motor MDCI10-1 Capacity Sound pressure level Pipe connections MDCI8-1 Factory charging kg Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6 Net dimension (W×H×D) mm 1,075×966 ×396 1,075×966 ×396 900×1,327 ×400 900×1,327 ×400 900×1,327 ×400 900×1,327 ×400 Packing size (W×H×D) mm 1,120×1,100 ×435 1,120×1,100 ×435 1,030×1,456 ×435 1,030×1,456 ×435 1,030×1,456 ×435 1,030×1,456 ×435 Net weight kg 75.5 75.5 95 95 100/102 107 Gross weight kg 85.5 85.5 106 106 111/113 118 Cooling °C -15~43 -15~43 -15~43 -15~43 -15~43 -15~43 Heating °C -15~27 -15~27 -15~27 -15~27 -15~27 -15~27 Operating temperature range Notes: Capacities are based on the following conditions: Cooling: Indoor temperature 27° C DB/19° C WB; Outdoor temperature 35° C DB/24° C WB. Heating: Indoor temperature 20° C DB/15° C WB; Outdoor temperature 7° C DB/6° C WB. Piping length: Piping length is 5 m, level difference is zero. Sound values are measured in a semi-anechoic room, at a position 1 m in front of the unit and 1 m above the floor. 54 | MDCI Series Outdoor Unit Specifications MDCI Series – Mini VRF Heat Pump Model Power supply Cooling Heating Connectable indoor unit V/Ph/Hz kW 20 22.4 26 kW 6.1 6.8 7.6 EER kW/kW 3.28 3.29 3.42 Capacity kW 22 24.5 28.5 Input kW 6.1 5.9 6.8 COP kW/kW 3.61 4.15 4.19 Total capacity % 50 – 130 50 – 130 50 – 130 10 11 12 59 59 60 Max. quantity dB(A) Liquid pipe mm Ф9.53 Ф9.53 Ф9.53 Gas pipe mm Ф19.1 Ф19.1 Ф22.2 DC DC DC 2 2 2 10,999 10,494 10,494 210 (up)/160 (down) 200 (up)/150 (down) 200 (up)/150 (down) 1 1 1 Quantity Air flow rate m³/h Motor output W Quantity Compressor Capacity kW 13.98 16.86 16.86 Crankcase heater W 25 25 25 FV50S FV50S FV50S ml 1400+1300 1700+1500 1700+1500 R-410A R-410A R-410A 4.8 6.2 6.2 Oil type Oil charge Type Refrigerant MDCI26-3 380-415/3/50 Input Type Fan motor MDCI22-3 380-415/3/50 Capacity Sound pressure level Pipe connections MDCI20-3 380-415/3/50 Factory charging kg Design pressure (High/Low) MPa 4.4/2.6 4.4/2.6 4.4/2.6 Net dimension (W×H×D) mm 1,120×1,558×528 1,120×1,558×528 1,120×1,558×528 Packing size (W×H×D) mm 1,270×1,720×565 1,270×1,720×565 1,270×1,720×565 Net weight mm 137 146.5 147 Gross weight mm 153 162.5 163 Operating temperature range Cooling °C -15~46 -15~46 -15~46 Heating °C -15~24 -15~24 -15~24 Notes: Capacities are based on the following conditions: Cooling: Indoor temperature 27° C DB/19° C WB; Outdoor temperature 35° C DB/24° C WB. Heating: Indoor temperature 20° C DB/15° C WB; Outdoor temperature 7° C DB/6° C WB. Piping length: Piping length is 5 m, level difference is zero. Sound values are measured in a semi-anechoic room, at a position 1 m in front of the unit and 1 m above the floor. MDCI Series | 55 Dimensions 8/10 kW Unit: mm 8/10.5kW 366 396 336 354 966 624 990 1075 12/14/16/18 kW Unit: mm 12/14/16/18kW 1327 900 360 400 320 348 600 56 | MDCI Series Dimensions 20/22.4/26 kW Unit: mm 20/22.4/26kW 1558 1120 528 205.8 494 400 414 668 MDCI Series | 57 Notes Indoor Units Lineup Indoor Units Lineup | 59 Indoor Units Lineup 62 1 Way Cassette 64 2 Way Cassette 66 Compact 4 Way Cassette 68 4 Way Cassette 70 Low & Medium Static Pressure Duct 72 High Static Pressure Duct 74 Ceiling & Floor 76 Wall Mounted 60 | Indoor Units Lineup Type 1.5 kW 1.8 kW 2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW 1 Way Cassette 2 Way Cassette Compact 4 Way Cassette 4 Way Cassette Low Static Pressure Duct Medium Static Pressure Duct High Static Pressure Duct Ceiling & Floor Wall Mounted More than 70 models are available to meet varied customer requirements, 1.5 kW model is only available for SDCI and MDCI series. Indoor Units Lineup | 61 8.0 kW 9.0 kW 10.0 kW 11.2 kW 12.5 kW 14.0 kW 16.0 kW 20.0 kW 25.0 kW 28.0 kW 40.0 kW 45.0 kW 56.0 kW 62 | Indoor Units Lineup 1 Way Cassette LED Auto Restart Fresh Air Auto Addressing Cleanable Panel Follow Me Anti-Cold Air Function LED Display Built-in Drain Pump DISPLAY Only 153 mm thickness Auto swing Compact design, ultra slim body with a minimum Auto swing mechanism guarantees thickness of 153 mm for model 18–36, especially even airflow distribution and a better suitable for narrow ceiling, such as in lobbies and room temperature balance. small meeting rooms. 153 mm UItra Thin Heating Single-flow design suits corner installation Standard built-in drain pump with 750 mm pump head. Cooling 750 mm Fresh air, improved air quality Reserved fresh air intake port for high quality air Special enzyme sterilization and filtering technologies creates a comfortable and healthy environment. filter bacteria, smog and pollen. Provide a clean, healthy and natural air supply. Acetaldehyde Acetic acid Formol NH3 Indoor Units Lineup | 63 Model C1W18-1 C1W22-1 C1W28-1 C1W36-1 C1W45-1 C1W56-1 C1W71-1 Power supply V/Ph/Hz 1.8 2.2 2.8 3.6 4.5 5.6 7,1 Cooling capacity kcal/h 1,500 1,900 2,400 3,100 3,900 4,800 6,100 Btu/h 6,100 7,500 9,600 12,300 15,400 19,100 24.200 2.2 2.6 3.2 4 5 6.3 8 kcal/h 1,900 2,200 2,800 3,400 4,300 5,400 7,000 Btu/h 27,000 kW kW Heating capacity Rated input Rated current 220-240/1/50 7,500 8,900 10,900 13,600 17,100 21,500 Cooling W 41 41 41 41 48 48 60 Heating W 41 41 41 41 43 44 55 Cooling A 0.24 0.24 0.25 0.25 0.37 0.39 0.30 Heating A 0.24 0.24 0.25 0.25 0.37 0.39 0.30 Airflow rate (H/M/L) m³/h 523/404/275 523/404/275 573/456/315 573/456/315 704/630/503 860/810/702 933/749/592 Sound pressure level (H/M/L) dB(A) 37/34/30 38/34/30 39/37/34 40/38/34 41/39/35 42/40/36 43/41/37 R-410A R-410A R-410A R-410A R-410A R-410A R-410A EXV EXV EXV EXV EXV EXV EXV Type Refrigerant Indoor Unit Panel Piping connections Control method Net dim. (W×H×D) mm 1,054×153 ×425 1,054×153 ×425 1,054×153 ×425 1,054×153 ×425 1,204×189 ×443 1,204×189 ×443 1,204×189 ×443 Gross dim. (W×H×D) mm 1,155×245 ×490 1,155×245 ×490 1,155×245 ×490 1,155×245 ×490 1,370×295 ×505 1,370×295 ×505 1,370×295 ×505 Net/Gross kg Net dim. (W×H×D) Gross dim. (W×H×D) 12.5/16 12.5/16 13/16.5 13/16.5 31.5/37.2 31.5/37.2 24.2/19.5 mm 1,180×36.5 ×465 1,180×36.5 ×465 1,180×36.5 ×465 1,180×36.5 ×465 1,350×25 ×505 1,350×25 ×505 1,350×25 ×505 mm 1,232×107 ×517 1,232×107 ×517 1,232×107 ×517 1,232×107 ×517 1,410×95 ×560 1,410×95 ×560 1,410×95 ×560 Net/Gross kg 3.5/5.2 3.5/5.2 3.5/5.2 3.5/5.2 9/12 9/12 9/12 L (flare) mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ9.53 Φ12.7 G (flare) mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ15.9 Φ15.9 Drain piping mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 Standard Controller Infrared Remote Controller (IRC) Notes: 1. Nominal cooling capacities are based on the following conditions: return air temperature.: 27° C DB, 19° C WB, outdoor temperature.: 35° C DB, equivalent ref. Piping: 8 m (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temperature.: 20° C DB, outdoor temperature.: 7° C DB, 6° C WB, equivalent ref. Piping: 8 m (horizontal) 3. Sound level is measured at 1.4 m below the unit. 64 | Indoor Units Lineup 2 Way Cassette LED Auto Restart Fresh Air Auto Addressing Cleanable Panel Follow Me Anti-Cold Air Function LED Display Built-in Drain Pump DISPLAY Quiet operation High airflow Optimized airflow duct with low resistance greatly reduces noise, minimum down to 24 dB(A). High airflow for high ceiling application guarantees comfort in large space. It makes every person in the room get even distribution of airflow and temperature. Stylish design and slim body Thanks to the stylish appearance and slim body, the unit suits any room’s decor and ambience. At only 300 mm high, the unit requires only a small suspended ceiling space. Installation has no height limitations, which makes overall design features much more flexible. 300 mm 305 mm Standard built-in drain pump with 750 mm pump head. 750 mm Flat-type suction grille design greatly simplifies maintenance work. Indoor Units Lineup | 65 Model C2W22-1 Power supply kW Cooling capacity Heating capacity Rated current Piping connections Standard Controller C2W71-1 2.2 2.8 3.6 4.5 5.6 7.1 1,900 2,400 3,100 3,900 4,800 6,100 Btu/h 7,500 9,600 12,300 15,400 19,100 24,200 2.6 3.2 4.0 5.0 6.3 8.0 kcal/h 2,200 2,800 3,400 4,300 5,400 6,900 Btu/h 8,900 10,900 13,600 17,100 21,500 27,300 57 57 60 92 108 154 Heating W 57 57 60 92 108 154 Cooling A 0.35 0.45 0.45 0.55 0.55 0.75 Heating 0.35 0.45 0.45 0.55 0.55 0.75 m³/h A 654/530/410 654/530/410 725/591/458 850/670/550 980/800/670 1,200/1,000/ 770 dB(A) 33/29/24 36/32/29 36/32/29 39/35/30 39/35/30 44/40/34 R-410A R-410A R-410A R-410A R-410A R-410A EXV EXV EXV EXV EXV EXV Type Panel C2W56-1 W Sound pressure level (H/M/L) Body C2W45-1 Cooling Airflow rate (H/M/L) Refrigerant C2W36-1 220-240/1/50 kcal/h kW Power input C2W28-1 V/Ph/Hz Control method Net dim. (W×H×D) mm 1,172×299×591 1,172×299×591 1,172×299×591 1,172×299×591 1,172×299×591 1,172×299×591 Gross dim. (W×H×D) mm 1,355×400×675 1,355×400×675 1,355×400×675 1,355×400×675 1,355×400×675 1,355×400×675 Net/Gross kg 34/42.5 34/42.5 34/42.5 36/44.5 36/44.5 36/44.5 Net dim. (W×H×D) mm 1,430×53×680 1,430×53×680 1,430×53×680 1,430×53×680 1,430×53×680 1,430×53×680 Gross dim. (W×H×D) mm 1,525×130×765 1,525×130×765 1,525×130×765 1,525×130×765 1,525×130×765 1,525×130×765 10.5/15 Net/Gross kg 10.5/15 10.5/15 10.5/15 10.5/15 10.5/15 L (flare) mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ9.53 Φ9.53 G (flare) mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ15.9 Φ15.9 Drain piping mm OD Ф32 OD Ф32 OD Ф32 OD Ф32 OD Ф32 OD Ф32 Infrared Remote Controller (IRC) Notes: 1. Nominal cooling capacities are based on the following conditions: return air temperature.: 27° C DB, 19° C WB, outdoor temperature.: 35° C DB, equivalent ref. Piping: 8 m (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temperature.: 20° C DB, outdoor temperature.: 7° C DB, 6° C WB, equivalent ref. Piping: 8 m (horizontal) 3. Sound level is measured at 1.4 m below the unit. 66 | Indoor Units Lineup Compact 4 Way Cassette LED Auto Restart Fresh Air Auto Addressing Cleanable Panel Follow Me Anti-Cold Air Function LED Display Built-in Drain Pump DISPLAY Super High Air Flow Compact design, easy installation Fresh air intake Extremely compact casing suits any room’s decor Fresh air can enter through the cassette and requires little space for installation on a low unit so you can enjoy even fresher air in ceiling. Due to the compact body your room. and light weight, 570 all models can 0 be installed 57 mm mm without a hoist. Quiet operation, gentle air supply Sub duct Sub duct enables you to use the same air Diffuser conditioner unit to cool an additional smaller space nearby. 3-D spiral fan blade Streamline plate ensures quiet operation. Advanced 3-D spiral fan design reduces air resistance and operation noise. Indoor Units Lineup | 67 360° Airflow outlet High-lift drain pump 360° air outlet provides Drain pump with a 500 mm pump head strong air flow circulation is fitted as standard. to cool or heat every corner of a room and evenly distribute temperature. 500 mm Model MC4W15-1 MC4W22-1 MC4W28-1 MC4W36-1 MC4W45-1 Power supply V/Ph/Hz 1.5 2.2 2.8 3.6 4.5 Cooling capacity kcal/h 1,300 1,900 2,400 3,100 3,900 Btu/h 5,100 7,500 9,600 12,300 15,400 1.7 2.4 3.2 4.0 5.0 kcal/h 1,500 2,100 2,700 3,400 4,300 Btu/h 17,100 kW kW Heating capacity Rated input Rated current 220-240/1/5 5,800 8,200 10,900 13,600 Cooling W 36 50 50 56 56 Heating W 36 50 50 56 56 Cooling A 0.22 0.22 0.22 0.25 0.25 Heating A 0.22 0.22 0.22 0.25 0.25 Airflow rate (H/M/L) m³/h 501/435/283/208 522/414/313/238 522/414/313/238 610/521/409/314 610/521/409/314 Sound pressure level (H/M/L) dB(A) 34.9/32.5/22.5 35.8/33.4/23.4 35.8/33.4/23.4 41.5/35.6/28.8 41.5/35.6/28.8 R-410A R-410A R-410A R-410A R-410A EXV EXV EXV EXV EXV Type Refrigerant Indoor Unit Panel Piping connections Standard Controller Control method Net dim. (W×H×D) mm 570×260×570 570×260×570 570×260×570 570×260×570 570×260×570 Gross dim. (W×H×D) mm 675×285×675 675×285×675 675×285×675 675×285×675 675×285×675 Net/Gross kg 16/19.5 16/20 16/20 18/22 18/22 Net dim. (W×H×D) mm 647×50×647 647×50×647 647×50×647 647×50×647 647×50×647 Gross dim. (W×H×D) mm 715×123×715 715×123×715 715×123×715 715×123×715 715×123×715 2.4/4.5 Net/Gross kg 2.4/4.5 2.4/4.5 2.4/4.5 2.4/4.5 L (flare) mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35 G (flare) mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ12.7 Drain piping mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 Infrared Remote Controller (IRC) Notes: 1. Nominal cooling capacities are based on the following conditions: return air temperature.: 27° C DB, 19° C WB, outdoor temperature.: 35° C DB, equivalent ref. Piping: 8 m (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temperature.: 20° C DB, outdoor temperature.: 7° C DB, 6° C WB, equivalent ref. Piping: 8 m (horizontal) 3. Sound level is measured at 1.4 m below the unit. 68 | Indoor Units Lineup 4 Way Cassette LED Auto Restart Fresh Air Auto Addressing Cleanable Panel Follow Me Anti-Cold Air Function LED Display Built-in Drain Pump DISPLAY Super High Air Flow Lower operating sound The new designed fan blade, air deflector and the built-in throttling part make the noise reduced greatly. The former fan blade Optimized fan blade More reliable ▶ The connection of drainage pan adopts foaming technology which can further improve the connection tightness. ▶ Capacitor is isolated by a sheet metal box making it safer and even more reliable. ▶ The high voltage and low voltage electricity wires are separated in an electronic control box making the interference decreased greatly. Flexible air distribution type ▶ 7 discharge patterns in 2 to 4 directions can be selected to suit the requirements of installation site or the shape of the room. ▶ Duct connection is possible. Indoor Units Lineup | 69 Model C4W28-1 C4W36-1 C4W45-1 C4W56-1 C4W71-1 Power supply V/Ph/Hz 2.8 3.6 4.5 5.6 7.1 Cooling capacity kcal/h 2,400 3,100 3,900 4,800 6,100 Btu/h 9,600 12,300 15,400 19,100 24,200 3.2 4.0 5.0 6.3 8.0 kcal/h 2,800 3,400 4,300 5,400 6,900 Btu/h 27,300 kW kW Heating capacity Power input Rated current 220-240/1/50 10,900 13,600 17,100 21,500 Cooling W 80 80 88 88 88 Heating W 80 80 88 88 88 Cooling A 0.31 0.31 0.41 0.41 0.41 Heating A 0.31 0.31 0.41 0.41 0.41 Airflow rate (SH/H/M/L) m³/h 920/764/638/554 920/764/638/554 1,090/905/740/651 1,090/905/740/651 1,140/950/767/663 Sound pressure level (H/M/L) dB(A) 32/31/30 32/31/30 36/34/33 36/34/33 38/36/35 R-410A R-410A R-410A R-410A R-410A EXV EXV EXV EXV EXV Refrigerant Body Panel Piping connections Type Control met. Net dim. (W×H×D) mm 840×230×840 840×230×840 840×230×840 840×230×840 840×230×840 Gross dim. (W×H×D) mm 955×260×955 955×260×955 955×260×955 955×260×955 955×260×955 Net/Gross kg 21.5/26.7 21.5/26.7 23.7/28.9 23.7/28.9 23.7/28.9 Net dim. (W×H×D) mm 950×54.5×950 950×54.5×950 950×54.5×950 950×54.5×950 950×54.5×950 Gross dim. (W×H×D) mm 1,035×90×1,035 1,035×90×1,035 1,035×90×1,035 1,035×90×1,035 1,035×90×1,035 Net/Gross kg 6/9 6/9 6/9 6/9 6/9 L (flare) mm Φ6.35 Φ6.35 Φ6.35 Φ9.53 Φ9.53 G (flare) mm Φ12.7 Φ12.7 Φ12.7 Φ15.9 Φ15.9 Drain piping mm Ф32 Ф32 Ф32 Ф32 Ф32 Standard Controller Infrared Remote Controller (IRC) Model C4W80-1 C4W90-1 C4W100-1 C4W112-1 C4W140-1 Power supply V/Ph/Hz 8.0 9.0 10.0 11.2 14.0 Cooling capacity kcal/h 6,900 7,700 8,600 9,600 12,000 Btu/h 27,300 30,700 34,100 38,200 47,800 9.0 10.0 11.1 12.5 16.0 kcal/h 7,700 8,600 9,500 10,800 13,800 Btu/h 54,600 kW kW Heating capacity Power input Rated current 220-240/1/50 30,700 34,100 37,900 42,700 Cooling W 110 140 165 165 176 Heating W 110 140 165 165 176 Cooling A 0.48 0.67 0.72 0.72 0.75 Heating A 0.48 0.67 0.72 0.72 0.75 Airflow rate (SH/H/M/L) m³/h 1,380/1,200/ 1,021/789 1,598/1,332/ 1,129/908 1,750/1,651/ 1,304/1,127 1,750/1,651/ 1,304/1,127 1,774/1,658/ 1,335/1,130 Sound pressure level (H/M/L) dB(A) 42/39/37 42/39/37 45/42/40 45/42/40 46/41/39 R-410A R-410A R-410A R-410A R-410A EXV EXV EXV EXV EXV Refrigerant Body Panel Piping connections Standard Controller Type Control met. Net dim. (W×H×D) mm 840×230×840 840×300×840 840×300×840 840×300×840 840×300×840 Gross dim. (W×H×D) mm 955×260×955 955×330×955 955×330×955 955×330×955 955×330×955 Net/Gross kg 23.7/28.9 28.7/34.1 28.7/34.1 28.7/34.1 30.9/36.3 Net dim. (W×H×D) mm 950×54.5×950 950×54.5×950 950×54.5×950 950×54.5×950 950×54.5×950 Gross dim. (W×H×D) mm 1,035×90×1,035 1,035×90×1,035 1,035×90×1,035 1,035×90×1,035 1,035×90×1,035 Net/Gross kg 6/9 6/9 6/9 6/9 6/9 L (flare) mm Φ9.53 Φ9.53 Φ9.53 Φ9.53 Φ9.53 G (flare) mm Φ15.9 Φ15.9 Φ15.9 Φ15.9 Φ15.9 Drain piping mm Ф32 Ф32 Ф32 Ф32 Ф32 Infrared Remote Controller (IRC) Notes: 1. Nominal cooling capacities are based on the following conditions: return air temperature.: 27° C DB, 19° C WB, outdoor temperature.: 35° C DB, equivalent ref. Piping: 8 m (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temperature.: 20° C DB, outdoor temperature.: 7° C DB, 6° C WB, equivalent ref. Piping: 8 m (horizontal) 3. Sound level is measured at 1.4 m below the unit. 70 | Indoor Units Lineup Duct Type (Low&Medium Static Pressure) Auto Restart Fresh Air Follow Me Anti-Cold Air Function Built-in Drain Pump Wired Controller Auto Addressing Super High Air Flow Connectable To Duct Compact size External static pressure Only 210 mm (15~71 models) or 270 mm (80 to Four speed fan motor (Super high speed is 112 models) or 300 mm (140 model) in height. optional). Change the wiring connection from ‘SH’ to ‘H’ to change the ESP. min.5 mm 210 mm or 270 mm or 300 mm ceiling Convenient installation The EXV is fixed inside of the indoor unit. Standard filter is housed in an aluminum frame, which is removable from the bottom in the downward direction. Suction chamber is included as standard equipment. Fresh air hole, air inlet/outlet flange are standard for easy duct connection. A rear air inlet is standard and an inlet at the bottom is optional. Both use the same connectable duct. air intake from back air intake from below drain pump as standard 750 mm ceiling Flexible control and easy maintenance Standard wired remote controller WRC-HP. Standard functional ports are included such as Remote On/Off Dry contact switch and Alarm signal output (220 V). Indoor Units Lineup | 71 Model SLPD15-1 Power supply kW Cooling capacity Heating capacity Rated current 2.2 2.8 3.6 4.5 5.6 2,400 3,100 3,900 4,800 Btu/h 5,100 7,500 9,600 12,300 15,400 19,100 1.7 2.6 3.2 4.0 5.0 6.3 kcal/h 1,500 2,200 2,800 3,400 4,300 5,400 Btu/h 5,800 8,900 10,900 13,600 17,100 21,500 Cooling W 56 57 57 61 98 103 Heating W 56 57 57 61 98 103 Cooling A 0.31 0.31 0.31 0.33 0.36 0.36 Heating A Pa Sound pressure level (H/M/L) dB(A) Type Control method 0.31 0.31 0.31 0.33 0.36 0.36 588 (30 pa)/ 538/456/375 588 (30 pa)/ 538/456/375 588 (30 pa)/ 538/456/375 614 (30 pa)/ 597/514/429 763 (30 pa)/ 811/684/575 763 (30 pa)/ 811/684/575 10 (10-30) 10 (10-30) 10 (10-30) 10 (10-30) 10 (10-30) 10 (10-30) 35.8/34.6/31.4 36/35/32 37/35/32 38.6/37.5/33.8 39/37.9/34 39/37.9/34 R-410A R-410A R-410A R-410A R-410A R-410A EXV EXV EXV EXV EXV EXV Net dim. (W×H×D) mm 740×210×500 740×210×500 740×210×500 740×210×500 960×210×500 960×210×500 Gross dim. (W×H×D) mm 870×285×525 870×285×525 870×285×525 870×285×525 1,115×285×525 1,115×285×525 Net/Gross kg 17.5/20.5 17.5/20.5 17.5/20.5 17.5/20.5 22.5/26 22.5/26 L (flare) mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ9.53 G (flare) mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ15.9 Drain piping mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 Standard Controller Wired Remote Controller WRC-HP (6 meters connection wire) Model SLPD71-1 Power supply kW Capacity Power (Heating) MPD80-1 V/Ph/Hz Cooling Power (Cooling) SLPD56-1 1,900 ESP (external static pressure) Piping connections SLPD45-1 1.5 m³/h Indoor Unit SLPD36-1 1,290 Airflow rate (SH/M/L) Refrigerant SLPD28-1 220-240/1/50 kcal/h kW Rated input SLPD22-1 V/Ph/Hz MPD90-1 MPD112-1 MPD140-1 220-240/1/50 7.1 8.0 9.0 11.2 14.0 kcal/h 6,100 6,900 7,700 9,600 12,000 Btu/h 24,200 27,300 30,700 38,200 47,800 8.0 9.0 10.0 12.5 15.5 kW Heating kcal/h 6,900 7,700 8,600 10,800 13,300 Btu/h 27,300 30,700 34,100 42,700 52,900 Input W 105 198 200 313 274 Rated Current A 0.47 1.0 1.0 1.8 1.55 Input W 105 198 200 313 274 Rated Current A 0.47 1.0 1.0 1.8 1.55 1,127 (30 pa)/ 1,029/934/781 1,388 (50 pa)/ 1,345/1,165/1,013 1,388 (50 pa)/ 1,345/1,165/1,013 1,851 (80 pa)/ 1,800/1,556/1,400 1,745 (100 pa)/ 1,905/1,636/1,400 Indoor air flow (SH/H/M/L) m³/h ESP (external static pressure) Pa 10 (10-30) 20 (10~50) 20 (10~50) 40 (10~80) 40 (10~100) Sound pressure level (H/M/L) dB(A) 41.4/39/35 45.4/39.8/37 45.4/39.8/37 48.0 /41.9/38 47.7/43.2/39.0 R-410A R-410A R-410A R-410A R-410A EXV EXV EXV EXV EXV Type Refrigerant Indoor Unit Piping connections Standard Controller Control method Net dim. (W×H×D) mm 1,180×210×500 1,180×270×775 1,230×270×775 1,230×270×775 1,290×300×865 Gross dim. (W×H×D) mm 1,335×285×525 1,355×350×795 1,355×350×795 1,355×350×795 1,400×375×925 Net/Gross kg 28/31.5 38/46.5 40/48 40/48 49/58 L (flare) mm Φ9.53 Φ9.53 Φ9.53 Φ9.53 Φ9.53 G (flare) mm Φ15.9 Φ15.9 Φ15.9 Φ15.9 Φ15.9 Drain piping mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 OD Ф25 Wired Remote Controller WRC-HP (6 meters connection wire) Notes: 1. Nominal cooling capacities are based on the following conditions: return air temperature.: 27° C DB, 19° C WB, outdoor temperature.: 35° C DB, equivalent ref. Piping: 8 m (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temperature.: 20° C DB, outdoor temperature.: 7° C DB, 6° C WB, equivalent ref. Piping: 8 m (horizontal) 3. Sound level is measured at 1.4 m below the air outlet. External static pressure is based on high speed indoor air flow. 72 | Indoor Units Lineup High Static Pressure Duct Auto Restart Anti-Cold Air Function Auto Addressing Connectable To Duct Follow Me Wired Controller Flexible duct design External static pressure The longest distance of air supply is 14 m can be up to 196 Pa Fresh air in take min. (models 71 to 160) or 420 mm 280 Pa (models 200 to 450 mm INDOOR UNIT 560). Air supply The height of air supply is 6.5 m Air return INDOOR UNIT The maximum distance for air supply is about 14 m at height of 6.5 m. With a 420 mm (models 71 to 160) thick body, the minimum distance required above the ceiling is 450 mm. Convenient installation The EXV is fixed inside the indoor unit (models 70 to 160), requires no extra connection. Standard filter is housed in an aluminum frame, which is removable from the bottom in the downward direction. Flange for air in/outlet duct connection is standard. Flexible control and convenient for maintenance Wired remote controller WRC-HP is as standard, and wireless remote controller IRC is as an option. The display board is connected to the E-box in factory, easier troubleshooting by LED display. Easy access filters both at the rear & bottom. Standard functional port such as remote on/off dry contact. Option Double-skin drainage pan Drain pump with 750 mm pump head is optional (models 71 to 160) 750 mm Double-skin drainage pan provide double protection for ceilings (models 71 to 160 ceiling and models 400 to 560) Indoor Units Lineup | 73 Model HPD71-1 Power supply HPD80-1 V/Ph/Hz kW Cooling Capacity HPD112-1 HPD140-1 HPD160-1 7.1 8.0 9.0 11.2 14.0 16.0 kcal/h 6,100 6,900 7,700 9,600 12,000 13,800 Btu/h 24,200 27,300 30,700 38,200 47,800 54,600 8.0 9.0 10.0 12.5 16.0 17.0 kcal/h 6,900 7,700 8,600 10,800 13,300 14,600 Btu/h 58,000 kW Heating HPD90-1 220-240/1/50 27,300 30,700 34,100 42,700 54,600 Input W 263 263 423 524 724 940 Rated Current A 1.23 1.23 1.87 2.3 2.85 4.77 Input W 263 263 423 524 724 940 Rated Current A 1.23 1.23 1.87 2.3 2.85 4.77 m³/h 1,443/ 1,361/1,218 1,416/ 1,338/1,220 1,951/ 1,741/1,518 2,116/ 1,936/1,520 3,000/ 2,618/2,226 3,620/ 3,044/2,744 ESP (external static pressure) Pa 25 (25~196) 37 (37~196) 37 (37~196) 50 (50~196) 50 (50~196) 50 (50~196) Sound pressure level (H/M/L) dB(A) 48/46/44 48/46/44.5 52/49/47 52/49/47 53/50/48 54/52/50 R-410A R-410A R-410A R-410A R-410A R-410A EXV EXV EXV EXV EXV EXV Power (Cooling) Power (Heating) Indoor air flow (H/M/L) Type Refrigerant Indoor Unit Piping connections Control method Net dim. (W×H×D) mm 952×420×690 952×420×690 952×420×690 952×420×690 1,300×420×691 1,300×420×691 Gross dim. (W×H×D) mm 1,090×440×768 1,090×440×768 1,090×440×768 1,090×440×768 1,436×450×768 1,436×450×768 Net/Gross kg 45/50 45/50 46.5/52.4 50.6/56 68/70 70/77.5 L (flare) mm Φ9.53 Φ9.53 Φ9.53 Φ9.53 Φ9.53 Φ9.53 G (flare) mm Φ15.9 Φ15.9 Φ15.9 Φ15.9 Φ15.9 Φ15.9 Drain piping mm OD Ф32 OD Ф32 OD Ф32 OD Ф32 OD Ф32 OD Ф32 Standard Controller Wired Remote Controller WRC-HP (6 meters connection wire) Model HPD200-1 Power supply kW Cooling Capacity Power (Heating) 25 28 40 45 56 21,500 24,100 34,400 38,700 48,200 Btu/h 68,200 85,300 95,500 136,500 153,500 191,100 22.5 26 31.5 45 50 63 kcal/h 19,400 22,400 27,100 38,700 43,000 54,200 Btu/h 76,800 88,700 107,500 153,500 170,600 214,960 W 1516 1516 1516 2700 2700 3400 Rated Current A 8.6 8.6 8.6 12.5 12.5 15.5 Input W 1516 1516 1516 3700 2700 3400 Rated Current A m³/h Pa dB(A) Type Standard Controller HPD560-1 20 Sound pressure level (H/M/L) Piping connections HPD450-1 17,200 ESP (external static pressure) Indoor Unit HPD400-1 Input Indoor air flow (H/M/L) Refrigerant HPD280-1 220-240/1/50 kcal/h kW Heating Power (Cooling) HPD250-1 V/Ph/Hz Control method 8.6 8.6 8.6 12.5 12.5 15.5 4,700/ 4,100/3,599 4,700/ 4,100/3,599 4,700/ 4,100/3,599 7,472/ 6,072/4,995 7,472/ 6,072/4,995 9,550/ 7,950/6,600 200 (50~280) 200 (50~280) 200 (50~280) 200 (50~280) 200 (50~280) 200 (50~280) 59/55/52 59/55/52 59/55/52 61/59/56 61/59/56 63/60/57 R-410A R-410A R-410A R-410A R-410A R-410A EXV EXV EXV EXV EXV EXV Net dim. (W×H×D) mm 1,443×470×810 1,443×470×810 1,443×470×810 1,970× 668×902.5 1,970× 668×902.5 1,970× 668×902.5 Gross dim. (W×H×D) mm 1,509×550×990 1,509×550×990 1,509×550×990 2,095×800×964 2,095×800×964 2,095×800×964 Net/Gross kg 115/129 115/129 115/129 232/245 232/245 235/250 L (flare) mm Φ9.53x2 Φ9.53x2 Φ9.53x2 Φ9.53x2 Φ9.53x2 Φ9.53x2 G (flare) mm Φ15.9x2 Φ15.9x2 Φ15.9x2 Φ22.2x2 Φ22.2x2 Φ22.2x2 Drain piping mm OD Ф32 OD Ф32 OD Ф32 OD Ф32 OD Ф32 OD Ф32 Wired Remote Controller WRC-HP (6 meters connection wire) Notes: 1. Nominal cooling capacities are based on the following conditions: return air temperature.: 27° C DB, 19° C WB, outdoor temperature.: 35° C DB, equivalent ref. Piping: 8 m (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temperature.: 20° C DB, outdoor temperature.: 7° C DB, 6° C WB, equivalent ref. Piping: 8 m (horizontal) 3. Sound level is measured at 1.4 m below the air outlet. External static pressure is based on high speed indoor air flow. 74 | Indoor Units Lineup Ceiling & Floor Auto Restart Cleanable Panel Auto Addressing Anti-Cold Air Function Follow Me LED LED Display DISPLAY Convenient installation ▶ The slim and sleek structure design ensures easy installation. ▶ It can be installed into a corner of the ceiling even if the ceiling is very narrow. >20 Drop ceiling 198 mm Air Outlet The unit can be installed either horizontally on the ceiling or vertically against the wall. Auto swing and wide angle air flow ▶ Two direction auto swing – vertical and horizontal. ▶ The range of horizontal air discharge is widened which secures wider air flow distribution to provide more comfortable air circulation no matter where the units is set up. ▶ Three air flow speeds: low, medium and high; double air guides. More comfortable ▶ Adopt electrical expansion valve, ensuring precise flow control, lower modulation noise when EXV operating. ▶ Low noise operations; minimum 36 dB(A). ▶ Smoother airflow and less turbulence due to the multi-blade fan and the air guide design. Indoor Units Lineup | 75 Model CF36-1 Power supply kW Cooling capacity Heating capacity Rated current CF71-1 3.6 4.5 5.6 7.1 3,100 3,900 4,800 6,100 Btu/h 12,300 15,400 19,100 24,200 4.0 5.0 6.3 8.0 kcal/h 3,400 4,300 5,400 6,800 Btu/h 13,600 17,100 21,500 27,300 Cooling W 49 120 122 125 Heating W 49 120 122 125 Cooling A 0.23 0.67 0.67 0.67 Heating A Airflow rate (H/M/L) Sound pressure level (H/M/L) 0.23 0.67 0.67 0.67 m³/h 650/570/500 800/600/500 800/600/500 800/600/500 dB(A) 40/38/36 43/41/38 43/41/38 43/41/38 R-410A R-410A R-410A R-410A EXV EXV EXV EXV Type Refrigerant CF56-1 220-240/1/50 kcal/h kW Power input CF45-1 V/Ph/Hz Control method Net dimension (W×H×D) mm 990×203×660 990×203×660 990×203×660 990×203×660 Packing dimension (W×H×D) mm 1,089×296×744 1,089×296×744 1,089×296×744 1,089×296×744 Net weight kg 26 28 28 28 Gross weight kg 32 34 34 34 Piping connections L (flare) mm Φ6.35 Φ6.35 Φ9.53 Φ9.53 G (flare) mm Φ12.7 Φ12.7 Φ15.9 Φ15.9 Drain piping mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 Standard Controller Infrared Remote Controller (IRC) Model CF80-1 Power supply kW Cooling capacity Heating capacity Rated current CF140-1 8.0 9.0 11.2 14.0 6,900 7,700 9,600 13,300 Btu/h 27,300 30,700 38,200 47,800 9.0 10.0 12.5 15.0 kcal/h 7,700 8,600 10,800 12,900 Btu/h 30,700 34,100 42,700 51,200 Cooling W 130 130 182 182 Heating W 130 130 182 182 Cooling A 0.83 0.83 1.11 1.11 Heating A Airflow rate (H/M/L) Sound pressure level (H/M/L) 0.83 0.83 1.11 1.11 m³/h 1,200/900/700 1,200/900/700 1,980/1,860/1,730 1,980/1,860/1,730 dB(A) 45/43/40 45/43/40 47/45/42 47/45/42 R-410A R-410A R-410A R-410A Type Refrigerant CF112-1 220-240/1/50 kcal/h kW Power input CF90-1 V/Ph/Hz Control method EXV EXV EXV EXV Net dimension (W×H×D) mm 1,280×203×660 1,280×203×660 1,670×244×680 1,670×244×680 Packing dimension (W×H×D) mm 1,379×296×744 1,379×296×744 1,764×329×760 1,764×329×760 Net weight kg 34.5 34.5 54 54 Gross weight kg 41 41 59 59 Piping connections Standard Controller L (flare) mm Φ9.53 Φ9.53 Φ9.53 Φ9.53 G (flare) mm Φ15.9 Φ15.9 Φ15.9 Φ15.9 Drain piping mm OD Ф25 OD Ф25 OD Ф25 OD Ф25 Infrared Remote Controller (IRC) Notes: 1. Nominal cooling capacities are based on the following conditions: return air temperature.: 27° C DB, 19° C WB, outdoor temperature.: 35° C DB, equivalent ref. Piping: 8 m (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temperature.: 20° C DB, outdoor temperature.: 7° C DB, 6° C WB, equivalent ref. Piping: 8 m (horizontal) 3. Floor standing: Sound level is measured 1 m from air-outlet in horizontal distance, 1 m above the floor in vertical distance. Ceiling mounted: Sound level is measured 1 m from air-outlet in horizontal distance, 1 m from air-outlet in vertical distance. 76 | Indoor Units Lineup Wall Mounted Auto Restart Cleanable Panel Auto Addressing Anti-Cold Air Function Follow Me LED LED Display DISPLAY Auto Swing Louver Easy maintenance The Auto Swing Louver function The front panel can be removed for easy ensures that the air direction maintenance access. corresponds to the mode selected. 1 2 Step 3 4 Swing Convenient installation ▶ Multi-refrigerant outlet pipe method: leftrightrear, Optimal comfort through better flow control and quiet operations more flexible for installation. ▶ The EXV is built-in the indoor unit, compact size, longer The mechanical expansion valve offers the connection pipe; gas pipe: 468 mm; liquid pipe: 2,000-stage element positions to ensure 550 mm, more flexible for installation. precise flow control and less modulation ▶ Adopts new type fixing plate, is easy to install and stable. noise when the EXV is operating for a quiet and comfortable environment. Three air flow speeds: low, medium and high; double air guides. Smoother airflow and less turbulence is ensured by the multi-blade fan and the air guide design. Rear Left Right Indoor Units Lineup | 77 HW15-1 Model Power supply kW Cooling Capacity Power input Rated current HW22-1 V/Ph/Hz HW28-1 HW36-1 HW45-1 HW56-1 220-240/1/50 1.5 2.2 2.8 3.6 4.5 5.6 kcal/h 1,300 1,900 2,400 3,100 3,900 4,800 Btu/h 5,100 7,500 9,600 12,300 15,400 19,100 1.7 2.4 3.2 4.0 5.0 6.3 kW Heating kcal/h 1,500 2,100 2,800 3,400 4,300 5,400 Btu/h 5,800 8,200 10,900 13,600 17,100 21,500 Cooling W 28 28 28 28 45 45 Heating W 28 28 28 28 45 45 Cooling A 0.12 0.14 0.14 0.14 0.2 0.2 0.12 0.14 0.14 0.14 0.2 0.2 Indoor air flow (H/M/L) Heating m³/h A 427/389/336 525/480/430 525/480/430 590/520/480 860/755/630 925/860/755 Sound pressure level (H/M/L) dB(A) 33/31/28 35/32/29 35/32/29 35/32/29 40/38/34 40/38/34 R-410A R-410A R-410A R-410A R-410A R-410A EXV EXV EXV EXV EXV EXV Type Refrigerant Control method Net dimension (W×H×D) mm 915×290×230 915×290×230 915×290×230 915×290×230 1,072×315×230 1,072×315×230 Packing size (W×H×D) mm 1,020×390×315 1,020×390×315 1,020×390×315 1,020×390×315 1,180×415×315 1,180×415×315 Net weight kg 12.4 13 13 13 15.1 15.1 Gross weight kg 15.9 16.8 16.8 16.8 19.5 19.5 Φ9.53 Piping connection L (flare) mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35 G (flare) mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ15.9 Drain piping mm OD Ф16.5 OD Ф16.5 OD Ф16.5 OD Ф16.5 OD Ф16.5 OD Ф16.5 Standard Controller Infrared Remote Controller (IRC) Model HW71-1 Power supply V/Ph/Hz kW Cooling Capacity Power input Rated current HW80-1 HW90-1 220-240/1/50 7.1 8.0 9.0 kcal/h 6,100 6,900 7,700 Btu/h 24,200 27,300 30,700 8.0 9.0 10 kW Heating kcal/h 6,900 7,700 8,600 Btu/h 27,300 30,700 34,100 Cooling W 75 86 86 Heating W 75 86 86 Cooling A 0.33 0.39 0.39 0.33 0.39 0.39 Indoor air flow (H/M/L) Heating m³/h A 1190/780/580 1,320/840/640 1,320/840/640 Sound pressure level (H/M/L) dB(A) 47/43/42 48/43/38 49/43/38 R-410A R-410A R-410A EXV EXV EXV Type Refrigerant Control method Net dimension (W×H×D) mm 1,250×325×245 1,250×325×245 1,250×325×245 Packing size (W×H×D) mm 1,345×430×335 1,345×430×335 1,345×430×335 19.9 Net weight kg 19.9 19.9 Gross weight kg 25 25 25 Φ9.53 Φ9.53 Φ9.53 L (flare) Piping connections Standard Controller mm G (flare) mm Φ15.9 Φ15.9 Φ15.9 Drain piping mm OD Ф16.5 OD Ф16.5 OD Ф16.5 Infrared Remote Controller (IRC) Notes: 1. Nominal cooling capacities are based on the following conditions: return air temperature.: 27° C DB, 19° C WB, outdoor temperature.: 35° C DB, equivalent ref. Piping: 8 m (horizontal) 2. Nominal heating capacities are based on the following conditions: return air temperature.: 20° C DB, outdoor temperature.: 7° C DB, 6° C WB, equivalent ref. Piping: 8 m (horizontal) 3. Sound level is measured 1 m below the air outlet horizontally and vertically. 78 | Control Systems Control Systems Network Control Connectable To Various Sized Gateway Centralised Control Centralised Controller Touch style BVI VIM VIM X,Y,E BVIM Software Interface Gateway CC-TS Lonworks Gateway Card Lonworks Gateway BMS-LON Bacnet Gateway Card Indoor Centralised Controller Bacnet Gateway X,Y,E BMS-BAC CC-WT Web Monitoring System Modbus Gateway Card Modbus Gateway BMS-MOD Note: The wires in the diagram show the signal flows only, while not represent the actual connecting ways. Control Systems | 79 Individual Control Wired Controller WRC-HP HWRC WRC-HR Remote Controller IRC Accessories Card-key Interface HK-IM HK-IM Wired Controller Card-key Infrared Sensor IFS Infrared Control Box Wired Controller Infrared Sensor Module Outdoor Units 80 | Control Systems Wireless Remote Controller IRC Functions Portable device The wireless remote controller is a portable control device that enables users to control the A/C anywhere within a distance of 11 m. Simplified user interface Users can synchronize the air conditioners’ parameters with the display panel on the wireless remote controller to precisely control a room’s environment. Temp 1 Transmitting display 2 3 ON/OFF Running mode 4 5 Time 6 Lock ON Economic operation 8 OFF 7 Time ON/OFF 9 Fan speed Control Systems | 81 Background light The background light allows users to operate the device in a dark room. The device lights up when a button is pressed, and turns off AUTO Auto mode DRY mode Timer Lock HEAT mode COOL mode FAN mode when a given operation is completed. Built-in timer The built-in daily timer offers the convenience of automatically starting and stopping the system at set times. Eco mode Address setting ON 0 3 6 9 12 15 Besides the machine’s auto addressing function, users can set the indoor unit’s address on the wireless remote controller IRC. Specifications Dimensions (H×W×D) (mm) Power (V) 18 21 Time The indoor unit is set to work in automode from 8:00 to 20:00. Setting addresses Model OFF 24°C IRC 150×65×20 1.5 V (LR03/AAA) ×2 82 | Control Systems Wired Remote Controller AUTO Auto mode DRY mode Timer Lock HEAT mode COOL mode Filter cleaning Follow Me remind WRC-HP Functions Air filter cleaning reminding The wired controller records the total running time of the indoor unit. When the accumulated running time reaches the preset value, it will remind users need to clean the air filter of the indoor unit. Cleaning the filter regularly can keep indoor air fresh and clean, good for your health. Silent mode Under the cooling, heating and auto mode, when operating the silent mode, it can reduce the running noise through setting the fan speed to low. This will help you bring a quieter environment. FAN mode Address setting Silent mode Control Systems | 83 Remote signal receiving function Remote signal receiver WRC-HP provide a signal receiver for remote controller. Signal from remote controller can be received by a wired Air filter cleaning reminding icon controller, then sent to the indoor unit and it conveniences to control. Silent Key WRC-HP (Touch key) Locking wired controller The locking function can be used to prevent other people from using the controller. Specifications Model Dimensions (H×W×D) (mm) Power (V) WRC-HP 120×120×20 DC 5V 84 | Control Systems Wired Remote Controllers HWRC WRC-HR Functions Wired Controller For Hotel Room – Mode Setting Mode-button hidden controller: Press the temperature buttons "▲" and "▼" simultaneously for 3 seconds to 26°C Shortcut Setting select the operation mode: COOL and HEAT. The design Combination key is suitable for hotels, hospitals, schools and other similar types of buildings. Selecting Mode HWRC Wired Controller For RDCI Series – Auto Mode Under the auto mode of RDCI system, it can automatically switch to COOL or HEAT mode according to the temperature difference value between Tf (indoor temperature) and Ts (setting temperature) WRC-HR Specifications Model Dimensions (H×W×D) (mm) Power (V) HWRC WRC-HR 86×86×18 120×120×20 DC 5V Control Systems | 85 Centralized Controller Net Filter cleaning remind HEAT mode Cooling lock Timer Fan mode Heating lock COOL mode Swing Keyboard lock Remote controller lock Net connection CC-TS Functions Centralized control The centralized controller is a multifunctional device that can control up to 64 indoor units within a maximum connection length of 1,200 m. The device connects to the master outdoor units of Bosch’s newly designed products to simplify and centralize the wiring configuration. The 2 ways of connecting are as follows: X,Y,E X,Y,E P,Q,E X,Y,E P,Q,E P,Q,E X,Y,E X,Y,E *If it connects to XYE ports of master ODU, ODU must be set to auto addressing mode. Three lock modes Centralized controller provides a superior way to manage the indoor units. Users are able to make their own choice from locking the wireless controller, locking the running mode or locking the centralized controller’s keyboard as they wish. Locking Running Mode Locking Remote Controller Locking Keyboard 86 | Control Systems Functions Indoor unit working status display The centralized controller displays indoor units’ working status and error Connecting status matrix Error code or protection code codes so users can easily identify faults the userʼs manual before contacting a service engineer. GROUP QUERY RUN SET #GROUPALL # ERROR INLINE ON OFF PROTECT MODE 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 AUTO (1.6) via checking the error codes table in 00+ 16+ SET.TEMP ROOM.TEMP T3 Hr ON OFF T2A T2B 32+ FAN 48+ Hr OPR.UNSUCCESS Air filter cleaning reminding function The air filter cleaning reminding function is only available on the touch-key central controller CC-TS. Air filter cleaning reminding icon The "FL" icon indicates that the air filter in a given indoor unit needs cleaning. CC-TS Stylish design Stylish design suits high-end environments. The keyboard lock function is used to prevent operational mistakes. Control Systems | 87 Single/unified control OPR.UNSUCCESS The control object can be either a single unit or all units, which vastly simplifies the control process. Operation signal feedback ensures that all units are working in the correct mode. Access to network monitoring The centralized controller is able to bridge up to 64 indoor units on the network monitoring and building management systems. X,Y,E F1,F2,E MAX. 64 Indoor CC-TS Specifications Model Dimensions (H×W×D) (mm) Power (V) CC-TS 180×122×78 198 – 242 V (50 Hz) 88 | Control Systems Centralized Controller – Weekly Schedule AUTO Auto mode COOL mode HEAT mode Fan mode DRY mode Weekly schedule Keyboard lock Cooling lock Heating lock Remote controller lock Swing CC-WT Functions 8:00 Weekly schedule 16:00 23:59 Sun 28°C 22°C Mon 26°C 22°C 17°C 23°C Tue 26°C 22°C 17°C 23°C Wed 26°C 22°C 17°C per day, and select the desired running mode and Thu 26°C 22°C 26°C room temperature. The operating object can be a Fri 26°C 22°C 26°C single indoor unit or all the indoor units. Sat 28°C off 24°C CC-WT can include up to 64 indoor units in the weekly schedule. Users can set up to 4 periods 24°C 23°C Three lock modes Centralized controller CC-WT provides a superior way to manage the indoor units. Users are able to make their own choice from locking the wireless controller, locking the running mode or lock the Locking Running Mode Locking Remote Controller Locking Keyboard CC-WT’s keyboard as they wish. Single/unified control mode The control object can be either a single unit or all units, which vastly simplifies the control process. Operation signal feedback ensures that all units are working in the correct mode. OPR.UNSUCCESS Control Systems | 89 Indoor unit working status display CC-WT displays indoor units’ working status and error codes so users can easily identify faults via checking the error codes table in the user’s manual before contacting a service engineer. *If it connects to XYE ports of master ODU, ODU must be set to auto addressing mode. Error code or protection code Connecting status matrix # ERROR INLINE ON OFF PROTECT MODE 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 AUTO 00+ 16+ SET.TEMP ROOM.TEMP T3 Hr ON OFF T2A T2B 32+ FAN 48+ Hr OPR.UNSUCCESS Specifications Model Dimensions (H×W×D) (mm) Power (V) CC-WT 179×119×74 198 – 242 V (50 Hz) (1.6) GROUP QUERY RUN SET #GROUPALL 90 | Central Control Software Central Control Software BVIM (Intelligent Manager of Bosch) 4th Generation Network Control System Functions Intelligent Manager of Bosch, designed specifically to control VRF systems, is based on a centralized format and dedicated to the complete control and monitoring of all the system’s functions. It can be used as a flexible multi-purpose system and applied to a variety of needs, according to the scale, purpose and control method of each building. ▶ Up to 4 interfaces, 64 refrigerant systems, 1,024 indoor units, and 256 outdoor units can be controlled by one PC. ▶ Web access ▶ User friendly operation ▶ Central building monitoring and control ▶ Energy saving management ▶ SMS modem (optional) ▶ Electricity charge distribution ▶ Schedule management ▶ Low-load operation indicator ▶ Generation of operational history reports (daily, weekly, monthly) ▶ Fault display & Warning message ▶ Air filter cleaning reminding function ▶ Emergency stop and Alarm signal output Network Control Application ▶ Can run on Windows 7_32/64 bit, Windows XP_32 bit and Windows 8. ▶ Can monitor and control A/C anytime, anywhere by PC, iPhone, iPad and notebook computer. ▶ Supports WEB access: IE, Firefox, Safari and Chrome. ▶ Enables remote access through DSL, VPNs and so on. Network monitoring Internet Long distance PC (IMM) IP/Ethernet Through VPN Firewall Local PC (IMM) Router A/C Units Central Control Software | 91 Various Managements Simple Operation and Management Data Management Click & Operate, a user-friendly interface allows Operational information of individual indoor units even non-experts to perform the building manage- are monitored, allowing for distribution of power ment system easily. consumption at outdoor units. Stores operation data on multiple systems and displays it in graphical format for visual management. Uses BVIM software to generate tenant reports and help building owners bill for energy use. Electricity Charge Distribution (Patented) Provides information on proportional electrical power distribution to optimize electricity consumption management. Uses software to calculate electric power proportional distribution, output and save electricity consumption data for each indoor unit (or group) which is connected to the intelligent manager. Applies the patented Bosch Calculation Method to calculate consumption rates according to capacity demand which is based on various parameters: setting temperature, room temperature, running mode, rated HP, public areas, unused rooms, and nighttime use; outputs this information on a charge calculation sheet to evenly divide power consumption charges among tenants. Highlights Web Access function Visual Navigation With the web access function, a PC, laptop computer or a smartphone can be used as a remote controller. Clicking the jump button will display a list of all available screens. Clicking the back button will return to the previous screen. Schedule Control Data Backup Automatically performs facility start/stop control, switches the operating mode, sets temperatures and enables/disables the remote control according to the present time schedule. 4 sections and 20 actions per day for each single unit or group. The interface will automatically back up data on the installed SD card (2 GB) in case system failure occurs, such as: power failure or system dam. BVIM software also stores the previous 3 months’ operational data on the HDD. Energy Saving Management Multiple Languages Based on a predetermined schedule, the Intelligent Manager executes capacity control and intermittent operations on all air conditioning units to maintain a high comfort index. Provides seven language settings: English, Russian, French, German, Italian, Spanish, Simple Chinese Warning Message Electricity Charge Distribution The system can receive error messages from air conditioning units in more than one buildings or structures via public phone lines. Electricity charges can be easily divided when billing users for air conditioning power charges; for example, for tenants in a commercial building, offices in a rented building, or rooms in a hotel. *Requires the Bosch "SMS Modem" to send automatic warning messages to designated phone numbers. 92 | Central Control Software Accessories Bacnet Gateway Card BMS-BAC Contains 4 groups of RS485 communication ports and be able to connect up to 256 indoor units or 128 outdoor units to the BMS. Built-in WEB function. Network example XYE Each port can connect to XYE CC-TS BMS-BAC ports of IDU/ODU or the K1K2E Indoor units ports of the outdoor units. F1 F2 E XYE Each port can also connect to one centralized controller F1F2E ports. HUB Outdoor units Indoor units TCP/IP XYE Web monitoring system PQE BMS Outdoor units Indoor units PQE *If it connects to XYE ports of master ODU, ODU must be set to auto addressing mode. Monitoring units online BMS-BAC allows users to track units’ operational status and change their running parameters on Internet Explorer for maximum control convenience. Wide compatibility BMS-BAC has a wonderful adaptability to the BMS Company BMS software 1 SIMENS APOGEE 2 TRANE Tracer Summit 3 Honeywell Alerton 4 Schneider Andover 5 Johnson METASYS Brand Central Control Software | 93 Accessories Modbus Gateway Card BMS-MOD Supports Modbus protocol networks. Bridges the Bosch VRF system to BMS. Connect up to 64 indoor units or 16 indoor units and 4 outdoor units.* Built-in Web server function. * 4 outdoor units must be in the same system Network example 1) TCP connection method BMS-MOD Outdoor units Modbus TCP/IP K1K2E/ XYE bus Max. 4 K1 K2 E PQE Modbus system Indoor units Max. 64 2) RTU connection method BMS-MOD Modbus system Modbus RTU Outdoor units K1K2E/ XYE bus Max. 4 K1 K2 E PQE Indoor units Max. 64 * 1. If it connects to XYE ports of master ODU, ODU must be set to auto addressing mode. 2. XYE and K1K2E must be connected hand by hand. Config A/C System via Web When the Modbus network is set, users can conveniently configure their A/C network system over the Internet using different TCP/IP browsers. 94 | Central Control Software Accessories Lonworks Gateway Card BMS-LON Comply with LonMark protocol, realizes the management and control of VRF system. Can connect up to 64 indoor units to the BMS. Realizes nonpolarity communication, and also the application can be downloaded online. Network example Connection method 1: Suitable for all of air conditioner systems and connects maximum 64 indoor units. BMS-LON RS485 X,Y,E X,Y,E X,Y,E X,Y,E BMS system Connection method 2: Only suitable for SDCI series and connects maximum 64 indoor units. System 1 BMS-LON P,Q,E RS485 X,Y,E X,Y,E X,Y,E X,Y,E P,Q,E System 2 P,Q,E BMS system System N Specifications Model Dimensions (H×W×D) (mm) Power (V) BMS-LON 319×251×61 177~265V AC (50 Hz) X,Y,E Central Control Software | 95 Accessories Three Phase Connector TPP Detects the power condition and makes the corresponding protecting action. Protects the compressor from being damaged. Automatically distinguishes the abnormal power supply conditions and automatically recovers. Excellent reliability The protector protects the entire system from power supply problems, and auto restarts after recovery. Specifications Model Power supply (V-N-Hz) Temp. range (C) Rated operational power (VA) TPP 380~480V-3N 50/60 Hz -20° C~50° C 13 VA Over voltage 18 % Under voltage -12 % Phase imbalance Dimensions (W×H×D) (mm) 8% 81×67×35 96 | Central Control Software Digital Power Ammeter DPA-3 Calculates power consumption. Does not need adjusting after long-term use. Corresponds one outdoor unit to one digital power meter. Low power consumption The digital power meter consumes minimal energy. Voltage circuit: less than 2W/10 VA. Current circuit: less than 2.5 VA Indications and installation 15mm long crack 72 The digital power meter is tested after manufacture LCD so it can be immediately deployed and used on-site. A phase B phase C phase 201 shown in the figure on the left. Impulse 230 The LED indicators and installation schematic are 131 145 Specifications Model Dimensions (H×W×D) (mm) Power (V) DPA-3 230×145×72 200 – 500 V (50/60 Hz) Outdoor Unit Failure Alarm ODU-FA Functions Simple design ODU-FA is specially designed for engineering applications. It does not display the outdoor units working parameters, but it can be connected to the alarm device. When outdoor unit is working abnormally, the RUN light will flash. Specifications Model Dimensions (H×W×D) (mm) Power (V) ODU-FA 150×85×70 198 – 242 V (50/60 Hz) Central Control Software | 97 Accessories Infrared Sensing Controller IFS Automatically adjusts the room conditions. Automatically extends the shutting down time, avoiding frequent ON/OFF. Stylish appearance accommodates itself to different buildings. Installation example Remote controller or wired controller can Wired controller Wired controller control indoor unit. IFS IFS Electrical wiring Infrared Sensing Controller Infrared inductive control box Display panel CN3 CN2 CN1 IFS S1 Infrared sensor Display Network panel port module port Indoor main board Wired controller Remote controller Specifications Model Dimensions (H×W×D) (mm) Power (V) IFS Sensor part: 46×30×25.6, Control box: 86×72.8×15.5 DC 5V 98 | Central Control Software Hotel Card Key Interface Module HK-IM Cooperates with the wired controller to automate control. Eliminates the need for high voltage power, making the device safe and steady. Includes a build-in auto-restart function. Remote controller or wired controller can control indoor unit. Installation example Wired controller Wired controller HK-IM HK-IM Card key Electrical wiring Display panel port Hotel card key interface module Indoor main board Display panel Check Network module port Hotel Card-inserter HK-IM CN1 5 meters RUN Wired controller CN2 COM1 GND To hotel control system Remote controller Specifications Model Dimensions (H×W×D) (mm) Power (V) HK-IM 86×72.8×15.5 DC 5V Central Control Software | 99 Accessories DX-AHU KIT AHU KIT01-1/AHU KIT02-1/AHU KIT03-1 Can be used to connect VRF outdoor units with DX AHU or other brand indoor units. Introduction AHU KIT01-1/AHU KIT02-1/AHU KIT03-1 is an independent control box that can connect an AHU to SDCI series system to realize centralized control with SDCI system. Control box wiring is as follows: Power supply Power supply Centralized Controller P/Q/E X/Y/E Wired Controller T1/T2/T2B/T2C Gas/Liquid pipe Fan/pump x EXV Power supply DX AHU or other brand indoor units Specifications Model Dimensions (H×W×D) (mm) Power (V) AHU KIT01-1/AHU KIT02-1/AHU KIT03-1 335×375×150 220 – 240V ~ 50 Hz 100 | System Selection & Design Selection software To meet desginers, consultants and installers requirements, Bosch has developed an advanced design automation tool that can be used in AutoCAD-based CAD version or Windows-based version. The software provides quick and convenient selectable options for users, supports multiple languages, and greatly improves the selection process. Windows Version Load calculation: Provides two calculation methods (detailed room load calculation and rough load calculation). Indoor & outdoor units selection: There are versatile indoor units and different outdoor units for choosing. Piping drawing: Displays the detailed layout of an A/C system and the parameters for piping and branch distributors. Controller selection: Provides a selection of controllers for indoor units and outdoor units, including wireless and remote controllers for indoor units. Report output: Outputs a comprehensive selection report as a Word or Excel document. CAD Version AutoCAD add-on software Automatic Calculation: Refrigerant & drain pipe size Automatic Selection: Distributor kit & branch joint System Check: Installation regulation & refrigerant addition Automatic Report: Piping installation diagram, equipment list & quotation HRV | 101 Heat Recovery Ventilation Units (HRV) Larger air supply rate enhanced heat exchange efficiency enhanced energy saving The heat recovery ventilation unit (HRV) can regain heat energy lost through ventilation and reduce the room temperature fluctuation caused by ventilation process. By utilizing the most advanced technology and technics, Bosch HRV has extremely good performance. The heat exchanger core is made of special paper processed with chemical treatment, which could realize better temperature and humidity control of the room environment. Temperature exchange efficiency is above 65 % and enthalpy exchange efficiency between 50 – 65 %. Model Names HRV200-1 HRV500-1 HRV1500-3 HRV300-1 HRV800-1 HRV2000-3 HRV400-1 HRV1000-1 RA (Returm air from room) SA Heat Moisture u 14。 C Cold air SA 0 0°C EA 6。 C Heat (Supply air to room) Moisture Warm air 。 20°C C Heat exchange plate EA (Exhaust air to outdoors) OA (Fresh air from outdoors) Low noise Sound proof material is used to guarantee quiet operation. Compact design, flexible installation and easy maintenance With a minimum height of only 264 mm and 23 kg weight, the unit provides best convenience and possibility for installation in limited spaces (HRV200-1 model). 102 | HRV Multi-modes for different Situations Heat exchange mode Heat exchange mode Damper When air flow formed by the fans goes through the heat exchanged core in cross way, due to temperature EA R difference between two channels of the core, thermal Element transmission happens naturally. In summer days, high temperature outdoor air gets cooled by indoor OA S exhaust air; in winter, low temperature outdoor air gets heated by indoor exhaust air. So the energy contained in exhaust air can be reclaimed and energy efficiency Bypass mode Damper gets improved. R EA Element Bypass mode OA In mild climate areas or seasons, when temperature and humidity level difference between indoor and outdoor is small, the unit works as a conventional ventilation fan. Both supply fan and exhaust fan work at the same speed (Hi/mid/low/auto). Air supply mode It is one kind of bypass mode with air supply fan speed higher than exhaust fan speed. It can be used in mild climate areas where a large amount of fresh air is needed. Exhaust air mode Auto mode It is also one kind of bypass mode with The controller chooses heat exchange mode exhaust fan speed higher than air supply fan or bypass mode according to the temperature speed. It can be used in mild climate areas difference between outdoor and indoor tem- where a large amounf ot exhaust air needs to perature. Both the two fans work at low speed. be expelled. S HRV | 103 Flexible Control Interlocking control with other indoor units by controller is possible. EA OA Duct IDU RA SA IDU Centralized control SA CC-WT IDU = VRF Indoor Unit SA = Supply Air RA = Return Air OA = Outdoor Air (Fresh Air) EA = Exhaust Air 104 | HRV Specifications Model Power supply Cooling Heating Sound pressure level V/Ph/Hz Temperature exchange efficiency Enthalpy exchange efficiency Temperature exchange efficiency Enthalpy exchange efficiency Heat exchange mode Bypass mode HRV200-1 HRV300-1 HRV400-1 HRV500-1 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 High % 55 55 55 55 Medium % 55 55 55 55 Low % 60 60 60 60 High % 50 50 50 50 Medium % 50 50 50 50 Low % 55 55 55 55 High % 60 60 60 65 Medium % 60 60 60 65 Low % 65 65 65 70 High % 55 55 60 60 Medium % 55 55 60 60 Low % 60 60 65 65 High dB(A) 27 30 32 35 Medium dB(A) 26 29 31 34 Low dB(A) 20 23 25 28 High dB(A) 28 31 33 36 Medium dB(A) 27 30 32 35 Low dB(A) 22 25 27 30 Net dimension (W×D×H) mm 866×655×264 944×722×270 944×927×270 1038×1026×270 Packing size (W×D×H) mm 930×730×445 1010×800×450 1010×1010×450 1120×1120×452 Net/gross weight kg 23/40 26/44 31/52 41/64 Casing Galvanized steel plate Heat exchange system Air to air cross flow total heat (sensible heat + latent heat) exchange Heat exchange element material Specially processed nonflammable paper Type Airflow rate Fan ESP Centrifugal fan High m3/h 200 300 400 500 Medium m3/h 200 300 400 500 Low m3/h 150 225 300 375 High Pa 75 75 80 80 Medium Pa 58 60 65 68 Low Motor output Pa 35 40 43 45 W 20 40 80 120 Ф144 Ф144 Ф144 Ф194 Duct diameter mm Operating temperature range °C Notes: 1. For the units model of HRV (200 – 1000), there are 3-speed adjustable air volume (Hi, Med, Low), but for the units model of HRV (1500 – 2000), there are only 1-speed which cannot be adjusted. 2. Sound level is measured at 1.4m below the center of the body in an anechoic chamber. 3. Efficiency is measured under the following conditions: * Cooling Condition: Air Exhaust Temp. 27°C DB, 19.5°C WB., Fresh Air Temp. 35°C DB, 28°C WB. * Heating Condition: Air Exhaust Temp. 21°C DB, 13°C WB., Fresh Air Temp. 5°C DB, 2°C WB. -7~43 DB, 80 % RH or less HRV | 105 Model Power supply Cooling Heating Sound pressure level V/Ph/Hz Temperature exchange efficiency Enthalpy exchange efficiency Temperature exchange efficiency Enthalpy exchange efficiency Heat exchange mode Bypass mode HRV800-1 HRV1000-1 HRV1500-3 HRV2000-3 220-240/1/50 220-240/1/50 380-415/3/50 380-415/3/50 55 High % 55 55 55 Medium % 55 55 – – Low % 60 60 – – 50 High % 50 50 50 Medium % 50 50 – – Low % 55 55 – – 65 High % 65 65 65 Medium % 65 65 – – Low % 70 70 – – 60 High % 60 60 60 Medium % 60 60 – – Low % 65 65 – – 53 High dB(A) 39 40 51 Medium dB(A) 38 39 – – Low dB(A) 32 33 – – 54 High dB(A) 40 41 52 Medium dB(A) 39 40 – – Low dB(A) 34 35 – – Net dimension (W×D×H) mm 1286×1006×388 1286×1256×388 1600×1270×540 1650×1470×540 Packing size (W×D×H) mm 1380×1100×573 1390×1350×580 1680×1350×720 1760×1580×720 Net/gross weight kg 62/88 79/110 163/224 182/247 Casing Galvanized steel plate Heat exchange system Air to air cross flow total heat (sensible heat + latent heat) exchange Heat exchange element material Specially processed nonflammable paper Type Airflow rate Fan ESP Motor output Centrifugal fan High m3/h 800 1000 1500 2000 Medium m3/h 800 1000 – – Low m3/h 600 750 – – High Pa 100 100 160 170 Medium Pa 82 85 – – Low Pa 54 58 – – W 360 360 450 450 Ф242 Ф242 346×326 346×326 Duct diameter mm Operating temperature range °C Notes: 1. For the units model of HRV (200 – 1000), there are 3-speed adjustable air volume (Hi, Med, Low), but for the units model of HRV (1500 – 2000), there are only 1-speed which cannot be adjusted. 2. Sound level is measured at 1.4m below the center of the body in an anechoic chamber. 3. Efficiency is measured under the following conditions: * Cooling Condition: Air Exhaust Temp. 27°C DB, 19.5°C WB., Fresh Air Temp. 35°C DB, 28°C WB. * Heating Condition: Air Exhaust Temp. 21°C DB, 13°C WB., Fresh Air Temp. 5°C DB, 2°C WB. -7~43 DB, 80 % RH or less Joints Joints | 107 Joints Dimensions 108 Joints 110 Dimensions 108 | Joints Joints Branch joints of two-pipe system (Heat Pump VRF) Model Appearance Branch joint for outdoor unit Branch joint for indoor unit X: The total capacity of indoor units which is connected to this branch joint Model name Packing Size (mm)/ Gross Weight (kg) Description ODU-BJ02 255×150×185/1.5 For two outdoor units connection ODU-BJ03 345×160×285/3.4 For three outdoor units connection ODU-BJ04 475×165×300/4.8 For four outdoor units connection IDU-BJ01 290×105×100/0.4 X <16.6 kW IDU-BJ02 290×105×100/0.6 16.6 ≤ X <33 kW IDU-BJ03 310×130×125/0.9 33 kW ≤ X <66 kW IDU-BJ04 350×180×170/1.5 66 kW ≤ X <92 kW IDU-BJ05 365×195×215/1.9 92 kW ≤ X Joints | 109 Branch joints of three-pipe system (Heat Recovery VRF) Model Appearance Branch joint between outdoor unit Branch joint between SBOX and outdoor unit Branch joint between SBOX and indoor unit X: The total capacity of indoor units which is connected to this branch joint Model name Packing Size (mm)/ Gross Weight (kg) Description ODU-BJR02 272×167×232/2.2 For two outdoor units connection ODU-BJR03 472×157×312/5.0 For three outdoor units connection ODU-BJR04 745×160×335/7.5 For four outdoor units connection IDU-BJR01 257×127×107/0.8 X <16.6 kW IDU-BJR02 287×137×107/0.9 16.6 ≤ X <33 kW IDU-BJR03 297×167×177/1.4 33 kW ≤ X <66 kW IDU-BJR04 372×197×187/2.3 66 kW ≤ X <92 kW IDU-BJR05 432×222×227/3.3 92 kW ≤ X IDU-BJ01 290×105×100/0.4 X <16.6 kW ID:15.9 ID:25.4 ID:22.2 OD:22.2 ID:22.2 OD:22.2 (ID:19.1) ID:15.9 ID:44.5 ID:41.3 OD:19.1 (ID:15.9) ID:12.7 ID:9.5 ID:34.9 OD:34.9 ID:22.2 ID:19.1 OD:19.1 ID:19.1 OD:19.1 (ID:15.9) ID:12.7 ID:38.1 ID:34.9 OD:34.9 OD:34.9 ID:28.6 OD:15.9 (ID:12.7) ID:9.5 ID:6.4 OD:28.6 ID:22.2 ID:19.1 ID:15.9 ID:15.9 ID:19.1 OD:15.9 ID:15.9 OD:15.9 (ID:12.7) ID:9.5 ID:31.8 ID:28.6 OD:28.6 ID:28.6 OD:28.6 ID:22.2 ID:19.1 OD:12.7 ID:9.5 ID:6.4 OD:22.2 (ID:19.1) ID:15.9 ID:12.7 ID:9.5 ID:12.7 OD:12.7 ID:12.7 OD:12.7 ID:9.5 ID:6.4 ID:25.4 ID:22.2 OD:22.2 ID:22.2 OD:22.2 (ID:19.1) ID:15.9 OD:9.5 ID:9.5 ID:6.4 OD:19.1 (ID:15.9) ID:12.7 ID:9.5 OD:12.7 ID:9.5 OD:9.5 ID:6.4 ID:15.9 ID:19.1 OD:19.1 ID:19.1 OD:19.1 (ID:15.9) ID:12.7 Gas side joints OD:22.2 (ID:19.1) IDU-BJ05 OD:41.3 ID:44.5 ID:41.3 ID:28.6 ID:22.2 Branch model ID:12.7 ID:41.3 ID:22.2 ID:19.1 IDU-BJ04 ID:34.9 ID:34.9 110 | Joints Dimensions Indoor branch joints Liquid side joints IDU-BJ01 IDU-BJ02 IDU-BJ03 Joints | 111 Outdoor branch joints Branch model Gas side joints Liquid side joints ID:31.8 0D:31.8 ID:25.4 0D:15.9 ID:34.9 Q2 Q1 ID:34.9 0D:31.8 0D:31.8 ID:19.1 0D:15.9 0D:15.9 ID:15.9 ID:12.7 0D:34.9 ID:19.1 Y2 Y6 Q7 Y1 ID:38.1 ID:31.8 ID:31.8 ID:15.9 ID:15.9 ID:34.9 0D:31.8 ODU-BJ03 ID:15.9 ID:15.9 ID:31.8 Q2 ID:25.4 Y3 ID:22.2 ID:12.7 ID:25.4 Q1 Y1 ID:38.1 ID:31.8 0D:19.1 Y6 Q3 ID:31.8 ID:25.4 ID:19.1 Y2 Q4 ODU-BJ02 ID:15.9 ID:12.7 0D:34.9 0D:15.9 ID:12.7 ID:38.1 ID:19.1 ID:41.3 ID:22.2 0D:22.2 Y7 Q5 Y4 ID:19.1 Y1 Q1 ID:31.8 ID:15.9 0D:31.8 ID:12.7 ID:31.8 ID:25.4 0D:31.8 ID:15.9 0D:15.9 ID:31.8 ID:25.4 0D:15.9 0D:34.9 ID:12.7 Q2 ID:38.1 ID:15.9 ID:15.9 ID:34.9 0D:31.8 ID:25.4 Y6 Y1 ID:31.8 ID:31.8 ID:19.1 Y2 Q7 Q1 ID:15.9 0D:15.9 ID:12.7 ID:19.1 ID:38.1 ID:22.2 ID:41.3 Y7 ODU-BJ04 Q5 Y1 Q1 ID:31.8 0D:15.9 ID:12.7 ID:31.8 ID:25.4 ID:15.9 ID:15.9 0D:31.8 ID:41.3 ID:44.5 ID:22.2 Q6 Q1 Y8 0D:25.4 Y5 ID:22.2 ID:31.8 ID:31.8 ID:25.4 Description ID:25.4 Y1 ID:15.9 0D:31.8 ID:12.7 ID:15.9 0D:15.9 Bosch Thermotechnik GmbH Junkersstraße 20-24 73249 Wernau/Germany
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : No XMP Toolkit : 3.1-701 Producer : Acrobat Distiller 7.0.5 (Windows) Trapped : False Create Date : 2015:08:18 12:01:26+02:00 Metadata Date : 2015:08:18 12:00:29+02:00 Modify Date : 2015:08:18 12:01:26+02:00 Creator Tool : Adobe InDesign CS6 (Macintosh) Instance ID : uuid:190e27cd-5222-4e9d-8e75-1f6d1233906b Document ID : xmp.id:21CD81F617206811822AAC3B8A4DC2C1 Rendition Class : proof:pdf Original Document ID : adobe:docid:indd:e8268213-9827-11dc-a256-ad3cfdcdc22c Derived From Instance ID : xmp.iid:C21DD03F29206811808386F82020FE7E Derived From Document ID : xmp.did:C1244366312068118083D45EE5D4D9F7 Derived From Original Document ID: adobe:docid:indd:e8268213-9827-11dc-a256-ad3cfdcdc22c Derived From Rendition Class : default History : Format : application/pdf Title : Bosch_Climate_5000_VRF_Catalogue_English_EN_ES.pdf Creator : JuelligMike Slug : , , , Page Count : 112 Author : JuelligMike
EXIF Metadata provided by EXIF.tools