- Manuals
- Brands
- CAREL Manuals
- Controller
- uC2SE
Manuals and User Guides for CAREL uC2SE. We have 2 CAREL uC2SE manuals available for free PDF download: User Manual
µC2SE for process chiller electronic control User manual ENGLISH IMPORTANT WARNINGS CAREL bases the development of its products on several years’ experience in the HVAC field, on continuous investment in technological innovation of the product, on rigorous quality procedures and processes with in-circuit and function tests on 100% of its production, on the most innovative production technologies available on the market. CAREL and its branch offices/affiliates do not guarantee, in any case, that all the aspects of the product and the software included in the product will respond to the demands of the final application, even if the product is built according to state-of-the-art techniques. The client (builder, developer or installer of the final equipment) assumes every responsibility and risk relating to the configuration of the product in order to reach the expected results in relation to the specific final installation and/or equipment. CAREL in this case, through specific agreements, can intervene as consultant for the positive result of the final start-up machine/application, but in no case can it be held responsible for the positive working of the final equipment/apparatus. The CAREL product is a state-of-the-art product, whose operation is specified in the technical documentation supplied with the product or can be downloaded, even prior to purchase, from the website www . carel. com. Each CAREL product, in relation to its advanced technological level, needs a phase of definition / configuration / programming / commissioning so that it can function at its best for the specific application. The lack of such phase of study, as indicated in the manual, can cause the final product to malfunction of which CAREL can not be held responsible. Only qualified personnel can install or carry out technical assistance interventions on the product. The final client must use the product only in the manner described in the documentation related to the product itself. Without excluding proper compliance with further warnings present in the manual, it is stressed that in any case it is necessary, for each Product of CAREL: • To avoid getting the electrical circuits wet. Rain, humidity and all types of liquids or condensation contain corrosive mineral substances that can damage the electrical circuits. In any case, the product should be used and stored in environments that respect the range of temperature and humidity specified in the manual. • Do not install the device in a particularly hot environment. Temperatures that are too high can shorten the duration of the electronic devices, damaging them and distorting or melting the parts in plastic. In any case, the product should be used and stored in environments that respect the range of temperature and humidity specified in the manual. • Do not try to open the device in any way different than that indicated in the manual. • Do not drop, hit or shake the device, because the internal circuits and mechanisms could suffer irreparable damage. • Do not use corrosive chemical products, aggressive solvents or detergents to clean the device. • Do not use the product in application environments different than those specified in the technical manual. All the above reported suggestions are valid also for the control, serial unit, programming key or nevertheless for any other accessory in the product portfolio of CAREL. CAREL adopts a policy of continuous development. Therefore, CAREL reserves the right to carry out modifications and improvements on any product described in the present document without prior notice. The technical data in the manual can undergo modifications without obligation to notice. The liability of CAREL in relation to its own product is regulated by CAREL’s general contract conditions edited on the website www .carel. com and/or by specific agreements with clients; in particular, within the criteria consented by the applicable norm, in no way will CAREL, its employees or its branch offices/affiliates be responsible for possible lack of earnings or sales, loss of data and information, cost of substitute goods or services, damage to things or persons, work interruptions, or possible direct, indirect, incidental, patrimonial, of coverage, punitive, special or consequential in any way caused damages, be they contractual, out-of-contract, or due to negligence or other responsibility originating from the installation, use or inability of use of the product, even if CAREL or its branch offices/affiliates have been warned of the possibility of damage. 2. 3. 4. 5. Disposal of the product In reference to European Community directive 2002/96/EC issued on 27 January 2003 and the related national legislation, please note that: 1. we cannot be disposed of as municipal waste and such waste must be collected and disposed of separately; the public or private waste collection systems defined by local legislation must be used. In addition, the equipment can be returned to the distributor at the end of its working life when buying new equipment. the equipment may contain hazardous substances: the improper use or incorrect disposal of such may have negative effects on human health and on the environment; the symbol (crossed-out wheeled bin) shown on the product or on the packaging and on the instruction sheet indicates that the equipment has been introduced onto the market after 13 August 2005 and that it must be disposed of separately; in the event of illegal disposal of electrical and electronic waste, the penalties are specified by local waste disposal legislation. µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 3 ENGLISH 4 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 CONTENTS 7 ENGLISH 1. INTRODUCTION 1.1 General description ..............................................................................................................................7 1.2 User interface ........................................................................................................................................7 2. CONNECTIONS 9 2.1 General diagram ...................................................................................................................................9 2.2 Network layout .....................................................................................................................................9 3. APPLICATIONS 10 3.1 AIR/WATER chiller.................................................................................................................................10 3.2 WATER/WATER chiller .........................................................................................................................11 4. PARAMETERS 13 4.1 General parameters .............................................................................................................................13 4.2 Menu structure .....................................................................................................................................13 4.3 Parameter tables ..................................................................................................................................14 5. DESCRIPTION OF THE PARAMETERS 23 6. TABLE OF ALARMS 48 7. CONNECTIONS, ACCESSORIES AND OPTIONS 52 7.1 Connection diagram ..............................................................................................................................52 7.2 Expansion card .......................................................................................................................................53 7.3 EVD4*: Electronic expansion valve driver ........................................................................................53 7.4 Fan speed control board (code MCHRTF*).....................................................................................54 7.5 Fan ON/OFF control board (code CONVONOFF0) ......................................................................54 7.6 PWM to 0 to 10Vdc (or 4 to 20 mA)conversion board for fans ............................................... (code CONV0/10A0)....................................................................................................................................54 7.7 Minimum and maximum fan speed calculation .............................................................................54 7.8 Programming key (code PSOPZKEYA0) ...........................................................................................55 7.9 RS485 serial options..............................................................................................................................56 7.10 Terminals ................................................................................................................................................56 8. DIMENSIONS 57 9. CODES 59 10. TECHNICAL SPECIFICATIONS AND SOFTWARE UPDATES 59 10.1 Technical specifications .....................................................................................................................59 10.2 Software updates................................................................................................................................60 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 5 ENGLISH 6 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 ENGLISH 1. INTRODUCTION 1.1 General description The μC2SE is a compact CAREL electronic controller, the same size as a normal thermostat, for the complete management of process chillers: it can control air-water and water-water. 1.1.1 Main functions • • • • • • control of the water inlet and evaporator outlet temperature; defrost management by time and/or by temperature or pressure; fan speed control; complete alarm management; connection to serial line for supervision/telemaintenance; elimination of the expansion vessel. - Driver function • Management of electronic expansion valves. 1.1.2 Controlled devices • • • • • compressor; condenser fans; water pumps for evaporator and/or condenser; antifreeze heater; alarm signal device. 1.1.3 Programming CAREL offers the possibility to configure all the unit parameters not only from the keypad on the front panel, but also using: • a hardware key; • a serial line. 1.2 User interface 1.2.1 Display The display features 3 digits, with the display of the decimal point between -99.9 and 99.9. Outside of this range of measurement, the value is automatically displayed without the decimal (even if internally the unit still operates considering the decimal part). In normal operation, the value displayed corresponds to the temperature read by probe B1, that is, the evaporator water inlet temperature. Fig. 1.a show the symbols present on the display and on the keypad and their meanings. Fig. 1.a 1; 2 1; 3 A B C D E F G H amber amber amber amber amber amber amber red amber amber compressor 1 and/or 2 ON compressor 3 and/or 3 ON at least one compressor ON pump ON condenser fan ON defrost active heater ON alarm active heat pump mode chiller mode µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 with LED flashing start up request start up request start up request defrost request heat pump mode request chiller mode request K F Display with 3 green digits (plus sign and decimal point), amber symbols and red alarm symbols. meaning with LED ON L G 1.2.2 Symbols on the display colour J H E D C B A symbol I reference refrigerant circuit 1 2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 Table 1.a 7 ENGLISH 1.2.3 Functions associated with the buttons button I L I+L J K unit status Loading default values Go up a sub-group inside the programming area, until exiting (saving changes to EEPROM) In the event of alarms, mute the buzzer (if present) and deactivate the alarm relay Access the direct parameters Select item inside the programming area and display value of direct parameters/confirm the changes to the parameters Program parameters afters entering password Select top item inside the programming area Increase value Switch from standby to chiller mode (P6=0) and vice versa Provides immediate access to the condenser and evaporator pressure and temperature probes and DTE, DTC1-2 Select bottom item inside the programming area Decrease value Provides immediate access to the condenser and evaporator pressure and temperature probes and DTE, DTC1-2 J+K Manual alarm reset Immediately reset the hour counter (inside the programming area) L+J Force manual defrost on both circuits button press press at power ON press once press once press for 5 s press once press for 5 s press once or press and hold press once or press and hold press for 5 s press once press once or press and hold press once or press and hold press once press for 5 s press for 5 s press for 5 s Table 1.b 1.2.4 Programming and saving the parameters 1. 2. 3. 4. 5. 6. 7. 8. 9. press “ “ and “ ” for 5 seconds; the heating and cooling symbol and the figure “00” are displayed; use “ ” and “ ” to set the password (page 28) and confirm by pressing “ ”; use “ ” and “ ” to select the parameter menu (S-P) or levels (L-P) and then press “ ”; use “ ” and “ ” to select the parameter group and then press “ ”; use “ ” and “ “ to select the parameter and then press “ ”; after making the changes to the parameter, press “ ” to confirm or “ ” to cancel the changes; press “ ” to return to the previous menu; to save the modifications, press “ ” repeatedly until reaching the main menu. Note: a. the parameters that have been modified without being confirmed using the “ ” button return to the previous value; b. if no operations are performed on the keypad for 60 seconds, the controller exits the parameter modification menu by timeout and the changes are cancelled. 1.2.5. Keypad The keypad is used to set the unit operating values (see Parameters/alarms - Keypad combinations) 8 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 2.1 General diagram EVD*40*: driver for electronic expansion valve Optional board MCH200002*: I/O expansion board for µ2SE PSOPZKEY*: programming key CONVONOFF*: PWM/digital converter PW/Modbus® RTU CAREL Supervisory CONV0/10A0*: PWM/analogic converter NTC: temperature probes MCHRTF**A0: fan speed regulator MCH200485* RS485 serial card MCH2*T*: terminal PW/Modbus® RTU CAREL Supervisory MCH2*TSV*: adapter SPKT: 0 to 5 V pres. transducer Fig. 2.a 2.2 Network layout EV driver Fig. 2.b EV driver ESP. EV driver Fig. 2.c 2 µC SE process chiller +030220416 - rel. 1.1 - 27.04.2010 EVD*40*: driver for electronic expansion valve 9 ENGLISH 2. CONNECTIONS ENGLISH 3. APPLICATIONS 3.1 AIR/WATER chiller 3.1.1 Single circuit Key: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 condernser fan overload fan condenser probe flow switch outlet evaporator probe fan antifreeze heater inlet evaporator probe compressor 1 high pressure compressor overload low pressure water pump compressor 2 2 3 4 5 6 7 8 9 13 11 10 12 14 Fig. 3.a.a 3.1.2 Two circuits, 2 condenser fan circuits and 2 evaporators Key: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 1 condenser fan overload 1 and 2 fan 1 and 2 condenser probe 1 and 2 flow switch outlet temperature probe evaporator 1 and 2 outlet evaporator probe 1 and 2 antefreeze heater 1 and 2 compressor 1 high pressure 1 and 2 compressor overload 1 and 2 low pressure 1and 2 inlet evaporator probe compressor 2 water pump compressor 3 compressor 4 1 1 2 1 4 2 1 5 3 1 6 8 9 1 14 1 1 2 7 2 8 6 2 16 13 1 11 12 2 3 2 7 10 2 12 11 1 15 10 17 Fig. 3.a.b 10 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 1 Key: 1 3 3 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 2 4 5 1 6 7 1 8 1 7 2 2 6 8 condenser fan overload fan condenser probe 1 and 2 flow switch outlet temperature probe evaporator 1 and 2 outlet evaporator probe 1 and 2 antifreeze heater 1 and 2 compressor 1 high pressure 1 and 2 compressor overload 1 and 2 low pressure 1and 2 inlet evaporator probe compressor 2 water pump compressor 3 compressor 4 2 9 16 13 10 1 1 11 12 2 1 11 12 15 2 10 2 17 14 Fig. 3.a.c 3.2 WATER/WATER chiller 3.2.1 Single circuit Key: 1 2 3 4 5 6 7 8 9 10 11 12 13 3 1 4 2 5 6 7 8 10 9 11 12 13 Fig. 3.b.a µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 11 water condensing temperature probe condensator flow switch outlet evaporator probe evaporator antifreeze heater inlet evaporator probe compressor 1 high pressure compressor overload low pressure water pump compressor 2 ENGLISH 3.1.3 Two circuits, 1 condenser fan circuit ENGLISH 3.2.2 Two circuits Key: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 water condensing temperature probe 1 and 2 condensator 1 and 2 flow switch outlet evaporator probe evaporator antifreeze heater 1 and 2 compressor 1 high pressure 1 and 2 compressor overload 1 and 2 low pressure 1 and 2 inlet evaporator probe water pump compressor 2 compressor 3 compressor 4 3 1 4 1 2 1 1 2 2 2 6 5 14 7 11 8 1 9 1 10 2 1 10 9 8 2 2 12 13 15 12 Fig. 3.b.b 3.2.3 Two circuits, 2 evaporators Key: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 3 water condensing temperature probe 1 and 2 condensator 1 and 2 flow switch outlet temperature probe outlet evaporator probe 1 and 2 antifreeze heater 1 and 2 evaporator water pump compressor 1 high pressure 1 and 2 compressor overload 1 and 2 low pressure 1 and 2 compressor 3 compressor 2 compressor 4 inlet evaporator pressure 4 1 1 1 5 1 2 2 5 2 2 1 1 6 7 2 1 6 7 2 9 13 16 10 1 1 11 12 2 1 12 11 2 10 2 8 15 14 8 Fig. 3.b.c 12 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 2 ENGLISH 4. PARAMETERS 4.1 General parameters The parameters are divided into 4 different types, according to their level of access by the user (password) and their function. For each level, only the access to the parameters of the same or lower level can be set. This means that through “factory” password, acessing the menù “levels” (L-P), it is possible to set the desired level for each parameter. • Factory parameters: Accessible with the 66 “Factory” password, allow the configuration of all the unit parameters. • Super User parameters: Accessible with the 11 “Super User” password, allow the configuration of the Super User, User and Direct parameters. • User parameters: Accessible with password 22, allow the configuration of the parameters that typically can be set by the user (User parameters) and the Direct parameters, consequently relating to the options. • Direct parameters: Accessible without password, this are used to read the probe measurements and any data, by any user, without compromising the operation of the unit. N.B.: The modifications to the parameters regarding the configuration of the unit (type, number of compressors,...) must be performed with the controller in Standby. level _d_ _U_ _S_ _F_ 4.2 Menu structure password no password 22 11 66 F or 5” main menù Sa ve in the EEPROM level name direct user super user factory And F or 5” setting password Or Or parameter values parameter level parameters /* parameters F-r* parameters A* probe settings software antifreeze t* parameters clock settings parameters b* probes parameters r* regulation parameters c* compressor parameters P* alarm parameters D* parameters H* defrost parameters F* unit setting fan parameter values F1 parameters F1 level value F1 Or parameters Fn Fig. 4.a 2 µC SE process chiller +030220416 - rel. 1.1 - 27.04.2010 13 4.3 Parameter tables ENGLISH The following tables show of the parameters divided by type/family (e. g. compressor, probes, fans etc.). • Key to the parameter tables Level (default) S= super user F= factory D= direct Visibility: The visibility of some groups depends on the type of controller and the value of the parameters. D= defrost (if D01=1) F= fan (if F01=1) L= low noise (if F15=1-3) N= NTC probe (if /04-/08=2) P= pressure (if /04-/08=3) V= driver (if H08 =1-3) X= expansion (if H08=2-3) M= pump down (if D17=1) W= watch (if the clock board is fitted) - = always present Supervisor variables: R/W = supervisor read/write parameter R= supervisor read-only parameter 4.3.1 Evaporator and condenser temperature and pressure values: (d*) display indicat. dtE dC1 dC2 parameter and description default level D D D Current value of DTE Current value of DTC1 Current value of DTC2 min. max. 0 0 0 0 0 0 UOM variat. default visibility supervis. variable 0 99 (R) 0 100 (R) 0 101 (R) Modbus variable type 99 Analog 100 Analog 101 Analog Tab. 4.a 4.3.2 Probe setting parameters: (/*) display indicat. /01 /02 /03 /04 /05 /06 /07 /08 /09 /10 /11 /12 /13 /14 /15 /16 /17 /18 /19 /20 /21 /22 /23 parameter and description Probe type B1 0= not present 1= present Probe type B2 0= not present 1= present Probe type B3 0= not present 1= NTC Cond. Probe 2= NTC Out. Probe 3= differential control probe Probe type B4 0= not present 1= ON/OFF (D.I) 2= NTC Out. Probe 3= ratiometric cond. Probe, 5 Vdc 4= differential control probe Probe type B5 0= not present 1= present Probe type B6 0= not present 1= present Probe type B7 0= not present 1= NTC Cond. Probe 2= NTC Out. Probe 3= differential control probe Probe type B8 0= not present (expansion) 1= ON/OFF 2= NTC Out. Probe 3= ratiometric cond. Probe, 5 Vdc 4= differential control probe NB. if more than one differential control probe is configured, the priority is: B8, B7, B4, B3 Min. value voltage input Max. value voltage input Pressure min. value Pressure max. value Probe B1 calibration Probe B2 calibration Probe B3 calibration Probe B4 calibration Probe B5 calibration Probe B6 calibration Probe B7 calibration Probe B8 calibration Digital filter Input limitation Unit of measure 0= °C 1= °F default level F min. max. UOM variat. default 1 visibility supervis. variable 1 (R/W) 0 1 Flag 1 F 0 1 Flag F 0 3 F 0 F Modbus 1 variable type Digital 1 0 - 2 (R/W) 2 Digital int 1 0 - 14 (R/W) 221 Integer 4 int 1 0 - 15 (R/W) 222 Integer 0 1 Flag 1 0 X 3 (R/W) 3 Digital F 0 1 Flag 1 0 X 4 (R/W) 4 Digital F 0 3 int 1 0 X 16 (R/W) 223 Integer F 0 4 int 1 0 X 17 (R/W) 145 Integer F F F F F F F F F F F F U U U 0 /09 0 /11 -12.0 -12.0 -12.0 -12.0 -12.0 -12.0 -12.0 -12.0 1 1 0 /10 500 /12 999 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 15 15 1 0.01 Vdc 0.01 Vdc bar bar °C/°F °C/°F °C/°F °C/bar/°F °C/°F °C/°F °C/°F °C/bar/°F Flag 1 1 1 1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 1 1 1 50 450 0 345 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 4 8 0 P P P P X X X X - 18 (R/W) 19 (R/W) 1 (R/W) 2 (R/W) 3 (R/W) 4 (R/W) 5 (R/W) 6 (R/W) 7 (R/W) 8 (R/W) 9 (R/W) 10 (R/W) 20 (R/W) 21 (R/W) 5 (R/W) 225 226 1 2 3 4 5 6 7 8 9 10 227 228 5 Integer Integer Analog Analog Analog Analog Analog Analog Analog Analog Analog Analog Integer Integer Digital Table. 4.b 14 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 display indicat. A01 A02 A03 A05 A06 A07 A08 A08 A09 A10 A11 A11 A14 parameter and description default level Alarm set point antifreeze/low ambient temperature (air/air) U Differential for antifreeze/low ambient temperature alarm (air/air) U Bypass time for antifreeze alarm/low ambient temp. when turning on the unit U in heating mode Diff. for antifreeze heater/auxiliary heater U Auxiliary heater probe F 0= Control probe see (see Table 5.a) 1= Antifreeze probe see (see Table 5.a) Antifreeze alarm set point limit F Auxiliary heater set point in heating mode U Antifreeze/support heater set point differential U Auxiliary heater differential in heating mode U Antifreeze automatic start up U 0= disabled function 1= Heaters and pump on at the same time on A4/A8 2= Heaters and pump on indipendently on A4/A8 3= Heaters ON on A4/A8 Auxiliary heater 2 set point in heating U Support heater 2 differential in heating U Antifreeze alarm set point from EVD U min. max. A04 1220 150 UOM variat. default visibility supervis. variable °C/°F 0.1 30 11 (R/W) °C °F 0.1 50 12 (R/W) s 1 0 22 (R/W) Modbus variable type 11 Analog 12 Analog 229 Integer A07 3 0 3 0 500 1 °C/°F Flag 0.1 1 10 0 - 14 (R/W) 6 (R/W) 14 6 Analog Digital -400 A01 0 3 0 1760 r16 200 500 3 °C °F °C °F °C °F °C/°F 0.1 0.1 0.1 0.1 1 -400 250 70 30 0 AA AR - 15 (R/W) 16 (R/W) 78 (R/W) 17 (R/W) 23 (R/W) 15 16 78 17 230 Analog Analog Analog Analog Integer A01 0 A07 r16 200 A04 °C/°F °C/°F °C/°F 0.1 0.1 0.1 250 70 30 AA AR - 67 (R/W) 79 (R/W) 82 (R/W) 67 79 82 Analog Analog Analog Table 4.c 4.3.4 Probe reading parameters (b*) display indicat. b00 b01 b02 b03 b04 b05 b06 b07 b08 b09 b10 b11 b12 b13 b14 b15 b16 b17 b18 b19 b20 parameter and description Config. of probe to be shown on the display 0= probe B1 1= probe B2 2= probe B3 3= probe B4 4= probe B5 5= probe B6 6= probe B7 7= probe B8 8= set point without compensation 9= dynamic set point with possible compensation 10= remote ON/OFF digital input status 11= µAD probe Value read by probe B1 Value read by probe B2 Value read by probe B3 Value read by probe B4 Value read by probe B5 Value read by probe B6 Value read by probe B7 Value read by probe B8 Driver 1 evaporator temperature Driver 1 evaporator pressure Driver 1 superheating Driver 1 saturation temperature Driver 1 valve position Driver 2 evaporator temperature Driver 2 evaporator pressure Driver 2 superheating Driver 2 saturation temperature Driver 2 valve position Temp. probe at the outlet of the external coil c1 Temp. probe at the outlet of the external coil c12 default level U min. max. U.O.M. variat. default 0 visibility supervis. Modbus variable 24 (R/W) 231 variable type integer 0 11 N 1 D D D D D D D D D D D D D D D D D D D D 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1000 0 0 0 0 1000 0 0 °C /°F °C /°F °C /°F °C /°F/Dbar °C /°F °C /°F °C /°F °C /°F/Dbar °C /°F Dbar °C /°F °C /°F % °C /°F Dbar °C /°F °C /°F % °C /°F °C /°F - 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 X X X X V V V V V XV XV XV XV XV V XV Analog Analog Analog Analog Analog Analog Analog Analog Analog Analog Analog Analog Analog Analog Analog Analog Analog Analog Analog Analog 102 (R) 103 (R) 104 (R) 105 (R) 106 (R) 107 (R) 108 (R) 109 (R) 110 (R) 111 (R) 112 (R) 113 (R) 114 (R) 115 (R) 116 (R) 117 (R) 118 (R) 119 (R) 120 (R) 121 (R) 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 Table 4.d 4.3.5 Compressor setting parameters (c*) display indicat. c01 c02 c03 c04 c05 c06 c07 c08 c09 c10 c11 c12 c13 c14 c15 c16 c17 c18 parameter and description default level Minimum on time U Minimum off time U Delay between 2 starts of the same compressor U Delay between starts of the 2 compressors U Delay between 2 shut-downs of the 2 compressors U Delay at start-up U Delay in switching on the compressor after switching on the pump/inlet U fan (air/air) Delay in switching OFF the compressor after switching OFF the pump/ U inlet fan (air/air) Maximum compressor operating time in tandem U Compressor 1 timer D Compressor 2 timer D Compressor 3 timer D Compressor 4 timer D Operation timer threshold U Hour counter evaporator pump/fan 1 D Hour counter condenser backup pump/fan 2 D Minimum time between 2 pump starts U Minimum pump ON time U min. max. U.O.M. variat. def. visib. Modbus - supervis. variable 25 (R/W) 26 (R/W) 27 (R/W) 28 (R/W) 29 (R/W) 30 (R/W) 31 (R/W) 232 233 234 235 236 237 238 variabile type Integer Integer Integer Integer Integer Integer Integer 0 0 0 0 0 0 0 999 999 999 999 999 999 999 s s s s s s s 1 1 1 1 1 1 1 60 60 360 10 0 0 20 0 150 min 1 1 - 32 (R/W) 239 Integer 0 0 0 0 0 0 0 0 0 0 60 8000 8000 8000 8000 100 8000 8000 150 15 min 100 hours 100 hours 100 hours 100 hours 100 hours 100 hours 100 hours min min 1 1 1 1 0 0 0 0 0 0 0 0 30 3 - 33 (R/W) 122 (R) 123 (R) 124 (R) 125 (R) 34 (R/W) 126 (R) 127 (R) 35 (R/W) 36 (R/W) 240 122 123 124 125 241 126 127 242 243 Integer Analog Analog Analog Analog Integer Analog Analog Integer Integer Table 4.e µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 15 ENGLISH 4.3.3 Antifreeze/support heater setting parameters (A*) ENGLISH 4.3.7 Fan setting parameters (F*) display parameter and description indicat. F01 Enable Fan output 0=not present 1=present F02 Fan operating mode 0= always ON 1= depending ON the compressor (in parallel operation mode) 2= depending ON the compressors in ON/OFF control 3= depending ON the compressors in speed control mode F03 Min. voltage threshold for Triac F04 Max. voltage threshold for Triac F05 Speed temp. set point in Cooling mode Pressure value for min. speed Cooling F06 Differential value for max. speed Cooling Pressure value for max. speed Cooling F07 Fan shut-down differential in Cooling mode Fan shut-down pressure in Cooling mode F12 Triac impulse duration (fan start) F14 Fan with high condensing temperature when starting F15 Low noise activation 0= deactivated 1= activated in cooling F16 Low noise diff. in cooling default level F min. max. U.O.M. variat. def. 0 visibility supervis. variable 10 (R/W) 0 1 Flag 1 U 0 3 Int F F U U U U U U F U U 0 F03 -400 /11 0 0 0 0 0 0 0 F04 100 1760 /12 500 300 500 F05 10 999 1 step step °C/°F Dbar °C/°F Dbar °C/°F Dbar s - F 0 500 °C/°F/bar 0.1 Modbus 10 variable type Digital 1 0 F 48 (R/W) 255 Integer 1 1 0.1 0.1 0.1 0.1 0.1 0.1 1 1 1 35 75 350 130 100 30 150 50 2 0 0 F F FN FP FN FP FN FP F FN F 49 (R/W) 50 (R/W) 24 (R/W) 23 (R/W) 26 (R/W) 25 (R/W) 28 (R/W) 27 (R/W) 52 (R/W) 91 (R/W) 85 (R/W) 256 257 24 23 26 25 28 27 259 298 292 Integer Integer Analog Analog Analog Analog Analog Analog Integer Integer Integer 0 L 35 (R/W) 35 Analog Table 4.g 4.3.8 Unit setting parameters (H*) display parameter and description indicat. H01 Unit model 2= air_water chiller 4= water_water chiller H02 Number of condensers 0=1 circuit; 1=2 circuits H03 Number of evaporators 0=1 evaporator; 1=2 evaporators H04 Number of compressors per circuit 0=1 comp. ON 1 circuit (single circuit) 1=2 comp. in tandem ON 1 circuit (single circuit) 2=1 comp. per circuit, 2 circuits (two circuits) 3=2 comp. in Tandem, 2 circuits (two circuits) 4=1 compressor and 1 Capacity step in one circuit 5=1 compressor and 1 capacity Step per circuit H05 Pump/outlet fan (Air/Air) mode (output N2) 0= absent 1= always ON 2= ON upon request of the controller 3= ON upon request of the controller and for set time H06 Cooling/Heating digital input 0= absent; 1= present H07 ON/OFF digital input 0= absent; 1= present H08 µC2 network configuration 0= µC2SE only 1= µC2SE + EVD 2= µC2SE + exp. 3= µC2SE + exp. + EVD 4= µC2SE + I/O 5= µC2SE + EVD + I/O 6= µC2SE + exp. + I/O 7= µC2SE + I/O + EVD + exp. H09 Lock keypad 0= disabled; 1= enabled H10 Serial address 0= use as terminal H11 Output modes (see Table 5.3 and following pag. 56) H12 Capacity-control and reversing valve logic 0= Both normally closed 1= Both normally open 2= Inversion valve normally open and capacity-control valve normally closed 3= Inversion valve normally closed and capacity-control valve normally open H13 Activate pump down H14 Minimum pump down pressure H15 Maximum pump down time H21 Second pump function 0= Disabled 1= Backup and weekly rotation 2= Backup and daily rotation 3= Condensing control on corresponding set point 4= Condensing control always on 16 default level F min. max. U.O.M. variat. def. 2 visibility supervis. variable 54 (R/W) 2 4 Flag 2 U 0 1 Flag F 0 1 F 0 F Modbus 261 variable type Integer 1 0 - 12 (R/W) 12 Digital Flag 1 0 - 13 (R/W) 13 Digital 5 Flag 1 0 - 55 (R/W) 262 Integer 0 3 Flag 1 1 - 56 (R/W) 263 Integer U 0 1 Flag 1 0 - 14 (R/W) 14 Digital U 0 1 Flag 1 0 - 15 (R/W) 15 Digital F 0 7 Flag 1 4 - 57 (R/W) 264 Integer U 0 1 Flag 1 1 - 16 (R/W) 16 Digital U 1 200 - - 1 - 58 (R/W) 265 Integer F F 0 0 12 3 Int Flag 1 1 0 1 - 59 (R/W) 60 (R/W) 266 267 Integer Integer F F F F 0 0 0 0 1 500 180 4 Dbar s int 1 0.1 1 1 0 20 30 0 V M M - 17 (R/W) 37(R/W) 61 (R/W) 62 (R/W) 17 37 268 269 Digital Analog Integer Integer µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 default level F min. max. U.O.M. variat. def. 0 visibility supervis. variable 18 (R/W) 0 1 Flag 1 F F 0 0 1 3 Flag Flag F 0 1 F 0 1 Modbus 18 variable type Digital 1 1 0 0 - 11 (R/W) 124 (R/W) 11 331 Digital Integer Flag 1 0 - 25 (R/W) 25 Digital Flag 1 0 - 26 (R/W) 26 Digital 4.3.9 Firmware parameters (F-r*) display indicat. H99 H98 H97 H96 H95 parameter and description Software version, Driver 2 Software version, Driver 1 Expansion software version Software version (displayed when powering up the instrument) I/O board software version default level D D D D min. max. U.O.M. variat. default visibility Modbus variable type X V XV supervis. variable 1 (R) 2 (R) 3 (R) 4 (R) 0 0 0 0 999 999 999 999 Int Int Int Int - 14 0 0 0 208 209 210 211 Integer Integer Integer Integer D 0 999 Int - 0 - 149 (R) 356 Integer Table 4.i 4.3.10 Alarm setting parameters (P*) display indicat. P01 P02 P03 P04 P05 P07 P08 P09 P10 P11 P12 P13 P14 P15 P16 P17 P18 P19 P20 P21 P22 P23 P24 P25 P26 P27 P28 P29 P30 P31 P32 parameter and description Flow switch alarm delay when starting the pump Flow switch alarm delay during steady operation Low pressure alarm delay at compressor start-up Enable compressor capacity-control with high pressure 0= capacity control deactivated 1= capacity-control with high pressure active 2= capacity-control with low pressure active 3= capacity-control with high and low pressure active Alarm reset 0= HP1-2/LP1-2/A1-2/Lt manual 1= HP1-2/LP1-2/A1-2/Lt automatic 2= HP1-2/A1-2/Lt manual LP1-2 automatic 3= HP1-2 manual LP1-2/A1-2/Lt automatic 4= HP1-2/LP1-2 manual A1-2/Lt automatic 5= HP1-2/LP1-2 (thrice per hour) manual A1-2/Lt automatic 6= HP1-2/LP1-2 (thrice per hour) manual; A1-2/Lt manual Low pressure alarm with pressure probe: 0= Disabled; 1= Enabled Digital input 1 selection 0= N 1=FL man. 2=FL auto. 3=TP man. 4=TP auto 5= TC1 man. 6= TC1 auto. 7= TC2 man. 8= TC2 auto. 9= Cool/heat 10= Cool/heat with 11= LA man. delay 12= LA auto. 13= 2° Set 14= 2° Set timer 15= stop defrost c.1 16= stop 17= start 18= start defrost c.2 19= step 1 defrost c.2 defrost c.1 20 = step 2 21= step 3 22= step 4 23= remote ON/OFF Digital input 2 selection Digital input 6 selection Digital input 7 selection Digital input 10 selection Configuration of B4 as P8 if /4=1 (digital input) Configuration of B8 as /8=1 (digital input) Select low pressure alarm 0= not active with compressor OFF 1= active with compressor OFF High temperature alarm set High temperature alarm delay at start-up High pressure alarm set from transducer System low temperature alarm set point Enable system start-up protection: 0= Disabled; 1= Enabled Alarm relay output logic: 0= normally de-activated; 1= normally activated Low pressure alarm delay at start-up Compressor in heat pump Low pressure alarm delay at compressor start-up in defrost Deactivate compressors with HP and LP capacity-control Select digital output 2 Select digital output 3 Select digital output 4 Select digital output 5 Select digital output 7 Select digital output 8 Select digital output 9 Select digital output 10 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 default level U U U U min. max. U.O.M. variat. def. 20 5 40 0 visibility supervis. variable 63 (R/W) 64 (R/W) 65 (R/W) P 66 (R/W) Modbus variable type 270 Integer 271 Integer 272 Integer 273 Integer 0 0 0 0 150 120 200 3 s s s Flag 1 1 1 1 F 0 6 Flag 1 0 - 67 (R/W) 274 Integer F F 0 0 1 23 Flag Int 1 1 0 0 P - 68 (R/W) 69 (R/W) 275 276 Integer Integer F F F F F F F 0 0 0 0 0 0 0 23 23 23 23 23 23 1 Int Int Int Int Int Int Flag 1 1 1 1 1 1 1 0 0 0 0 0 0 0 X X X X - 70 (R/W) 71 (R/W) 72 (R/W) 73 (R/W) 74 (R/W) 75 (R/W) 76 (R/W) 277 278 279 280 281 282 283 Integer Integer Integer Integer Integer Integer Integer U U F U U F U -400 0 P33 -400 0 0 0 1760 250 999 1760 1 1 200 °C/°F s Dbar °C/°F Flag s 0.1 1 0.1 0.1 1 1 1 280 30 200 100 0 0 40 AA P AA - 38 (R/W) 77 (R/W) 39 (R/W) 40 (R/W) 20 (R/W) 8 (R/W) 86 (R/W) 38 284 39 40 20 8 293 Analog Integer Analog Analog Digital Digital Integer U D F F F F F F F F 0 0 0 0 0 0 0 0 0 0 999 1 11 11 11 11 12 12 12 12 s Int Int Int Int Int Int Int Int 1 1 1 1 1 1 1 1 1 1 40 0 0 0 0 0 0 0 0 0 P X X X X 87 (R/W) 21 (R/W) 108 (R/W) 109 (R/W) 110 (R/W) 111 (R/W) 112 (R/W) 113 (R/W) 114 (R/W) 115 (R/W) 294 21 315 316 317 318 319 320 321 322 Integer Digital Integer Integer Integer Integer Integer Integer Integer Integer 17 ENGLISH display parameter and description indicat. H22 Disable load default values 0= Function disabled 1= Function enabled H23 Enable Modbus® H24 Set the mode of high temperature alarm 0= no stop 1= high temperature stops compressor 2= low temperature stops compressor 3= high and low temperature stops H25 Hot as bypass function enable 0= disable; 1= enable H26 Special stand by mode enable 0= disable; 1= enable Table 4.h ENGLISH display indicat. P33 P34 P35 P36 P37 P38 P39 P40 P41 P42 P43 P44 P45 P46 parameter and description Low pressure alarm threshold Select digital input 5 Mute alarm with “mute“ button: 0= no; 1= yes Type of high pressure alarm management 0= always; 1= only if compressor active and 2 s after activation Select digital input 11 Select digital input 12 Select digital input 13 Select digital input 14 Select digital input 15 Select digital output 11 Select digital output 12 Select digital output 13 Select digital output 14 Select digital output 15 default level F F F F min. max. U.O.M. variat. def. 10 23 0 0 visibility supervis. variable P 76 (R/W) 122 (R/W) 23 (R/W) 24 (R/W) Modbus variable type 76 Analog 329 Integer 23 Digital 24 Digital 0 0 0 0 P18 23 1 1 Dbar Int - 0.1 1 1 1 F F F F F F F F F F 0 0 0 0 0 0 0 0 0 0 10 10 10 10 10 18 18 18 18 18 Int Int Int Int Int Int Int Int Int Int 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 - 345 346 347 348 349 350 351 352 353 354 138 (R/W) 139 (R/W) 140 (R/W) 141 (R/W) 142 (R/W) 143 (R/W) 144(R/W) 145 (R/W) 146 (R/W) 147 (R/W) Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Table 4.i 4.3.11 Control setting parameters (r*) display indicat. r01 r02 r05 r06 r07 r08 r09 r10 r11 r12 r13 r14 r17 r18 r19 r20 r21 r25 r27 r28 r29 r30 r43 r45 r46 r47 r48 parameter and description Cooling set point Cooling differential Compressor rotation 0= disabled; 1= FIFO type 2= con controllo ore/hour control 3= direct relation between (D.I. and compressors D.O.) Type of compressor control 0= proportional on inlet 1= proportional on inlet + dead zone 2= proportional on outlet 3= proportional on outlet + dead zone 4= time on outlet with dead zone Dead zone differential Maximum control output activation time Minimum control output activation time Maximum control output deactivation time Minimum control output deactivation time Compressor deactivation differential Minimum set point in Cooling Max. Cooling set point Cooling compensation constant Maximum distance from the set point Start compensation temperature in cooling mode Start compensation temperature in heating mode Second cooling set point from external contact Outside temp set point to stop compressors Enable accumulation vessel suppression 0= Disabled 1= Enabled in cool 2= Enabled in Heat 3= Always enabled Min. compressor running time for low load/damper travel time Chiller low load differential/freecooling differential Heat pump low load differential/freeheating differential Heater set point 0= A4, A8, A11, P16, P19 absolute values 1= A4, P16, P19 absolute value, A8 and A11 relative values 2= A8, A11, P16, P19 absolute values, A4 relative value 3= P16, P19 absolute values; A4, A8, A11 relative values 4= A4, A8, A11 absolute values; P16, P19 relative values 5= A4 absolute value, A8, A11, P16, P19 relative values 6= A8, A11 absolute values; A4, P16, P19 relative values 7= A4, A8, A11, P16, P19 relative values Maximum value of calculated set point in relative regulation Minimum value of calculated set point in relative regulation Set point for relative regulation Differential for relative regulation default level D D F min. max. U.O.M. variat. def. r13 1 0 r14 500 3 °C/°F °C/°F Flag 0.1 0.1 1 12.0 30 0 visibility supervis. variable 41 (R/W) 42 (R/W) 78 (R/W) Modbus variable type 41 Analog 42 Analog 285 Integer F 0 4 Flag 1 0 - 79 (R/W) 286 Integer F F F F F F U U U U U U D D F 1 0 0 0 0 0 -400 r13 -50 3 -400 -400 r13 -400 0 500 999 999 999 999 500 r14 1760 50 200 1760 1760 r14 800 3 °C/°F s s s s °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F Flag 0.1 1 1 1 1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 1 20 120 100 120 100 20 -400 800 0 3 300 0 120 -400 0 - 45 (R/W) 80 (R/W) 81 (R/W) 82 (R/W) 83 (R/W) 46 (R/W) 47 (R/W) 48 (R/W) 51 (R/W) 52 (R/W) 53 (R/W) 54 (R/W) 55 (R/W) 65 (R/W) 88 (R/W) 45 287 288 289 290 46 47 48 51 52 53 54 55 65 295 Analog Integer Integer Integer Integer Analog Analog Analog Analog Analog Analog Analog Analog Analog Integer F F F F 0 10 10 0 999 500 500 7 s °C/°F °C/°F - 1 0.1 0.1 1 60 30 30 7 - 89 (R/W) 58 (R/W) 59 (R/W) 121 (R/W) 296 58 59 328 Integer Analog Analog Integer D F D F r46 -400 -400 0 1760 r45 1760 500 °C/°F °C/°F °C/°F °C/°F 0.1 0.1 0.1 0.1 300 100 30 10 - 84 (R/W) 85 (R/W) 86 (R/W) 87 (R/W) 84 85 86 87 Analog Analog Analog Analog Table 4.k 18 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 display indicat. t01 t02 t03 t04 t05 t06 t07 t08 t09 t13 t14 t15 t16 t17 parameter and description RTC hours RTC minutes RTC day RTC month RTC year Start hours for 2nd set point in cooling Start minutes for 2nd set point in cooling End hours for 2nd set point in cooling End minutes for 2nd set point in cooling End minutes for 2nd set point in heating Start hours for 2nd low-noise in cooling Start minutes for 2nd low-noise in cooling End hours for 2nd low-noise in cooling End minutes for 2nd low-noise in cooling default level U U U U U U U U U U U U U U min. max. U.M. variat. def. 0 0 1 1 0 0 0 0 0 0 0 0 0 0 23 59 31 12 99 23 59 23 59 59 23 59 23 59 h min g mesi anni h min h min min h min h min 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 1 1 6 0 0 0 0 0 23 0 7 0 visibility supervis. variable W 129(R/W) W 130 (R/W) W 131 (R/W) W 132 (R/W) W 133 (R/W) W 92 (R/W) W 93 (R/W) W 94 (R/W) W 95 (R/W) W 99 (R/W) W 100 (R/W) W 101 (R/W) W 102 (R/W) W 103 (R/W) Modbus variabile type 336 337 338 339 340 299 300 301 302 306 307 308 309 310 Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Table 4.l 4.3.13 Supervisor-only variables display indicat. - parameter and description Show machine parameters (communication & SV CAREL) Circuit 1 alarm Circuit 2 alarm EVD valve 1 alarm EVD valve 2 alarm General alarm Probe alarm Compressor warning EVD 1 warning EVD 2 warning General warning Temperature warning Fan warning DTE/DTC alarm Digital input 1 Digital input 2 Digital input 3 Digital input 4 Digital input 5 Digital input B4 Digital input 1 Digital input 2 Digital input 3 Digital input 4 Digital input 5 Standby/On status 0= Standby 1= On Heating/Cooling status: 0= Heating 1= Cooling Gain constant for probe 1 calibration Gain constant for probe 2 calibration Gain constant for probe 3 calibration Gain constant for probe 4 calibration Offset constant for pressure probe calibration Offset constant for probe 1 calibration Offset constant for probe 2 calibration Offset constant for probe 3 calibration Offset constant for probe 4 calibration Gain constant for pressure probe calibration Compressor 1 operating hours Compressor 2 operating hours Compressor 3 operating hours Compressor 4 operating hours Compressor pump operating hours Evaporator pump operating hours Digital input 6 Digital input 7 Digital input 8 Digital input 9 Digital input 10 Digital input B8 Digital output 6 Digital output 7 Digital output 8 Digital output 9 Digital output 10 Digital input 11 Digital input 12 Digital input 13 Digital input 14 Digital input 15 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 default level F D D D D D D D D D D D D D D D D D D D D D D D D D min. max. U.O.M variat. def. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 250 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 167 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D 0 1 1 1 65 (R/W) 65 Digital F F F F F F F F F F D D D D D D D D D D D D D D D D D D D D D D 0 0 0 0 0 -8000 -8000 -8000 -8000 -8000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8000 8000 8000 8000 16000 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 - 1000 1000 1000 1000 1000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 (R) 6 (R) 7 (R) 8 (R) 150 (R) 9 (R) 10 (R) 11 (R) 12 (R) 151 (R) 152 (R) 153 (R) 154 (R) 155 (R) 156 (R) 157 (R) 66 (R) 67 (R) 68 (R) 69 (R) 70 (R) 71 (R) 72 (R/W) 73 (R/W) 74 (R/W) 75 (R/W) 76 (R/W) 80 (R) 81 (R) 82 (R) 83 (R) 84 (R) 212 213 214 215 357 216 217 218 219 358 359 360 361 362 363 364 66 67 68 69 70 71 72 73 74 75 76 80 81 82 83 84 Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Integer Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital 19 visibility supervis. variable 148 (R) 41 (R) 42 (R) 43 (R) 44 (R) 45 (R) 46 (R) 47 (R) 48 (R) 49 (R) 50 (R) 51 (R) 52 (R) 77 (R) 53 (R) 54 (R) 55 (R) 56 (R) 57 (R) 58 (R) 59 (R/W) 60 (R/W) 61 (R/W) 62 (R/W) 63 (R/W) 64 (R/W) Modbus variable type 355 Integer 41 Digital 42 Digital 43 Digital 44 Digital 45 Digital 46 Digital 47 Digital 48 Digital 49 Digital 50 Digital 51 Digital 52 Digital 77 Digital 53 Digital 54 Digital 55 Digital 56 Digital 57 Digital 58 Digital 59 Digital 60 Digital 61 Digital 62 Digital 63 Digital 64 Digital ENGLISH 4.3.12 Timer setting parameters (t*) ENGLISH 4.3.13 Supervisor-only variables display indicat. - - - - parameter and description Digital input B12 Digital output 11 Digital output 12 Digital output 13 Digital output 14 Digital output 15 Password to control outputs from the supervisor Defrost status bit 0= Defrost circuit 1 bit 1= Defrost circuit 2 bit 2= Fan Defrost circuit 1 bit 3= Fan Defrost circuit 2 Controls from the UAD: bit0= terminal status (0= not connected; 1= available) bit2; bit1= mode set from µAD (00= AUTO; 01= cooling; 10= heating) bit3= enable dehumidification bit4= enable humidification bit5= terminal probe alarm bit6= activate boiler output bit7= 0= process mode active; 1= process mode disabled Signals to the µAD bit0= cool/heat request from uAD in progress bit1= cool/heat request accepted from µAD (1= cooling; 0= heating) bit2= start fans bit3= alarm active on µCH bit4= RTC available on µCH2 SE DTE value saved in EEPROM Internal set point compensated in the event of autotuning Ambient set point (from µAD) Set point variation from µAM (µedronic) Differential for the ambient set point Controls by the µAD from save Active alarm signal: bit0= probe alarm (E1,E2,E,E4,E5,E6,E7,E8) bit1= high pressure alarm (HP1, HP2) bit2= low pressure alarm (LP1, LP2) bit3= flow switch alarm (FL) bit4= expansion communication alarm (ESP) bit5= EE2PROM alarm (EPB) bit6= antifreeze alarm (A1, A2) bit7= thermal overload alarm (TP, TP1, TP2) bit8= hour counter alarm (H1, H2, H, H4)” Terminal humidity probe (per terminal µAD) Reset alarms Digital input B Compatibility with the test Dummy digital Dummy integer Dummy analog default level D D D D D D D D min. max. U.O.M variat. def. 0 0 0 0 0 0 0 0 1 1 1 1 1 1 8000 255 1 1 1 1 1 1 - 0 0 0 0 0 0 0 0 visibility supervis. variable 85 (R) 86 (R/W) 87 (R/W) 88 (R/W) 89 (R/W) 90 (R/W) 13 (R/W) 134 (R) D 0 1023 1 0 135 (R/W) 342 Integer D 0 255 - 0 136 (R) 343 Integer D D D D D D D 0 0 -400 -100 -100 0 0 0 0 1760 100 100 32767 32767 0,1 0,1 0,1 1 1 0 0 0 0 0 0 0 98 (R) 97 (R) 95 (R/W) 96 (R/W) 94 (R/W) 137 (R/W) 128 (R/W) 98 97 95 96 94 344 335 Analog Analog Analog Analog Analog Integer Integer D D D F F F F 0 0 0 0 0 0 0 1000 % 1 1 1 0 0 0 0,1 1 1 - 0 0 0 0 0 0 0 129 (R/W) 78 (R/W) 79 (R) 19 (R/W) 22 (R) 123 (R/W) 133 (R) 129 78 79 19 22 330 133 Analog Digital Digital Digital Digital Integer Analog - Modbus variable type 85 Digital 86 Digital 87 Digital 88 Digital 89 Digital 90 Digital 220 Integer 341 Integer Table 4.m 20 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 ENGLISH 5. DESCRIPTION OF THE PARAMETERS To modify the parameters, see chapter 4 “Parameters.” • Probe settings: parameters (/*) (see Table 4.a) - Type of probe: from /01 to /08: enables the reading of the corresponding analogue input or sets the function • Functions of the probes Type of unit Parameter H01 Temp. control probe 1st circuit 2= air/water Chiller B1/B2 single circuit (B1/B5 two circuits) 4= water/water Chiller B1/B2 single circuit (B1/B5 two circuits) 11= Cooling-only air-air unit with electric heating B1 Antifreeze probe Cond. temp. Press probe 1st circuit probe 1st circuit 2nd evaporator B2 B3 B4 Antifreeze probe 2nd circuit B6 Cond. temp. probe Press. probe 2nd circuit B7 B8 B2 Not used Not used B6 Not used Not used B2 (low outlet temperature) B3 B4 Not used B7 B8 Table 5.a - Min/max voltage and pressure values From /09 to /12: sets the minimum/maximum voltage and pressure for the ratiometric signal. - Probe calibration From /13 to /20: calibrates the corresponding sensor (from B1 to B8). - Digital filter /21: Establishes the coefficient used in the digital filtering of the value measured. High values for this parameter will eliminate any continuous disturbance at the analogue inputs (however decrease the promptness of measurement). The recommended value is 4 (default). - Input limit /22: Establishes the maximum variation that can be measured by the probes in one unit program cycle; in practice, the maximum variations allowed in the measurement are between 0. 1 and 1.5 units (bars, °C or °F, depending on the probe and the unit of measure) approximately every one second. Low values for this parameter will limit the effect of impulsive disturbance. Recommended value 8 (default). - Unit of measure /23: Selects the unit of measure as degrees centigrade or Fahrenheit. When the parameter is modified, the µC2SE automatically converts the values read by the NTC temperature probes B1, B2, B3 into the new unit of measure; while all the other parameters set (set point, differential etc. ) remain unchanged. Example of antifreeze/outlet limit management • Antifreeze, auxiliary heater: parameters (A*) 1 - Antifreeze alarm set point A01: when probe B2 is installed on the coil represents the temperature (antifreeze set point) of the water at the evaporator outlet below which an antifreeze alarm is activated; in this condition the compressors corresponding to the circuit in question are stopped, while the pump remains on to decrease the possibility of freezing. The alarm is reset manually (or automatically, depending on parameter P05) only when the water temperature returns within the operating limits (that is, above A01+A02). ON OFF A1 A1+A2 2 Fig. 5.a.a - Antifreeze alarm differential A02: This represents the differential for the activation of the antifreeze alarm; the alarm condition cannot be reset until the temperature exceeds the set point + differential (A01+A02 or A14+A02). Key: 1. freecooling or comp - Antifreeze alarm bypass time low room temperature from unit start in heating mode A03: This represents the delay in the activation of the antifreeze alarm when starting the system. - Auxiliary heater probe in heating A06: This determines which probe is used for control the auxiliary heater. The meaning of the parameter is the following: A06 = 0 => Control probe see Table 5.a.a A06 = 1 => Antifreeze probe see Table 5.a.a Not valid if A10= 2 - Antifreeze alarm set point limit A07: Establishes the minimum limit for setting the antifreeze alarm set point (A01). - Heating (electrical heater or hot gas bypass) set point A08: Represents the threshold below which the heating function is activated. The set point in heating is compensated according to the following equation: The heating function could be realized by electrical heater or hot gas bypass valve. The set point in heating is compensated according to the following equation: Set_heaters (heating) = A08 + (Compensated set point - Set point set) A08 could both be absolute value or relative value to set point according to the parameter r43. µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 21 2. probe B2 ENGLISH - Heating differential A09: Represents the differential for the activation/deactivation of the heating function - Automatic switch-on A10: This parameter is valid when the unit is in standby. The operating mode switchover delay times are ignored. A10=0: function not enabled A10=1: heating function and pump are ON at the same time when the temperature is below A04 A10=2: heating function and compressor are ON at the same time when the temperature is below A04 (use for hot gas bypass) A10=3: heating function automatically switches on whne the temperature is below A04 In this case, the display will be as follows: • operating mode LED OFF; • cooling heating flag not switched (not detected by the supervisor); • antifreeze alarm A01 (remains active even at the end of the special operation if the unit was previously ON, deactivated by manual reset or in standby). A10=3: heaters ON based on the respective set point A04 and A08. Do not use with H1= 6 - Antifreeze heater 2 set point in defrost/auxiliary in heating A11: Heater 2 set point in heating, the control of the auxiliary heaters has been separated, each having its own activation set point (see A08). - Dirty filter signal set point (air/air units only) A12: Set point for the dirty filter signal based on B1-B2, the deactivation differential is A05 • Valid in the following conditions: • air-air units; • B1 is configured; • outlet limit active; • freecooling not active; • at least 1 compressor ON. The warning is reset automatically in the following conditions: • air-air units; • B1 is configured; • outlet limit active; • freecooling not active. - Outlet limit set point in freecooling conditions A13: With freecooling active, and only when the compressors are off, this represents the outlet limit. When the compressors are on, even if freecooling is active, the outlet limit alarm is bypassed and the antifreeze alarm is used. - Antifreeze alarm set point from EVD A14: With the EVD connected in the tLAN, A14 represents the evaporation temperature (sent by the EVD) below which the antifreeze alarm is activated; when the alarm is active, the compressors in the circuit affected are switched off, while the pump remains on to reduce the possibility of freezing. Manual reset (or automatic, depending on parameter P05), only occurs when the water temperature returns within the operating limits (that it, exceeds A14+A02 • Probe readings: parameters (B*) - Select probe to be shown on display. b00: Sets the probe reading to be displayed. 0= probe B1 1= probe B2 2= probe B3 3= probe B4 4= probe B5 5= probe B6 6= probe B7 7= probe B8 8= set point without compensation 9= dynamic set point with possible compensation 10= remote ON/OFF digital input status 11= probe AD For the list of parameter-probe associations see Table 4.d Note: probes that are not present cannot be selected. 22 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 • Compressor settings: parameters (c*) - Minimum ON time c01: This establishes the time that the compressor must remain ON for when started, even if the stop signal is sent. Key: ON t OFF ON 2 1. signal; 2. compressor; 3. min. ON time-interval. C2 t OFF 3 Fig. 5.a.c - Minimum OFF time c02: This establishes the time that the compressor must remain OFF for when stopped, even if the start signal is sent. The compressor LED flashes in this phase. ON 1 Key: t OFF ON 1. signal; 2. compressor; 3. min. OFF time-interval. 2 t C2 OFF 3 - Delay between 2 starts of the compressor c03: This sets the minimum time that must elapse between two successive starts of the same compressor Fig. 5.a.d (determines the maximum number of starts per hour for the compressor). The compressor LED flashes in this phase. If by mistake the user enters a value lower than the sum of C01 + C02, this parameter will be ignored and only the times C01 and C02 will be considered. ON 1 Key: t 1. signal; 2. compressor; 3. min. time-interval between two ON routins. OFF ON 2 C2 OFF t 3 Fig. 5.a.e - Start delay between compressors c04: This sets the delay between the starts of the two compressors, so as to reduce the peak power input and make the compressors start more smoothly. The compressor LED flashes in this phase. • In the event of capacity control, the delay c04 between compressor and valve becomes c04/2; • In the event of defrost operation, the delay between compressor and compressor is 3 seconds, and between compressor and valve is 2 seconds. ON 1 OFF ON 2 OFF ON 3 Key: 1. 2. 3. 4. 5. OFF 1st signal; 2nd signal; 1st compressore; 2nd compressor; time delay between two compressors ON routines/time-delay of the capacity-controlled routine. ON 4 OFF C4 5 Fig. 5.a.f - Stop delay between compressors c05: This sets the stop delay between the compressors. ON 1 OFF ON Key: 1. 2. 3. 4. 5. 2 2nd signal; 1st signal; 2nd compressor; 1st compressore; time delay between two compressors OFF routines/time-delay before the capacity-controlled routine. OFF ON 3 OFF ON 4 OFF C5 - Delay on power-up (reset power supply) c06: At power ON (when the controller is physically switched ON) the activation of all the outputs is delayed so 5 Fig. 5.a.g as to distribute the power input and protect the compressor against repeated starts in the event of frequent power failures. This means that after the delay time, the controller will start to manage the outputs based on the other times and the other normal functions. - Compressor start delay from pump/outlet fan (air/air) ON. c07: In cooling and heating operation, if the operation of the pump (outlet fan) is subject to the controller ON 1 (parameter H05=2), the compressor is started when required after the set time from the activation of the water pump (or outlet fan in air/air units). If the pump/outlet fan is always ON (H05=1) and consequently does not depend on the control logic, the compressor is started after the set time from when the unit starts. ON C7 inlet fan; pump; compressor; time-delay between pump-inlet fan and compressor. µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 OFF 3 Key: 1. 2. 3. 4. t 2 4 Fig. 5.a.h 23 t OFF ENGLISH 1 - Pump/outlet fan (air/air) start delay from compressor OFF c08: In cooling and heating operation, if the operation of the pump (outlet fan) is subject to the controller ON ENGLISH 1 t 2 ON (parameter H05=2), when the compressor is requested to stop, the control first stops the compressor and the pump (outlet fan). If the pump/outlet fan is always ON (H05=1), it is only stopped in standby mode. OFF Key: OFF 3 t C8 1. 2. 3. 4. 4 Fig. 5.a.i compressor; pump; inlet fan; time-delay between pump-inlet fan and compressor. - Maximum tandem compressor operating time c09: In the case of two compressors in tandem per circuit, one compressor should not operate for longer than the time set for c09 while the other compressor in the circuit is OFF. This prevents the oil shared in common from migrating over the allowed limit towards the active compressor, and consequently avoids damage when inactive compressor next starts (FIFO logic) due to poor lubrication. As a result, compressor 1 (or 2) in circuit 1, if requested to operate continuously, will actually stop OFF after the time c09 and hand over to compressor 2 (or 1) that was previously OFF. This function always considers the compressor times. Any value lower than the time set for c03 will be ignored, and the compressors (if the above condition is satisfied) will switch over after the time c03. When C9=0, the function is disabled (the compressors will not switch over). - Hour counter compressor 1-2-3-4 c10, c11, c12, c13: These indicate the number of operating hours of compressor 1, 2, 3, 4, expressed in hundreds of hours. Pressing and together, when the hour counter is displayed, resets the hour counter and, consequently, cancels any maintenance requests in progress. c10= operating hours comp. 1 c11= operating hours comp. 2 c12= operating hours comp. 3 c13= operating hours comp. 4 - Compressor operating hour counter threshold c14: This sets the number of compressors operating hours, expressed in hundreds of hours, above which the maintenance request signal is sent. c14= 0: function disabled. - Evaporator pump/fan 1 hour counter c15: This indicates the number of operating hours for the evaporator pump or fan 1, expressed in hundreds of hours. Pressing and together, when the hour counter is displayed, resets the hour counter and, consequently, cancels any maintenance requests in progress. - Condenser or backup pump/fan 2 hour counter c16: This indicates the number of operating hours for the condenser pump (or backup) or fan 2, expressed in hundreds of hours. Pressing and together, when the hour counter is displayed, resets the hour counter and, consequently, cancels any maintenance requests in progress. - Minimum OFF time before the next pump/fan start c17: The diagram below shows an example of the operation of the pump and with burst (active when H05=3, see parameter H05). The dashed areas on the compressor line indicate the pump-compressor and compressor-pump delay times. Burst mode is disabled in standby and during an alarm when the pump is OFF. At power ON the delay c17 must elapse before burst can start. - Minimum pump/fan ON time c18: This represents the minimum time that the pump remains ON for, see Fig. 5.i (active with H05=3 see parameter H05). 24 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 • Fan settings: parameters (F*) ENGLISH - Fan output F01: Enables the operation of the fans. F01=0: fans absent; F01=1: fans present. The PWM output (1 or 2, depending on the value of parameter H02) requires the presence of the optional fan control cards (ON/OFF for the CONVONOFF module or speed variation for MCHRTF or FCS three-phase). - Fan operating mode F02: This establishes the operating logic for the fans: F02=0: always ON at maximum speed, independently from the compressors. The fans are only switched OFF when the unit is in standby. F02=1: ON at maximum speed when at least one compressor in the corresponding circuit is ON (parallel operation in each circuit). F02=2: ON when the corresponding compressor is ON, with ON/OFF control based on the temperature/ pressure settings for the minimum and maximum speed (parameters F05-F06-F08 and F09). When the compressors are stopped, the corresponding fans are also stopped, irrespective of the condensing temperature/pressure. Cooling ON/OFF Heating ON/OFF 1 1 100% 100% F04 F04 0% Key: 1. speed %; 2. condensing temperature/pressure; 3. hysteresis. 0% F05 F08 2 F06 F09 2 Fig. 5.a.l Cooling with speed control 1 Heating with speed control 1 3 3 100 % F05 F04 F08 F04 F03 F03 0% 0% 2 F07 2 F06 F09 F10 Fig. 5.a.m F02=3: ON when the corresponding compressor is ON, with speed control. When the compressors are stopped the corresponding fans are also stopped, irrespective of the condensing temperature/pressure. With F02=3 and an NTC condenser probe, when the compressor starts the fans are started at maximum speed for the time F11, irrespective of the temperature measured. In the event of a condenser probe fault, the fans will be switched OFF. - Minimum voltage threshold for Triac F03: In the event of fan speed control, the optional phase cutting cards (MCHRTF*) are required, fitted with a triac. The voltage delivered by the triac to the electric fan motor corresponding to the minimum speed must be set. The set value does not correspond to the actual voltage in Volts applied, but rather to an internal unit of calculation in the µC2SE. If using FCS controllers, set this parameter to 0. F03 = Represents the minimum threshold for the triac - Maximum voltage threshold for Triac F04: In the event of fan speed control, the optional phase cutting cards (MCHRTF*) are required, fitted with a triac. The voltage delivered by the triac to the electric fan motor corresponding to the maximum speed must be set. The set value does not correspond to the actual voltage in Volts applied, but rather to an internal unit of calculation in the µC2SE. If using FCS controllers, set this parameter to 100. F04 = Represents the maximum threshold for the triac - Temperature/pressure set point for minimum speed in cooling F05: This represents the temperature or pressure below which the fans remain ON at minimum speed. In the case of ON/OFF control, it represents the temperature or pressure below which the fans are switched OFF (Fig. 5.a.k). µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 25 ENGLISH - Temperature/pressure differential for maximum speed in cooling F06: This represents the temperature or pressure differential in reference to F05 above which the fans are started at maximum speed; in the case of ON/OFF control, this represents the differential above which the fans are started (Fig. 5.a.k). - Temperature/pressure differential for fans Off in cooling F07: This represents the temperature or pressure differential in reference to F05 below which the fans are stopped. The fans are started 1 °C “lower” when using NTC temperature probes, or 0. 5 bars if using pressure probes. (Fig. 5.a.l) If NTC temperature probes or pressure probes are used to control the condensing temperature/pressure, there is an activation hysteresis of 1 °C or 0.5 bar respectively. - Fan start time F11: This establishes the operating time at maximum speed when the fans are started, so as to overcome the mechanical inertia of the motor. The same times are observed in reference to the start of the compressor (irrespective of the condensing temperature/pressure), if NTC temperature probes are used on the condenser and speed control is enabled, F02=3; this is done to bring forward the sudden increase in pressure (which does not necessarily correspond to a likewise rapid increase in temperature in the area where the probe is located) and consequently to improve control F11=0: the function is disabled, that is, the fans are activated at the minimum speed and then controlled based on the condensing temperature/pressure. - Triac impulse duration F12: This represents the duration in milliseconds for the impulse applied to the triac. For induction motors, set the parameter to 2 (default). On the other hand, when using the CONVONOFF0, CONV0/10A0 modules or FCS controllers, set the parameter to 0. - Fan on time when starting in high condensing temp. F14: establishes the time the fans are operated at maximum speed if starting with a high condensing temperature. F14 = 0: function disabled. F14 > 0: fan on time (in seconds). The function is operational only in chiller mode, if the probe on the condenser is a temperature sensor and only for air-cooled units. When the first compressor in the circuit in question starts, it is assumed that the temperature of the environment is close to the temperature of the condenser; if the value read by the condenser probe is higher than the value of F05-F07, as well as starting the compressor, the fans in the circuit in question are forced on at maximum speed for the time set by F14. - Activate low noise F15: This function moves the condensing pressure set point so as to lower the fan speed and consequently reduce noise (specifically at night). If low noise is active in cooling, the condenser control set points are increased by F16. If low noise is active in heating, the set points are reduced by F17. F15= 0: Low noise deactivated. F15= 1: Low noise activated in cooling. F15= 2: Low noise activated in heating. F15= 3: Low noise activated in cooling and heating. N.B. The variation in the set point is not active during defrost - Cooling set point differential F16: Differential added to the condenser control set point when low noise is active (valid for both temperature and pressure control). • Unit settings: parameters: (H*) - Unit model H01: Used to select the type of unit being controlled: H01= 2: AIR/WATER Chiller H01= 4:WATER/WATER Chiller (*) Note: Set H21= 4 (Condenser pump always on), if H02= 1 (Two condensers). - Number of condenser fan circuits/water condensers H02: This establishes the number of fan circuits present in the configurations with two circuits. With one fan circuit (H02=0) the unit may have 1 or 2 refrigerant circuits: • with one refrigerant circuit, the fans are exclusively controlled based on the pressure or temperature read by the sensor in the first circuit; • with two refrigerant circuits, the fans are controlled based on the higher temperature/pressure of the two circuits. In heat pump mode, the output depends on the lower temperature or pressure. The output used is Y1. Vice-versa, with 2 ventilation circuits (H02=1) each PWM output is independent and depends on its own condenser probe (B3 or B4 for circuit 1 and B7 or B8 for circuit 2). 26 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 ENGLISH - Number of evaporators H03: This establishes the number of evaporators present when there are 2 or 4 compressors, obviously with 2 circuits (including the expansion). With one evaporator (H03=0), the management of the heaters and the antifreeze function is performed only on B2. Vice-versa, with 2 evaporators (H03=1) antifreeze control will be performed using B2 and B6, while input B5 is used to control the water outlet temperature. - Number of compressors/circuits H04: This establishes the number of compressors per circuit and the number of circuits. For further details see Table 4.g. - Evaporator pump/fan operating mode H05: This establishes the operating mode for the evaporator water pump or the outlet fan (in air/air units). H05 = 0: pump disabled, (the flow switch alarm is ignored) H05 = 1: always ON (the alarm is managed) H05 = 2: ON when called by compressor (the alarm is managed) H05 = 3: the pump will be started and stopped at regular intervals (independently from the compressors) as per the Burst setting (see parameters c17 and c18). H05= 4: follow hot keep or hot start in heating, always on in cooling H05= 5: follow hot keep or hot start in heating, follow the compressors in cooling. When the heating or cooling signal is received, first the evaporator pump/outlet fan starts (always ON), and then the compressor, after the set times (c07, c08). The pump will not be stopped until all the compressors are Off. - Cooling/heating digital input H06: Establishes whether the cooling/heating selection from digital input is enabled. see parameters P08, P09, P10, P11, P12 and P13). The open status places the unit in cooling operation, vice-versa, in heating. D-IN Open = Cooling D-IN Closed = Heating - ON/OFF digital input H07: Establishes whether the ON/OFF selection from digital input is enabled or disabled. If the selection is enabled (H07= 1), the “open” status switches the unit Off, while in the “closed” status, the unit may be OFF or ON, as controlled by the keypad. This parameter is not valid for condensing units. - µC2SE network configuration H08: Establishes the layout of the tLan network. 0= µC2SE only 1= µC2SE + valve 2= µC2SE + exp. 3= µC2SE + exp. + valve 4= µC2SE + I/O 5= µC2SE + valve + I/O 6= µC2SE + exp. + I/O 7= µC2SE + I/O + valve + valve - Enable keypad H09: Used to disable the modification of the DIRECT and USER parameters from the keypad. The value of the parameters can always be displayed. The enable/disable cooling, heating and reset counter functions are also available. Values: 0: keypad disabled 1: keypad enabled (default) - Serial address H10: Establishes the address of the instrument for the serial connection, via an optional board, to a PC for supervision and/or telemaintenance. - Selection map outputs H11: This parameter is used to arbitrarily associate some digital outputs to the devices on the unit. H11= 0: standard (default); for units with one compressor per circuit (H04=0, 2). H11= 1: For cooling only units with two compressors (H01=0, 2, 4, 7, 9 and H04=1, 3, 5) H11= 2: The outputs of the expansion follow the same logic for the 2nd circuit. For H01= 1, 3, 5, 6, 8, 10 and H04= 1, 3, 5 H11= 3: The outputs of the expansion follow the same logic for the 2nd circuit. For H01= 1, 3, 5, 6, 8, 10 and H04= 1, 3, 5 H11= 4: For H01= 1, 3, 5, 6, 8, 10 and H04= 0, 1 H11= 5: For cooling only units with two compressors (H01= 0, 2, 4, 7, 9, and H04= 0) H11= 6: 1 compressor per circuit, heat pump H11= 7: 1 compressor per circuit, cooling only, solution 1 H11= 8: 1 compressor per circuit, cooling only, solution 2 H11= 9: 2 compressors per circuit, heat pump H11= 10: 2 compressors per circuit, cooling only, solution 1 H11= 11: 2 compressors per circuit, cooling only, solution 2 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 27 H11= 12: ENGLISH associated device H11=0 H11= 1 H11= 2 H11= 3 H11= 4 H11= 5 alarm compressor 2 heater 2 Condenser pump/backup reversing valve 2 C10 Warning compressor 1 heater 1 Pump/evaporator (fan) (on air/air units) Compressor 2 (or capacity control comp. 1) reversing valve 1 compressor 3 heater 2 Condenser pump/backup Compressor 4 (or capacity control comp. 2) reversing valve 2 compressor 1 reversing valve 1 Pump/evaporator (fan) (on air/air units) Compressor 2 (or capacity control comp. 1) alarm compressor 3 reversing valve 2 Condenser pump/backup Compressor 4 (or capacity control comp. 2) Warning compressor 1 heater 1 Pump/evaporator (fan) (on air/air units) condenser fan 1 C5 C6 C7 C8 C9 compressor 1 heater 1 Pump/evaporator (fan) (on air/air units) Compressor 2 (or capacity control comp. 1) alarm compressor 3 heater 2 Condenser pump/backup Compressor 4 (or capacity control comp. 2) Warning compressor 1 reversing valve 1 evaporator pump C4 compressor 1 heater 1 Pump/evaporator (fan) (on air/air units) reversing valve 1 outputs C1 C2 C3 outputs C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 H11= 6 H11= 7 H11= 8 compressor 1 1 step heater outlet fan reversing valve 1 alarm compressor 3 2 step heater open freecooling/ freeheating reversing valve 2 close freecooling/ freeheating compressor 1 1 step heater outlet fan 2 step heater alarm compressor 3 P29 open freecooling compressor 1 1 step heater outlet fan condenser fan 1 alarm compressor 3 2 step heater open freecooling humidifier (ON/OFF) close freecooling condenser fan 2 close freecooling associated device H11= 9 compressor 1 compressor 2 outlet fan reversing valve 1 alarm compressor 3 open freecooling/ freeheating 1 step heater close freecooling/ freeheating Compressor 2 (or capacity control comp. 1) alarm not used heater 1 Condenser pump/backup not used Warning alarm compressor 2 heater 2 Condenser pump/backup condenser fan 2 Warning H11= 10 H11= 11 H11= 12 compressor 1 compressor 2 outlet fan heating step 1 alarm compressor 3 compressor 4 open freecooling/ freeheating heating step 2 close freecooling/ freeheating compressor 1 compressor 2 outlet fan heating step 1 alarm compressor 3 compressor 1 P25 P26 P27 P28 compressore 3 P29 P30 open freecooling/ freeheating humidifier close freecooling/ freeheating P31 P32 Parameters P25 to P28 can have the following meanings: 0 = no function associated with the relay 1 = compressor 2 2 = Heater 1 3 = Reversing valve 1 4 = Pump/inside fan 5 = Open freecooling/freeheating 6 = Close freecooling/freeheating 7 = Humidifier 8 = Condenser fan 1 on/off 9 = Heater 2 10 = Alarm 10 = Boiler contact Parameters P29 to P32 can have the following meanings: 0 = no function associated with the relay 1 = compressor 4 2 = Heater 2 3 = Reversing valve 2 4 = Pump/inside fan 2nd evaporator 5 = Open freecooling/freeheating 6 = Close freecooling/freeheating 7 = Humidifier 8 = Condenser fan 2 on/off 9 = Warning 10 = Condenser pump/Backup 11 = Heater 1 28 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 ENGLISH - Capacity-control logic H12: Specifies the logic for the activation of the capacity-control steps for the compressors and the 4-way reversing valve. H12 = 0: 4-way reversing valve and capacity-control normally energised H12 = 1: 4-way reversing valve and capacity-control normally de-energised. Default value. H12 = 2: 4-way reversing valve normally de-energised and capacity-control normally energised H12 = 3: 4-way reversing valve normally energised and capacity-control normally de-energised. Note: in the event of capacity-control, the rotation between compressor and corresponding valve is disabled. FIFO or time logic can be used between the 2 circuits to optimise the starts or the operating hours of the 2 compressors (1 per circuit). - Enable pump down H13: This function allows the unit to be stopped while avoiding the possible formation of liquid refrigerant inside the evaporator. When the only active compressor is called to stop, the expansion valve is closed so as to depressurise the circuit. Valid only when the driver is installed, as the driver pressure probe is used. - Minimum pumpdown pressure H14: Limit pressure below which the compressor is deactivated. - Maximum pumpdown time H15: Maximum time after which the compressor is deactivated. - Function of the second pump H21: This parameter defines how the output dedicated to the second pump must be managed. H21= 0: the second pump is disabled. H21= 1: the second pump is used only as a backup. If the flow switch and corresponding alarm are activated, the pumps are switched over: • if the alarm passes, a warning is shown on the display and the warning relay is activated, while the unit continues to operate with the Backup pump. When the next alarm is activated the pumps will be switched over. • if the alarm remains active even with the second pump on for longer than the time set for P1, the generic alarm is generated and the unit is switched OFF. H21= 2: the second pump represents a backup pump. The two pumps are never used at the same time but each 24 hours, are switched over. In the event of flow alarms, the logic is the same as for setting 1. After being switched over due to the flow alarm, the 24-hour timer is set to zero. H21= 3: the second pump is used as an ON/OFF device in the same way as the condenser fan (which in this case is not present), in ON/OFF mode, with the same settings (in fact in this case the pump replaces the fan, including the symbol). H21= 4: the second pump is used for the condenser but is always ON. In this case the pump symbol is not managed. Note: In the event of flow alarms with automatic reset, 10 attempts are made to restart the pump every 90 seconds, for a maximum time of P02; after the 10 attempts, the alarm becomes manual reset. With the second pump, the attempt consists in switching over the pump that is on, with the same logic. - Disable load default values H22: If this parameter is set to 1, it disables the possibility of restoring the default parameters using the PRG button at power ON. - select supervisor protocol H23: establishes the protocol used for the connection to the supervisor from the serial board RS485 H23 = 0: CAREL protocol (baud rate 19200,…) H23 = 1: Modbus protocol - High/Low temperature alarm mode H24: determines when HT/LT alarm appears, whether the compressor stops H24 = 0: compressor doesn’t stop H24 = 1: compressor stops when HT alarm appears H24 = 2: compressor stops when LT alarm appears H24 = 3: compressor stops when HT or LT alarm appear - Enable hot gas bypass function H25: determines whether the hot gas bypass function is enabled H25 = 0: disable H25 = 1: enable - Enable special standby function H26: determines whether the special stanby function is enabled H25 = 0: disable H25 = 1: enable When this function is enable, if during STAND BY mode the temperature B1 drops below r3 the unit switches on the heating mode (electrical heater or hot gas bypass). µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 29 • Alarm settings: parameters (P*) ENGLISH - Flow switch alarm delay when starting pump P01: Establishes a delay in the recognition of the flow switch alarm when starting the pump (this allows the flow-rate to stabilise). In the event of alarms, the compressors are stopped immediately, ignoring the times. - Flow switch alarm delay in steady operation P02: Establishes a delay in the recognition of the flow switch alarm in steady operation, so as to filter any variations in flow-rate or air bubbles present in the water circuit. In the event of alarms, the compressors are stopped immediately, ignoring the times. - Low pressure alarm delay at compressor start P03: Establishes a delay in the recognition of the low pressure alarm when the compressor starts, so as to allow stable operating conditions to be reached. This delay is also counted when reversing the 4-way valve in the refrigerant circuit. - Part load in high pressure and low pressure in heat pump P04: enable or disable the part load operation of the circuit in high pressure. The function is valid if the unit is fitted with tandem or capacity controlled compressors and pressure transducers. In the event of high pressure alarms, that is, for values over P18 (hysteresis 0.5 bar), the controller deactivates a load step in the circuit in question and waits 10 seconds. After this interval, if the alarm is still active, the unit is stopped, otherwise it continues to operate in part load mode. In this situation, the display shows the message PH1 and/or PH2, depending on the circuit. This condition remains active until the pressure falls below the value corresponding to the maximum speed of the condenser fans (F05+F06). Below this value, the unit reactivates the load step that had previously been deactivated. P04=0: capacity control not activated P04=1: capacity control activated for high pressure P04=2: capacity control activated for low pressure P04=3: capacity control activated for high and low pressure With the unit operating in heat pump mode, due to low outside temperatures or the load the pressure may fall and stop the unit due to the low pressure alarm. If the circuit has 2 compressor steps and the pressure remains below the value of one bar for the time P22, the circuit can operate at part load. This capacity control is not activated when the alarm comes from the digital input. In the event of low pressure, the controller deactivates one step and if the pressure does not return above the threshold in 10 seconds, the alarm is activated and the circuit is stopped. This function is valid for all units with pressure transducers. Part load in low pressure all LP parz LP 1 bar 1,5 bar 2 bar F08-F09 pressure Fig. 5.b.b - Alarm reset P05: Enables automatic reset for all those alarms that normally feature manual reset (high pressure, low pressure, flow switch/antifreeze) as per the following table: P05= 0: (default) high pressure, low pressure and antifreeze (low temperature) with manual reset; P05= 1: all the alarms with automatic reset; P05= 2: high pressure and antifreeze (low temperature) manual, low pressure automatic; P05= 3: high pressure manual, low pressure and antifreeze (low temperature) automatic; P05= 4: high and low pressure manual, antifreeze (low temperature) automatic; P05= 5: high and low pressure manual after the third activation in one hour*, antifreeze (low temperature) automatic; P05= 6: high and low pressure manual after the third activation in one hour*, antifreeze (low temperature) manual. *: the high and low pressure alarms are managed in the same way both for the transducers and the pressure switches (digital input); if the unit is in standby the count (3 times in one hour) is reset. - Low pressure alarm with pressure probes P07: P07=0: this function is disabled. P07=1: if in heat pump mode the evaporator (external exchanger) pressure is less than 1 bar (and if the presence of the condenser pressure probe is enabled), the low pressure alarm is activated (while still considering the delay P03). Note: P07=1 the LP digital inputs in heat pump are ignored. note 1: if P08 is set to 10, the change in state considers the times d12 and d13, and respects the compressor protection times, both from the digital input and the keypad. note 2: if the digital input is used to switch the unit ON/OFF or change the operating mode, these functions are disabled on the keypad. note 3: ID5 for the condensing unit with reverse cycle has the function of cooling/heating changeover 30 - Select digital input ID1 P08= 0: none; P08= 1: flow switch with manual reset (normally closed); P08= 2: flow switch with automatic reset (N.C.); P08= 3: general thermal overload with manual reset (N.C.); P08= 4: general thermal overload with automatic reset (N.C.); P08= 5: thermal overload circuit 1 with manual reset (N.C.); P08= 6: thermal overload circuit 1 with automatic reset (N.C.); P08= 7: thermal overload circuit 2 with manual reset (N.C.); P08= 8: thermal overload circuit 2 with automatic reset (N.C.); P08= 9: cooling/heating (open = Cooling, closed = Heating) if H06= 1; P08= 10: cooling/heating with delays d12 and d13 (open = Cooling, closed = Heating) if H06= 1; P08= 11: alarm signal with manual reset (N.C.); P08= 12: alarm signal with automatic reset (N.C.); P08= 13: second set point from external contact (cooling and heating), (normally open); P08= 14: second cooling set point from external contact and heating from time band (N.O.); P08= 15: end defrost from external contact circuit 1 (N.C.); P08= 16: end defrost from external contact circuit 2 (N.C.); P08= 17: end defrost from external contact circuit 1 (N.C.); P08= 18: end defrost from external contact circuit 2 (N.C.); P08= 19: condenser step 1 (N.O.); P08= 20: condenser step 2 (N.O.); P08= 21: condenser step 3 (N.O.); P08= 22: condenser step 4 (N.O.); P08= 23: remote ON/OFF. µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 ENGLISH - Select digital inputs ID2, ID6, ID7, ID10, ID5 P09, P10, P11, P12, P34: Configuration of digital inputs ID2, ID6, ID7, ID10, and ID5 respectively (as per the table above for digital input ID1). Note: Cooling/heating (9, 10) cannot be set on P10, P11, P12, and P14. - Select input B4 if /04 = 1 P13: If input B4 is used as ON/OFF (/04 = 1) the same options are valid as for P08. - Select input B8 if /08 = 1 P14: If input B8 is used as ON/OFF (/08 = 1) the same options are valid as for P08. - Select low pressure alarm P15: Used to select whether the low pressure alarm is detected when the compressor is OFF (P15=1) or alternatively only when the compressor is ON (P15=0, default). When the compressor starts the alarm is in any case ignored for the time P03. - High temperature/high system start-up temperature alarm delay P16: Represents the high temperature alarm threshold detected by probe B1; the differential is set at 2 °C and the alarm is reset automatically (the alarm relay is activated, signal only, and the message “Ht” is shown). When starting the system, this alarm is ignored for the time P17. If the system start-up protection is enabled (see parameter P20) and the alarm is activated, the time P17 is ignored and the alarm has no hysteresis. - High temperature alarm delay on power-up P17: High temperature alarm delay when the control is switched on (power ON), from the remote ON/ OFF contact or from the keypad. - High pressure alarm from transducer set point P18: Sets the value beyond which the high pressure alarm is generated. Each circuit will be managed by its own transducer. P18= 0: the function is disabled. For all other values greater than 3.0, due to the hysteresis (3 bars), the alarm is managed according to the set value. - Low temperature alarm set point P19: Represents a threshold for the low temperature (measured by probe B1) alarm, the differential is set at 2 °C and it is reset automatically (the alarm relay is activated and the disply shows the message “Lt”) - System start-up protection for high/low temperature P20: If set to 1, this parameter enables the system protection function when starting, both at power ON and when switching ON from Standby. For values of B1 greater than the set point P19, an alarm is activated and the unit is not started (display “AHt”). The alarm is reset automatically. P20=0: the function is not enabled. - Low pressure alarm waiting time in heat pump P22: Delay in generating the low pressure alarm in heat pump mode If the pressure remains below 1 bar for the time p22 and the circuit has 2 compressor steps, the circuit can operate at part load (see P04). This preventive capacity control function remains active until the pressure rises above F08-F09. - Low pressure alarm waiting time during defrost P23: Delay in generating the low pressure alarm in heat pump mode during defrost - Deactivate compressors in capacity control for HP and LP P24: Decide which compressor must be stopped in each circuit during capacity control P24= 0 stops compressors 1 and 3 P24= 1 stops compressors 2 and 4 - Low pressure alarm set point from transducer P33: : Sets the value beyond which the low pressure alarm is generated when the unit is operating in heat pump mode. Each circuit will be managed according to its own transducer. P33= 0 the function is disabled. - Mute alarm relay using “PRg/mute” button P35=0 the PRG/mute button does not alter the status of the relay, if the alarm is active and in progress. P35=1 the PRG/mute button alters the status of the relay even if the alarm is active and in progress, as if it were a buzzer or a siren. - High pressure alarm management P36: the parameter is used to consider the high pressure alarm even when the compressor is off or consider it only when the compressor is on, depending on whether the pressure switch is directly connected to the digital input on the controller or via another circuit. P36=0: high pressure alarm always considered (pressure switch connected directly to the digital input). P36=1: high pressure alarm considered 2 seconds after starting the compressor. µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 31 ENGLISH - Definition of DI11 to DI15 P37: selection of digital input 11 (input 1 I/O board) P38: selection of digital input 12 (input 1 I/O board) P39: selection of digital input 13 (input 1 I/O board) P40: selection of digital input 14 (input 1 I/O board) P41: selection of digital input 15 (input 1 I/O board) Each parameter can be: 0= not connected 1= alarm Ad1 2= alarm Ad2 3= alarm Ad3 4= alarm Ad4 5= alarm Ad5 6= warning Ad1 7= warning Ad2 8= warning Ad3 9= warning Ad4 10= warning Ad5 Note: all alarms stop the unit. THe alarm relay will be activated. All warning activate the warning relay. - Definition of DO11 to DO15 P42: selection of digital output 11 (output 1 I/O board) P43: selection of digital output 12 (output 1 I/O board) P44: selection of digital output 13 (output 1 I/O board) P45: selection of digital output 14 (output 1 I/O board) P46: selection of digital output 15 (output 1 I/O board) Each parameter can be: 0= not connected 1= Ad1 2= Ad2 3= Ad3 4= Ad4 5= Ad5 6= HP1 7= HP2 8= LP1 9= LP2 10= TC1 11= TC2 12= FL 13= LT 14= HT 15= ALT 16= AHT 17= TP 18= FLB • Control settings: parameters (r*) - Cooling set point r01: between r13 and r14 r02: cooling differential value of DTE when the unit is first started (autotuning enabled) - Compressor rotation r05: The rotation of the compressors allows the operating hours to be balanced either statistically, using FIFO logic, or absolutely, by counting the effective operating hours. Settings: r05=0: rotation disabled; The customer can use compressors with different power ratings according to the desired logic or manage the capacity-control functions. The compressors are started/stopped in proportional mode. r05=1: rotation with FIFO logic (first ON, first OFF, and vice-versa first OFF, first ON); in this mode the operating hours are optimised together with the number of starts, even if the compressor safety times are always respected. r05=2: rotation with control of operating hours; in this way the compressors will have the same operating hours, as the compressor with the least operating hours is always started first, again observing the safety times. This does not however consider FIFO logic and does not optimise the starts and stops. In the case of capacity controlled compressors (1 per circuit), FIFO logic or timed operation will refer to the actual circuit and not the compressor valves. If, for example, when capacity is required from circuit 1, compressor 1 starts first, capacity controlled (not at full capacity), and then the valve is managed as a second step, so that the compressor will work at maximum efficiency. If less capacity is required, the second step will be deactivated first, and then the compressor. There is no rotation between the compressor and the valve. If extra capacity is required, the second circuit will start with compressor 2 and then, if required, the valve is operated. 32 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 ENGLISH When stopping, the valve is managed first and then the actual compressor as a whole. Both FIFO logic and timed operation will involve either one circuit or the other. The activation and deactivation of the valves are not subject to timers, but rather only a hysteresis that is equal to the set point and the differential of the step (in fact the valve performs the same function as a hermetic compressor). r05=3: direct correspondence between the digital inputs and the compressor relays (condensing units only). - Type of compressor control r06: This parameter is used to set the logic for maintaining the set point: r06= 0: proportional on inlet r06= 1: proportional on inlet + dead zone (see Dead zone, below) r06= 2: proportional on outlet r06= 3: proportional on outlet with dead zone r06= 4: on outlet by time with dead zone (see timed outlet temperature control) ON DEAD ZONE The dead zone essentially shifts the proportional band from the set point by the value set for the parameter r07.This parameter is valid in all configurations if enabled (for r070: dead zone set and enabled). Key Figure 5.b.c: r06: enable the dead zone (enabled if r06=1 or 3) r07: dead zone r01: cooling set point r02: cooling differential OFF r01 r01+r07+r02/4 r01+r07 r01+r07+r02*3/4 r01+r07+r02/2 r01+r07+r02 Fig. 5.b.c In chiller (cooling) mode, the dead zone moves the cooling proportional band above the set point by the value r07. Outlet temperature control by time r06 = 4 This type of control is based on the need to maintain the outlet temperature as constant as possible, despite the load being variable or the reduced inertia of the system. The logic has the aim of keeping the temperature inside the dead zone. If outside the zone, the compressors will be activated with the logic described below, so as to return inside the dead zone, neither too quickly (using an integral or derivative), nor too slowly, with fixed time logic. There are two logical times involved: the activation time and deactivation time. - Dead zone differential r07: (see dead zone) - Activation delay at lower limit of r07 (if r06 = 4) r08: The value set is used in the control algorithm (see timed outlet temperature control) as the maximum time (at the start of the differential) for the activation of the compressors. - Activation delay at upper limit of r07 (if r06 = 4) r09: The value set is used in the control algorithm (see timed outlet temperature control) as the minimum time (at the end of the differential) for the activation of the compressors. Activation time (cooling) The activation time is not a set parameter, but rather the combination of two set parameters, that is, r08 and r09. When the temperature leaves the dead zone, the activation time is equal to r08, while at the end of the differential r02 the activation time is equal to r09. Inside the differential r02, the activation time varies linearly between r08 and r09. This means that as the temperature moves away from the set point, the times are reduced and the esponse of the process becomes more dynamic. r10 time activation time r11 temperature - Deactivation delay at upper limit of r12 (if r06 = 4) r10: The value set is used in the control algorithm (see timed outlet temperature control) as the maximum time (at the set point) for the deactivation of the compressors. r03+r12 dead zone comp. act. differential Fig. 5.b.e - Deactivation delay at lower limit of r12 (if r06 = 4) r11: The value set for this parameter is used in the control algorithm (see timed outlet temperature control) as the minimum time (at the end of the deactivation differential) for the deactivation of the compressors. µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 r03 33 deactivation time time ENGLISH r01 - Compressor deactivation differential (if r06 = 4) r12: This represents the temperature differential for the deactivation of the compressors, according to the procedure described in “Deactivation time”. Deactivation time (cooling) Fig. 5.b.f In the same way as for the activation time, the deactivation time also varies between a maximum value, set for the parameter r10 and corresponding to the set point temperature, and a minimum, set for the parameter r11 corresponding to the end of the differential for the deactivation of the compressors, set by the parameter r12. r01 A1 A4 temperature compressor r01-r12 compressor stop Below this value, the deactivation time will be equal to the minimum set until reaching the temperature A04, after which all the compressors will be switched OFF, irrespective of the times. As the temperature moves away from the set point, the response of the process becomes more dynamic. deactivation time Fig. 5.b.f - Minimum Cooling set point r13: Establishes the minimum limit for setting the Cooling set point. - Maximum Cooling set point r14: Establishes the maximum limit for setting the Cooling set point. - Cooling compensation constant (chiller mode): r17: Sets the coefficient that controls the cooling compensation algorithm. In cooling mode, if r17 is positive, the set point increases as the outside temperature increases (measured by the outside probe); if on the other hand r17 is negative the set point decreases as the outside temperature increases. This difference in the set point from the set value can have a maximum absolute value equal to the setting of r18. The values for the parameters shown on the graph are: r17=±2, r01=25, r19=32 and r18=5). 50 3 40 4 1 30 20 5 r18 6 r18 Key: 1. 2. 3. 4. 5. 6. 7. 7 10 2 Fig. 5.b.i temperature; time; external temperature (probe B3/B4); comp. start temperature (r19); positive compensation (r17= 2); set point (r1); negative compensation (r17=-2). - Maximum deviation from the set point r18: Indicates the maximum deviation from the set point beyond which compensation is stopped (maximum and minimum limits in reference to the set point). Example of compressor deactivation due to outside temperature 1 ON r25 r25+1 °C - Start compensation temperature in cooling (outside probe) r19: Sets the temperature (measured by the outside probe) above which the compensation function starts (cooling), value between -40T80 °C. 2 Fig. 5.b.l - Start compensation temperature in heating (outside probe) r20: Sets the temperature (measured by the outside probe) below which the compensation function starts (heating), the value must be between -40T80 °C. - Second cooling set point from external contact r21: Represents the alternative to r01 if an associated digital input is closed (see parameter P08), between r13 and r14. - Outside temperature set point to stop compressors r25: To avoid energy efficiency lower than electrical heating, the compressors are stopped if the outside temperature falls below r25, the differential to start them again is set to 1 degree. The heaters can then be activated according to the corresponding set point. Setting 25 to “-40” (default value) disabled the function. - Buffer tank suppression (low load) r27: The low load condition is determined when only one compressor is started and then is stopped after operating for less than the time set for parameter r28. The settings are: r27=0: the function is disabled; r27=1: enabled only in chiller mode; r27=2: enabled only in heat pump mode; r27=3: enabled in chiller and heat pump modes. 34 - Minimum compressor on time to determine low load condition r28: This parameter represents the minimum compressor on time below which the low load condition is determined. Whenever the compressor stops, the controller analyses the load status. If already in low load condition, the time considered by the controller for the analysis becomes “r28 x r29: r02” in chiller mode, or “r28 x r30 : r04” in heat pump mode. This parameter also has the meaning of damper travel time when freecooling/heating is enabled. When the sum of the opening times reaches 2*damper travel time, the damper is no longer moved. The sum is reset when the damper is closing. Operation is the same in closing. µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 ENGLISH - Differential during the low load condition in chiller mode r29: This parameter represents the new differential considered by the controller in chiller mode during the low load condition. Specifically, r02 is replaced by r29. This also has the meaning of freecooling differential. - Differential during the low load condition in heat pump mode r30: This parameter represents the new differential considered by the controller in heat pump mode during the low load condition. Specifically, r04 is replaced by r30. This also has the meaning of freeheating differential. 1 2 on Key: on off r01 r01 + r02 off 5 r01 r01 + r29 1. chiller; 2. chiller in low load; 5. temperature. 5 Fig. 5.b.m - Electric heater set point relationship r43: defines the relationship between the absolute set point, considered as the activation threshold for the electric heaters, and the relative set point, that is, the activation threshold for the electric heaters referred to a working set point (set point sent by µAD, r01 or r04 or from time band) depending on the various applications and the mode, cooling or heating, and more precisely: r43= 0 A4, A8, A11, P16, P19 absolute values r43= 1 A4, P16, P19 absolute values; A8, A11 relative values r43= 2 A8, A11, P16, P19 absolute values; A4 relative value r43= 3 P16, P19 absolute values; A4, A8, A11 relative values r43= 4 A4, A8, A11 absolute values; P16, P19 relative values r43= 5 A4 absolute value; A8, A11, P16, P19 relative values r43=6 A8, A11 absolute values; A4, P16, P19 relative values r43=7 A4, A8, A11, P16, P19 relative values - Maximum value of calculated set point in relative regulation r45: for the relative set point function, there is a maximum limit. When the control works in relative mode, the set point calculated is lmited by r45. - Minimum value of calculated set point in relative regulation r46: for the relative set point function, there is a minimum limit. When the control works in relative mode, the set point calculated is lmited by r46. • Firmware parameters: (F-r*) These parameters cannot be set (display only: H95: software version of I/O board; H96-H97: software version of Driver 1, 2; H98: software version of the expansion; H99: software version of the µC2SE controller. Functions available with the clock board The alarm log is only active and operative if the clock board is fitted. The terminal shows whether the clock board is fitted by displaying the following parameters: - RTC hours t01: RTC hours - RTC minutes t02: RTC minutes - RTC day t03: RTC day - RTC month t04: RTC month - RTC year t05: RTC year The alarms are only shown on the local display. The controller saves the significant events that stop (alarms) or limit (warnings) the operation of the unit. Up to 25 events can be saved, highlighting: — Event code; — Start hours; — Start minutes; — Start day; — Start month; — End hours; — End minutes; — End day; — End month. µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 35 ENGLISH The log is accessed by pressing PRG+SEL for 5s and entering the password 44. The alarms saved are complete, as they include both the start and end of the event. The alarms can be deleted individually by pressing UP and DOWN for 5s when the desired event is displayed. If there are no alarms saved, “noH” is displayed. The table shows the possible alarms that can be saved: SV All. Circ. 1 All Circ. 2 All. Circ. 1 All Circ. 2 All. Gen. All. Circ. 1 All. cir. 2 All. Gen All. Sonde All. Sonde All. Sonde Display HP1 HP2 LP1 LP2 TP tC1 tC2 FL E1 E2 E3* Type High pressure circuit 1 High pressure circuit 2 Low pressure circuit 1 Low pressure circuit 2 General thermal overload Thermal overload circuit 1 Thermal overload circuit 2 Flow switch alarm Probe B1 alarm Probe B2 alarm Probe B3 alarm SV All. Sonde All. Sonde All. Sonde All. Sonde All. Sonde All. Gen. All. Circ. 1 All. Circ. 2 All. Gen. All. Evd 1 All. Evd 2 Display E4* E5 E6 E7* E8* ESP A1 A2 EHS Ed1 Ed2 Type Probe B4 alarm Probe B5 alarm Probe B6 alarm Probe B7 alarm7 Probe B8 alarm Expansion error Frost alarm circ. 1 Frost alarm circ. 2 High power supply voltage EVD1 tLAN error EVD2 tLAN error SV OFF All. Evd 2 All. Evd 1 All. Evd 2 All. Evd 1 All. Evd 2 All. Evd 1 All. Evd 2 All. Evd 1 All. Evd 2 All. Sonda µAD Display SH1 SH2 EP1 EP2 ES1 ES2 EU1 EU2 Eb1 Eb2 Et Type EVD1 overheat alarm EVD2 overheat alarm EEPROM error EVD 1 EEPROM error EVD 2 Probe error EVD 1 Probe error EVD 2 Valve open error EVD 1 start Valve open error EVD 2 start EVD 1 battery alarm EVD 2 battery alarm uAD terminal probe alarm - Start hours for 2nd set point in cooling t06 (I92): Hour when the second cooling set point starts(r21). - Start minutes for 2nd set point in cooling t07 (I93): Minutes when the second cooling set point starts (r21). - End hours for 2nd set point in cooling t08 (I94): Hour when the second cooling set point stops (r21). - End minutes for 2nd set point in cooling t09 (I95): Minutes when the second cooling set point stops (r21). If a digital input is configured as the second set point from external contact (e.g. p08 = 13) the time bands are ignored. If a digital input is configured as the second cooling set point from external contact and heating set point from time band (e.g. p08 = 14), the cooling time bands are ignored. The second set point from external contact input has priority over the second cooling set point from external contact and heating set point from time band. - Start hours for low noise in cooling t14: Start hours for low noise in cooling - Start minutes for low noise in cooling t15: Start minutes for low noise in cooling - End hours for low noise in cooling t16: End hours for low noise in cooling - End minutes for low noise in cooling t17: End minutes for low noise in cooling 36 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 Key to the table of alarms: *: if the probe is set for the compensation function, in the event of probe faults, the unit continues to operate. ON*: if the expansion card is not present. EVD 1= EVD400 connected to µC2SE (1st circ.) EVD 2= EVD400 connected to the expansion (2nd circ.) alarm display IO HP1 HP2 LP1 LP2 TP tC1 tC2 LA FL FLb E1 E2 E3* E4* E5 E6 E7* E8* Hc1-4 EPr EPb ESP EL1-2 dF1-2 d1-2 A1 A2 Ht Lt AHt ALt ELS EHS Ed1 Ed2 SH1 SH2 nO1 nO2 LO1 LO2 HA1 HA2 EP1 EP2 ES1 ES2 EU1 EU2 Eb1 Eb2 L Ed1 Ed2 PH1 PH2 SUL alarm type resetting Compressor pump fan heater Valve alarm OFF warning superv. variable - superv. variab. description Signal on display variab. type Digital Communication error with I/O board High pressure High pressure Low pressure Low pressure General overload Circuit 1 overload Circuit 2 overload advice Flow controller alarm Backup pump warning Probe B1 alarm Probe B2 alarm Probe B3 alarm Probe B4 alarm Probe B5 alarm Probe B6 alarm Probe B7 alarm Probe B8 alarm Hour warning C1-4 EEPROM error during operation EEPROM error at the start-up Expansion Error Zero cross Defrosting error Defrost on circuit in question Frost alarm circ. 1 Frost alarm circ. 2 High temperature Low ambient temp. High temperature at the start-up Low temperature at the start-up Low supply voltage High supply voltage EVD 1 tLAN error EVD 2 tLAN error EVD 1 superheat alarm EVD 2 superheat alarm MOP 1 warning MOP 2 warning LOP 1 warning LOP 1 warning High inlet temperature warning circ.1 High inlet temperature warning circ. 2 EVD 1 Eeprom error EVD 2 Eeprom error EVD 1 probe error EVD 2 probe error Open valve EVD 1 error at the start-up Open valve EVD 2 error at the start-up EVD 1 battery alarm EVD 2 battery alarm Low load warning tLan EVD 1 communication error tLan EVD 2 communication error Low pressure circ. 1 warning Low pressure circ. 2 warning low outlet temperature warning Automatic OFF OFF OFF OFF OFF Depends on P05 Depends on P05 Depends on P05 Depends on P05 Depends on P08 Depends on P08 Depends on P08 Depends on P08 Depends on P08 Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic OFF C1-2 OFF C3-4 OFF C1-2 OFF C3-4 OFF OFF C1-2 OFF C3-4 OFF OFF OFF OFF OFF OFF OFF OFF OFF - OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF - ON(60”) ON(60”) OFF 1 OFF 2 OFF OFF 1 OFF 2 OFF OFF OFF OFF OFF OFF OFF OFF OFF - OFF OFF OFF OFF OFF OFF OFF OFF - - ON ON ON ON ON ON ON ON* ON ON ON ON ON ON ON ON ON - ON ON ON ON 41 (R) 42 (R) 41 (R) 42 (R) 45 (R) 41 (R) 42 (R) 50 (R) 45 (R) 50 (R) 46 (R) 46 (R) 46 (R) 46 (R) 46 (R) 46 (R) 46 (R) 46 (R) 47 (R) 50 (R) Circuit 1 alarm Circuit 2 alarm Circuit 1 alarm Circuit 2 alarm General warning Circuit 1 alarm Circuit 2 alarm General advice General alarm General advice Probe alarm Probe alarm Probe alarm Probe alarm Probe alarm Probe alarm Probe alarm Probe alarm Compressor advice General advice Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Automatic Automatic Automatic Automatic - OFF OFF - OFF OFF - OFF OFF 100% - OFF OFF - OFF OFF - OFF ON ON* - OFF ON ON - 45 (R) 45 (R) 52 (R) 50 (R) - General alarm General alarm Fan advice General warning Signal on display Digital Digital Digital Digital - Depends on P05 Depends on P05 Automatic Depends on P05 Automatic OFF C1-2 OFF C3-4 OFF - OFF 1 OFF 2 OFF OFF - ON ON ON* ON* - ON ON ON 41 (R) 42 (R) 51 (R) 51 (R) 50 (R) Circuit 1 alarm Circuit 2 alarm Temperature advice Temperature advice General warning Digital Digital Digital Digital Digital Automatic OFF - OFF OFF - - ON 50 (R) General warning Digital Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic OFF OFF C1-2 OFF C3-4 OFF C1-2 OFF C3-4 - OFF - OFF OFF OFF OFFOFF- OFF - OFF - OFF ON ON ON ON - ON OFF ON ON ON ON ON 50 (R) 45 (R) 43 (R) 44 (R) 43 (R) 44 (R) 48 (R) 49 (R) 48 (R) 49 (R) 48 (R) General warning General alarm EVD 1 warning EVD 2 warning EVD 1 warning EVD 2 warning EVD 1 advice EVD 2 advice EVD 1 advice EVD 2 advice EVD 1 advice Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Digital Automatic - - - - - - ON 49 (R) EVD 2 advice Digital Automatic Automatic Automatic Automatic Automatic OFF C1-2 OFF C3-4 OFF C1-2 OFF C3-4 OFF C1-2 - OFFOFFOFFOFFOFF - - ON ON ON ON ON - 43 (R) 44 (R) 43 (R) 44 (R) 43 (R) EVD 1 warning EVD 2 warning EVD 1 warning EVD 2 warning EVD 1 warning Digital Digital Digital Digital Digital Automatic OFF C3-4 - OFF - - ON - 44 (R) EVD 2 warning Digital Automatic Automatic Automatic Automatic OFF C1-2 OFF C3-4 OFF C1-2 - OFF OFF OFF - - ON ON ON - 43 (R) 44 (R) 43 (R) EVD 1 warning EVD 2 warning Signal on display EVD 1 warning Digital Digital Digital Automatic OFF C3-4 - OFF - - ON - 44 (R) EVD 2 warning Digital - - - - - - - - - Signal on display Signal on display Signal on display - Table 6.a Note: The warning relay differs from the alarm relay as it is only activated for warnings, that is, signals only, which have no direct effect on the operation of the unit, and the display does not show the alarm symbol (bell). N.B. The alarm relating to the circuit with the fault must not interact with the operation of the other circuit, as long as the condenser is not shared in common. µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 37 ENGLISH 6. TABLE OF ALARMS ENGLISH IO: communication error with I/O board If the control loses communication with I/O board, all of the system will be inhibited to prevent the unit being damaged. The alarm relay will be activated and the message will be visible on the display with fixed red LED. HP1: High pressure circuit 1 The alarm is detected irrespective of the status of the pump and the compressors. The compressors corresponding to circuit 1 are immediately stopped (ignoring the set protection times), the buzzer and alarm relay are activated, and the display starts flashing. The fans corresponding to the condenser in circuit 1 are activated at maximum speed for 60 s, so as to oppose the alarm situation, after which they are switched OFF. This alarm may also be generated when the high pressure limit is exceeded (valid only when the pressure transducer is fitted) set by the parameter P18, which to be enabled must be greater than 3.0 bars, due to the corresponding hysteresis. HP2: High pressure circuit 2 As for HP1 but relating to circuit 2. LP1: Low pressure circuit 1 The alarm depends on P15, P7 and P3. P15= 0, P07= 0: the alarm is detected only if the compressors in circuit 1 are ON, and after the time P03 from when the compressors started, otherwise it is immediate. P15= 1, P07= 0: the alarm is detected even if the compressors in circuit 1 are off, after the time P03. P15= 0, P07= 1: the alarm is detected only if the compressors in circuit 1 are ON, and after the time P03 from when the compressors started, otherwise it is immediate, and if in heat pump mode, is activated for pressure values less than 1 bar. P15= 1, P07= 1: the alarm is detected also if the compressors in circuit 1 are Off, after the time P03, and if in heat pump mode, is activated for pressure values lower then 1 bar. The hysteresis for this alarm is 1 bar. LP2: Low pressure circuit 2 As for LP1 but relating to circuit 2. PH1: Compressor part load circuit 1 Indicates the part load of circuit 1 due to high pressure. This situation is signalled by the message “PH1” on the display the activation of the warning relay. PH2: Compressor part load circuit 2 As for PC1, but for circuit 2. tP: General thermal overload The alarm is detected irrespective of the status of the pump and the compressors. The compressors, the pumps and fans stop (without observing the protection times) or are inhibited from starting, the alarm relay is activated, the display flashes the corresponding message, and the LED flashes. It can be reset either manually or automatically (see par. P08, P09, P10, P11, P12, P13). tC1: Thermal overload circuit 1 As for tP but relating to circuit 1 tC2: Thermal overload circuit 2 As for tC1 but relating to circuit 2. LA: generic warning This represents a generic warning that appears on the display, from digital input, without modifying the operation of the unit. With the 1st circuit module only, the alarm relay is activated, while with the expansion card the warning relay can be used. FL: flow alarm This alarm is detected only if the pump is ON (excluding the delays when starting P01 and in steady operation P02), irrespective of the status of the compressor. All of the outputs are disabled: pump, compressor (without observing the OFF times), condenser fan, and the buzzer sounds, the alarm relay is activated and the display flashes. The presence of the utility water pump must be enabled (H50). It can be reset either manually or automatically (see P08, P09, P10, P11, P12, P13). FLb: Backup pump warning The warning activates the warning relay and displays the message “FLb”; reset is manual. This indicates the operation of the backup pump (if present) due to a probable fault on the main pump, suggesting that maintenance is required. If the flow alarm features automatic reset, the controller will make 10 attempts to re-start the pumps, after which the FL alarm will replace FLb. If the flow alarm features manual reset, when first activated the controller will display the alarm FLb, switching over the pumps; when activated again the FL alarm will replace FLb. E1 to E8: probe error detected even when the unit is in Standby The presence of a probe alarm causes the deactivation of the compressor, the condenser fans, the pump (outlet fan in AIR/AIR units) and the heaters (so as to avoid fires in the air/air units); the buzzer and alarm relay are activated, and the display starts flashing. If the probe has a compensation function, the unit will continue a operate correctly, with the exception of the corresponding function, and the warning relay will be activated and a message shown on the display, from E1 to E8 for probes from B1 to B8. 38 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 ENGLISH Hc1 to Hc4: compressor operating hour limit exceeded warning When the number of operating hours for the compressor exceeds the maintenance threshold (as default equal to zero, and consequently the function is disabled), the maintenance request signal is activated. The buzzer and the alarm relay are not activated, however the warning relay is activated (with the expansion card fitted). Epr, EPb: EEPROM error A problem has occurred when saving the parameters to the unit’s non-volatile memory (EEPROM); in the event of an Epr error, the µC2SE continues to perform the control functions with the data present in the volatile memory (RAM), where there is a physical copy of all of the data. After the first power failure the configuration will be lost. The buzzer and the alarm relay are not activated. If the occurs when starting the unit, “EPb”, the controller will not operate. ESP: communication error with expansion card If the controller loses communication with the expansion card, the entire system will be stopped to avoid adversely affecting the unit. The alarm relay is activated and the display will show the message, with the red LED on steady. EL1-2: warning, zero crossing error circuit 1-2 If the controller detects errors in the power supply, control may be lost over the fan speed. In this case, the display will show a warning, and the fans will be controlled at maximum speed. The alarm is reset automatically, so as to not affect the operation of the unit. If the expansion card is used, the warning relay is activate) dF1-2: warning, end defrost circuit 1-2 due to maximum time If the defrost ends after the maximum time when end defrost by temperature or from external contact has been selected, the unit displays the text dF1 for circuit 1 or dF2 for circuit 2. The message is cancelled using the delete alarm procedure or when the next correct defrost cycle is completed. The buzzer and the alarm relay are not activated. If the expansion card is used, the warning relay is activated (if used). A1: antifreeze alarm outlet limit circuit 1 The alarm is only detected in water chillers (H01= 2, 3, 4, 5 or 6) by the evaporator water outlet probe (B2/B6) or, if the electronic expansion driver (EVD) is connected to the tLAN, based on the evaporation temperature sent by the driver. The evaporator water outlet temperature is compared against the threshold A01, while the evaporation temperature is compared against the threshold A14. The compressors in circuit 1 and the condenser fans in circuit 1 are immediately stopped, the buzzer and alarm relay are activated, and the display starts flashing. If the µC2SE is in Standby, the alarm condition is not detected, and only the heaters are managed. Reset depends on parameter P5: 1. in the event of automatic reset, the unit restarts automatically if the temperature is above the value A01+A02 or A14+A02. 2. in the event of manual reset, the unit can restart manually even if the alarm is active. After the time A03, if the alarm persists the unit will stop again. For air/air units the parameter becomes the antifreeze-outlet limit alarm set point. If the outlet limit is active, the freecooling damper is forced closed and the message SUL is shown on the display. A2: antifreeze alarm circuit 2 As for A1 but relating to circuit 2 Ht: high temperature warning This alarm is activated when the threshold is exceeded (read by B1), set for the parameter P16. It is delayed at power ON by the parameter P17 and causes the activation of the alarm relay and the buzzer, without deactivating the outputs. It is reset automatically when conditions that caused the alarm are no longer present. Lt: low temperature warning For direct expansion units (H01=0, 1) the alarm is used to measure a low room temperature using probe B1 or B2 (depending on par. A06). The alarm may be reset manually or automatically, and depends on the parameter P05. If the expansion is present, the corresponding relay is activated; in the event of µC2SE module only, the alarm relay will be used. AHt: high temperature warning when starting the system The advice does not activate the relay, and displays the message “AHt”. ALt: low temperature warning when starting the system The advice does not activate the relay, and displays the message “ALt”. ELS/EHS: warning, low/high power supply alarm If the power supply voltage is too low or too high, the corresponding message is displayed. In these cases, the correct operation of the µC2SE is no longer guaranteed. In the low voltage conditions only the requests to deactivate the loads are effected. Any start-up requests remain pending. The high voltage condition involves the deactivation of all the energised relays. L: Low load warning The warning does not activate the relay and displays the message “ L ”; reset is automatic. µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 39 ENGLISH D1: defrost signal circuit 1 When the defrost is on circuit 1, the display shows the message D1. D2: defrost signal circuit 2 When the defrost is on circuit 2, the display shows the message D2. Driver All the driver alarms on the µC2SE that stop the unit feature automatic reset. Consequently, the possibility to select the automatic resetting of the entire system must be selected for the drivers by setting the corresponding parameters. The µC2SE can send the Go Ahead command according to the normal procedure for resetting the alarms from the keypad. Ed1: tLan communication error with Driver 1 The alarm is generated after a fixed time (5 s) from when the µC2SE loses contact with Driver 1. In this case, circuit 1 is disabled for safety reasons. Ed2: tLan communication error with Driver 2 (expansion card) As for Ed1, but relating to driver 2. SH1: low superheat alarm circuit 1 The low superheat alarm for circuit 1, after a fixed time (5 s), inhibits the circuit 1 for safety reasons. The risk is that the compressors will flood. SH2: low superheat alarm circuit 2 As for SH1, but relating to driver 2 nO1: MOP warning (maximum operating pressure) circuit 1 The warning appears on the display and, if the expansion card is fitted, the corresponding relay is activated. nO2: MOP warning (maximum operating pressure) circuit 2 The warning appears on the display and, if the expansion card is fitted, the corresponding relay is activated. LO1: LOP warning (lowest operating pressure) circuit The warning appears on the display and, if the expansion card is fitted, the corresponding relay is activated. LO2: LOP warning (lowest operating pressure) circuit 2 As for LO1, but relating to driver 2 HA1: high evaporator temperature warning circuit 1 The warning appears on the display and, if the expansion card is fitted, the corresponding relay is activated. HA2: high evaporator temperature warning circuit 2 As for HA1, but relating to driver 2. EP1: EEPROM error driver 1 The circuit 1 is disabled for safety reasons, as the status of Driver 1 is not known. EP2: EEPROM error driver 2 As for EP1, but relating to driver 2. ES1: probe error driver 1 The circuit 1 is disabled for safety reasons, as the status of Driver 1 is not known. ES2: probe error driver 2 As for ES1, but relating to driver 2. EU1: EVD 1 error, valve open when starting If when starting the system the Driver detects that the valve is still open, an alarm is sent to the µC2SE that stops the compressors and the fans in the corresponding circuit. EU2: EVD 2 error, valve open when starting As for EU1, but relating to EVD 2. Eb1: EVD 1 battery alarm The EVD 1 battery alarm stops the compressors from starting so as to prevent the risk of liquid returning to circuit 1, and disables the corresponding fans. Eb2: EVD 2 battery alarm The EVD 2 battery alarm stops the compressors from starting so as to avoid the risk of liquid returning to circuit 2, and disables the corresponding fans. 40 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 ENGLISH 7. CONNECTIONS, ACCESSORIES AND OPTIONS 7.1 Connection diagram Below is the connection diagram for the µC2SE. Panel version N AUX10 AUX6 AUX7 AUX8 AUX9 Line L No6 C6/7C6/7C8/9 x C10 No7 No8 No9 C8/9 x No10 Tx/Rx GND Top I/O Bottom GND Tx/Rx GND B8 V+ G0 B5 B6 B7 ID10 ID8 ID6 G GND GND Y2 GND ID9 ID7 P N EV Driver EV driver ESP pressure probe L Line EV driver Expansion board N Line Tx/Rx GND AUX5 AUX2 AUX3 L tLAN AUX4 EV Driver No1 C1/2 C1/2 C3/4 x C5 No2 No3 No4 C3/4 x No5 GND B4 G0 B1 B2 V+ B3 ID5 ID3 ID1 Key/SPV G GND GND Y1 GND ID4 ID2 P pressure probe To program key RS485 option N Line L Fig. 7.a To serial link I/O layout µC2SE B1 B2 B3 B4 (universal) ID1* ID2* ID3 ID4 ID5 Y1 C1/2-NO1 C1/2-NO2 C3/4-NO3 C3/4-NO4 C5-NO5 Expansion B5 B6 B7 B8 (universal) ID6** ID7** ID8 ID9 ID10 Y2 C6/7-NO6 C6/7-NO7 C8/9-NO8 C8/9-NO9 C10-NO10 Description Programmable I/O Programmable I/O Programmable I/O Programmable I/O Programmable I/O (*= Any of the options for P08 can be selected (see Table 5.11)) Programmable I/O (*= Any of the options for P08 can be selected (see Table 5.11)) Programmable I/O Programmable I/O Programmable I/O Programmable I/O Programmable I/O Programmable I/O Programmable I/O Programmable I/O Programmable I/O Table 7.a Description Programmable I/O Programmable I/O Programmable I/O Programmable I/O Programmable I/O (**= Any of the options for P08 can be selected, except for E/I and E/I delay.) Programmable I/O (**= Any of the options for P08 can be selected, except for E/I and E/I delay.) Programmable I/O Programmable I/O Programmable I/O Programmable I/O Programmable I/O Programmable I/O Programmable I/O Programmable I/O µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 Table 7.b 41 7.2 Expansion card ENGLISH This device allows the µC2SE to manage the second refrigerant circuit on chillers, heat pumps and condensing units with up to 4 hermetic compressors. The following figure shows the connection diagram for the µC2SE expansion card, code MCH200002*. N EV Driver Line EV driver L No6 C6/7 C6/7 C8/9 x No7 No8 No9 C8/9 x No10 C10 Tx/Rx GND Top Expansion board Bottom GND Tx/Rx GND B8 V+ remote ON/OFF high press. multi funct. low press. multi funct. G GND GND Y GND ID9 ID7 inlet probe outlet probe cond. probe G0 B5 B6 B7 ID10 ID8 ID6 P temperature probe digital input t-LAN N pressure probe L Line Fig. 7.b NOTE: The expansion features two LEDs on the main board (to see these, remove the top or bottom door), which display its status by the following messages: ON Board powered green LED red LED Flashing Board powered and serial communication with µC2SE in progress 1 flash: Probe fault alarm 2 flashes: Zero crossing alarm (mains frequency not detected) 3 flashes: Serial communication alarm with EVD 4 flashes: Serial communication alarm with µC2SE Table 7.c The alarms are displayed in sequence and are separated from each other by pauses. 7.3 EVD4*: Electronic expansion valve driver This device is used to control electronic expansion valves. The device is connected to the µC2SE via a tLAN serial line. The condensing pressure probe must be connected to the µC2SE, which then sends the reading to the driver. Nota: for all other information on the connections, refer to the EVD4* driver manual. PHOENIX¡ MC1,5/3-ST-3,81 1 GND 2 COM NO PHOENIX¡ GMSTB 2,5/2 ST 3 GND 4 EEV driver FCSER00000 MOLEX¡ Mini-Fit 538-39-01-2140 G Vbat DI1 S4V S3 S2 S1 G0 GND DI2 S4I Vr1 Vr2 OC GNX RT+ RT- MOLEX¡ Mini-Fit 538-39-01-2060 Fig. 7.c 42 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 7.4 Fan speed control board (code MCHRTF*) The phase cutting boards (code MCHRTF****) are used to control the speed of the condenser fans. 2 ENGLISH 1 IMPORTANT: The power supply to the µC2SE (G and G0) and the MCHRTF**** board must be in phase. If, for example, the power supply to the µC2SE system is three-phase, make sure that the primary of the transformer supplying the µC2SE board is connected to the same phase that is connected to terminals N and L on the speed control board; therefore, do not use 380 Vac/24 Vac transformers to supply the controller if the phase and neutral are used to directly power the speed control boards. Connect the earth terminal (where envisaged) to the earth in the electrical panel. GND Y - + Key: 1. 2. 3. 3. to µchiller; earth; to motor. al motore. LOAD LINE 3 220 Vac Fig. 7.d to µchiller 7.5 Fan ON/OFF control board (code CONVONOFF0) 24 Vac Y GND The relay boards (code CONVONOFF0) are used for the ON/OFF management of the condenser fans. The control relay has a switchable power rating of 10 A at 250 Vac in AC1 (1/3 HP inductive). 1 2 3 4 5 6 7 8 No Com Nc Fig. 7.e to µchiller 7.6 PWM to 0 to 10Vdc (or 4 to 20 mA)conversion board for fans (code CONV0/10A0) 24 Vac Y GND 1 2 3 4 The CONV0/10A0 boards convert the PWM signal at terminal Y on the µC2SE to a standard 0 to 10 Vdc (or 4 to 20 mA) signal. The FCS series three-phase controllers can be connected to the µC2SE without using this module. 5 6 7 8 G0 0-10V G0 4-20mA Fig. 7.f 7.7 Minimum and maximum fan speed calculation LOAD LINE L N N Vac? The operation is now completed. µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 + - This procedure should only be performed when the fan speed control boards are sued (code MCHRTF*). it must be stressed that if the ON/OFF modules (code CONVONOFF0) or alternatively the PWM to 0 to 10 V converters (code CONV0/10A0) are used, parameter F03 should be set to zero, and parameter F04 to the maximum value. Given the different types of motors existing on the market, the user must be able to set the voltages supplied by the electronic board corresponding to the minimum and maximum speeds. In this regard (and if the default values are not suitable), proceed as follows: • set parameter F02= 3 and set F03 and F04 to zero; • the condenser control set point (evaporator in HP mode) has been modified to take the output signal to the maximum value (PWM); • increase F04 until the fan operates at a sufficient speed (make sure that, after having stopped it, it can rotate freely when released); • “copy” this value to parameter F03; this sets the voltage for the minimum speed; • connect a voltmeter (set for AC, 250V) between the two “L” terminals (the two external contacts); • increase F04 until the voltage stabilises at around 2 Vac (inductive motors) or 1.6, 1.7 Vac (capacitive motors). Once the value has been found, it will be evident that even when increasing F04 the voltage no longer decreases. In any case do not increase F04 further so as to avoid damaging the motor; • restore the correct condenser set point (evaporator in HP mode). Fig. 7.g 43 L 7.8 Programming key (code PSOPZKEYA0) ENGLISH The programming keys PSOPZKEY00 and PSOPZKEYA0 for CAREL controllers are used for copying the complete set parameters for µC2SE. The keys must be connected to the connector (4 pin AMP) fitted on the controllers, and can work with the instruments ON or OFF, as indicated in the operating instructions for the specific controller. The two main functions (upload/download) that can be selected through two dip-switches (which are placed under the battery cover). They are: • Loading to the key the parameters of a controller (UPLOAD); • Copying from the key to one or more controllers (DOWNLOAD). Fig. 7.h Warning: the copying of the parameters is allowed only between instruments with the same code. Data loading operation to the key is always allowed. To make identification of the key easier CAREL has inserted a label on which you can describe the loaded programming or the machine to which you are referring. Fig. 7.i IMPORTANT NOTE: the key can be used only with controllers µC2SE that have the same Firmware version. UPLOAD - copying the parameters from an instrument to the key: • open the rear hatch of the key and place the two dip-switches in the OFF position (see Fig. 7.j.a). Close the hatch; • connect the key to the connector of the instrument; • press the button on the key and keep it pressed, checking the LED signal sequence: at first it is red, after a few seconds it becomes green; • if the sequence of signals is as indicated above, the copying operation has been completed correctly (green LED ON), the button can be released and the key disconnected from the instrument; in case of different signals: if the green LED doesn’t turn on or if there are some flashes, there’s a problem. Refer to the corresponding table for the meaning of the signals. Fig. 7.j.a DOWNLOAD - copying the parameters from the key to the instrument: • open the rear hatch of the key and place the dip-switch n. 1 in the OFF position and the dip-switch n. 2 in the ON position (see Fig. 7.j.b). Close the hatch; • connect the key to the connector of the instrument; • press the button on the key and keep it pressed, checking the LED signal sequence: at first it is red, after a few seconds it becomes green; • if the sequence of signals is as indicated above, the copying operation has been completed correctly (green LED ON), the button can be released; after a few seconds the LED turns off and the key can be disconnected from the instrument; • in case of different signals: if the green LED doesn’t turn on or if there are some flashes there’s a problem. Refer to the corresponding table for the meaning of the signals. The operation takes maximum 10 seconds to complete. If after this period the completed operation signal hasn’t yet appeared, i.e. the green LED ON, try releasing and pressing the button again. In the event of flashes, refer to the corresponding table for the meaning of the signals. Fig. 7.j.b LED signal error red LED flashing Flat batteries at the beginning of the copying green LED Flat batteries at the end flashing of the copying (only on PSOPZKEY00) Alternate red/ Not compatible green LED instrument flashing (orange signal) red and green Copying error LEDs ON red LED always Data transmission error ON LEDs OFF Batteries disconnected Power supply not connected meaning and solution The batteries are flat, the copying cannot be carried out. Replace the battery (only on PSOPZKEY00). The copying operation has been carried out correctly but at the end of the operation the voltage of the batteries is low. It is advisable to replace the batteries. The setup of the parameters cannot be copied since the model of the connected parameters is not compatible. Such error happens only with the DOWNLOAD function, check the controller code and make the copy only on compatible codes. Error in the copied data. Repeat the operation; if the problem persists, check the batteries and the connections of the key. The copying operation hasn’t been completed because of serious data transmission or copying errors. Repeat the operation, if the problem persists, check the batteries and the connections of the key. Check the batteries (for the PSOPZKEY00) Check the power supply (for the PSOPZKEYA0) Table 7.d Technical specifications Power supply to the PSOPZKEY00 Power supply to the PSOPZKEYA0 Operating conditions Storage conditions Case - Use three 1.5 V 190 mA batteries (Duracell D357H or equivalent) - Maximum current supplied 50 mA max. - switching power supply: Input 100 to 240 V~; (-10%, +10%); 50/60 Hz; 90 mA. Output: 5 Vdc; 650 mA 0T50°C r.H. <90% non-condensing -20T70°C r.H. <90% non-condensing Plastic, dimensions 42x105x18 mm including prod and connector Figs. 1 and 2 Table 7.e (Here we have dealt only with the base functions of the instrument. For the remaining specific functions, see the manual of the instrument that is being used). 44 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 7.9 RS485 serial options ENGLISH RS485 serial option for µC2SE panel version (code MCH2004850) The MCH2004850 serial option is used to connect the µC2SE controller to a supervisor network via a standard RS485 serial line. This option uses the input normally associated with the programming key, which has the dual function of key connector/serial communication port. Fig. 7.k 7.10 Terminals The µC²SE features the following user interfaces: Remote terminal The remote terminal allows the complete configuration of the µC2SE from a remote position. The buttons and indications on the display faithfully reproduce the µC2SE user interface. In addition, PlantVisor can be connected to the remote terminal using the special accessory. Product code: MCH200TP00 for panel installation MCH200TW00 for built-in assembly For further information see the instruction sheet +050001065. Fig. 7.l µAD µAD is the µC2SE room terminal. This terminal, fitted with built-in temperature and humidity probes, controls the temperature-humidity conditions in the environment where its is installed, interacting with the units controlled by the µC2SE. The µAD can be used to set time bands, the temperature and humidity set point, switch the system on/off and change operating mode simply and intuitively. Product code: ADMA001000: with NTC probe ADMB001010: with NTC probe, RTC and buzzer ADMG001010: with NTC and humidity probe, RTC and buzzer ADMH001010: with NTC and humidity probe, RTC, buzzer and backlighting For further information see the instruction sheet +05000750 and the manual +030220465. Fig. 7.m µAM µAM is the µArea controller compatible with the µC2SE. This can control up to 10 fan coils (fitted with the e-droFAN electronic controller). By analysing the temperature-humidity conditions in the different rooms, µAM optimises the temperature of the water produced by the chiller/HP, improving power consumption, performance and comfort. In addition, the µAM centralises the data, such as set point, heat/cool mode and on/off for the individual fan coil and the entire system, including time bands. Product code: ADEC001010: with NTC probe, RTC, buzzer and backlighting ADEH001010: cwith NTC and humidity probe, RTC, buzzer and backlighting Fig. 7.n For further information see the instruction sheet +050000740 and the manual +030220460. µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 45 ENGLISH 8. DIMENSIONS The following are the mechanical dimensions of each component in the µC2SE controller; all the values are expressed in millimetres. Note: the dimensions include the free connectors inserted. 33 MCH20000* µC2SE panel mounting version 75 64 74 drilling template 71x29 mm comp x100 PRG Sel panel mounting overall dimensions 91,5x36x5 mm Fig. 8.a CONVONOFF0 and CONV0/10 A modules 88 44 110 Expansion board for µC2SE Expansio n board Expansion board DIN rail mounting 36 60 11 60 70 Fig. 8.c Fig. 8.b 24 RS485 serial card: codeMCH2004850 5 31 3 56 59 75 85 5 Fig. 8.d 46 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 Model MCHRTF04C0 MCHRTF08C0 MCHRTF12C0 A (component side) 43 75 75 B 100 100 100 C 40 58 58 D 50 82 82 ENGLISH MCHRTF series single-phase speed controllers E 107 107 107 Note: the version with screw teminals code MCHRTF*D0 is available on request Table 8.a D A D A C 8 e 12 A 4A B E Fig. 8.e Model MCHRTF10C0 Table 8.b 90 3 12.5 74.5 19 19 50 35.5 84 64 Ø4 15 29.5 3 74.5 12.5 Fig. 8.f µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 47 C B E ENGLISH 9. CODES Description µC2SE single circuit, 2 compressors, panel mounting µC2SE single circuit, 2 compressors, panel mounting (20 pcs. multiple package) µC2SE expansion board for 2nd. circuit maximum 4 compressors µC2SE expansion board for 2nd. circuit maximum 4 compressors (10 pcs. multiple package) RS485 optional board for µC2SE panel version Programming key for µC2SE ON/OFF fan card (only screw terminals) PWM - 0 to 10 V fan card (only screw terminals) Temperature probes for regulation or condensation control ***depending on the length (015= 1.5 m, 030= 3 m, 060=6 m) Pressure probes for condensing pressure control ** depending on the pressure (13= 150 PSI, 23= 75 PSI, 33= 500 PSI) Connectors kit for code MCH2000001 (multiple package 20 pcs) Connectors kit for code MCH2000001 (multiple package 10 pcs) Minifit connectors kit + 1 meter length for code MCH2** Minifit connectors kit + 2 meter length for code MCH2** Minifit connectors kit + 3 meter length for code MCH2** Remote terminal for MCH20000** for panel installation MCH200TP0* Remote terminal for MCH20000** for wall-mounting MCH200TW0* Supervisor serial connection kit for remote terminal Fan speed PWM 4 A/230 Vac Fan speed PWM 8 A/230 Vac Fan speed PWM 12 A/230 Vac Fan speed PWM 10 A/230 Vac 1 Pc. Nor. Ind. Fan speed PWM 10 A/230 Vac 10 Pc. Nor. Ind. Code MCH2000050 MCH2000051 MCH2000020 MCH2000021 MCH2004850 PSOPZKEY00 CONVONOFF0 CONV0/10A0 NTC***WP00 SPK*R* MCH2CON001 MCH2CON021 MCHSMLCAB0 MCHSMLCAB2 MCHSMLCAB3 MCH200TP0* MCH200TW0* MCH200TSV0 MCHRTF04C0 MCHRTF08C0 MCHRTF12C0 MCHRTF10C0 MCHRTF10C1 Table 9.a 10. TECHNICAL SPECIFICATIONS AND SOFTWARE UPDATES 10.1 Technical specifications Electrical specifications In the following specifications “Group A” defines the grouping of the following outputs: valve, pump, compressor, heater. Power supply 24 Vac, range +10/–15 %; 50/60 Hz Maximum power input: 3W Fuse (compulsory) in series with the power supply to the µC2SE: 315mAT 12 pin connector Max. current 2 A for each relay output, extendable to 3 A for one single output Relays Max current at 250 Vac: EN60730: resistive: 3A, Inductive: 2A cos =0.4 60,000 cycles UL: Resistive: 3A, 1 FLA, 6 LRA cos =0.4 30,000 cycles For further information refer to the characteristics shown in Figure 10.a Minimum interval between communications (each relay): 12 s (the manufacturer of the unit that the device is integrated into must ensure the correct configuration so as to respond to this specification Type of microswitching: 1 C Insulation between relays in group A: functional Insulation between the relays in group A and the very low voltage parts: reinforced Insulation between relays in group A and the signal relays: primary Insulation between the signal relays and the very low voltage parts: reinforced Insulation between the relays and the front panel: reinforced Digital inputs Electrical standard: voltage-free contacts Closing current to earth: 5 mA Maximum closing resistance: 50 W Analogue inputs B1, B2, B3, B4: NTC CAREL temperature probes (10 kW at 25 °C) The response time depends on the component used, typical value 90 s B4: NTC temp. probes (10 kW at 25 °C) or CAREL 0 to 5 V ratiometric pressure probes SPKT00**R* Fan output Control signal for CAREL modules MCHRTF****, CONVONOFF* and CONV0/10A* Phase width modulation (settable width) or modulation of the duty cycle No-load voltage: 5V ± 10% Short-circuit current: 30 mA Minimum output load: 1 kW Front panel index of protection IP55 Storage conditions -10T70 °C – humidity 80 % rH non-condensing Operating conditions -10T55 °C – humidity <90 % rH non-condensing Degree of pollution Normal Cat. of resist. to heat and fire D (RU94 V0) PTI of the insulating materials All the insulating materials have PTI250 V Software class and structure A Period of electric stress across Long insulating parts 300 number of operations (x 104) 200 120 Vac 100 250 Vac 30 Vdc AC 120 V cosø =0.7 50 AC 250 V cosø =0.7 30 20 10 5 3 2 1 0 30 Vdc 120 Vac cosø =0.4 250 Vac cosø =0.4 30 Vdc 1 2 3 4 5 current on contacts (A) Fig. 10.a Homologations CE/RU (File EI98839 sez.16) Table10.a Nota: all the relays must have the common terminals (C1/2, C3/4, C6/7, C8/9) connected together. 48 µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 Functional characteristics Pressure measurement error Temperature probes: range -40T80 °C, 0.1 °C Range -20T20 °C, ±0.5 °C (excluding probe) Range -40T80 °C, ±1.5 °C (excluding probe) The % error with a voltage reading with a range of input from 0.5 to 4.5 is ± 2% (excluding probe). The error in the converted value may vary according to the settings of parameters /9, /10, /11, /12 ENGLISH Resolution of the analogue inputs Temperature measurement error Table 10.b Characteristics of the connectors The connectors may be purchased using CAREL code (MCHCON0***) or from the manufacturer Molex® Molex® codes of the connector 39-01-2120 39-01-2140 Number of pins 12 14 Table 10.c Max. number of insertion/removal cycles for the connectors: 25 cycles Code of the contacts according to the cross-section of the connection cables to the 12- and 14-pin connectors (use the special Molex® tool code 69008-0724 for crimping Molex® code of the contact 39-00-0077 39-00-0038 39-00-0046 Cross-section of cables allowed AWG16 (1,308 mm2) AWG18-24 (0,823...0,205 mm2) AWG22-28 (0,324...0,081 mm2) Table 10.d In addition, the pre-wired kits MCHSMLC*** are also available WARNINGS • If one transformer is used to supply both the µC2SE and the accessories, all the G0 terminals on the various controllers or the various boards must be connected to the same terminal on the secondary, and all the G terminals to the other terminal on the secondary, so as to avoid damaging the instrument; • For use in residential environments, use shielded cable (two wires + shield earthed at both ends, AWG 20-22) for the tLAN connections (EN 55014-1). • Avoid short-circuits between V+ and GND so as to not damage the instrument; • Perform all the maintenance and installation operations when the unit is not connected to the power supply; • Separate the power cables (relay outputs) from the cables corresponding to the probes, digital inputs and serial line; • Use a transformer dedicated exclusively to the electronic controllers for the power supply. Protection against electric shock and maintenance warnings The system made up of the control board (MCH200003*) and the other optional boards (MCH200002*, MCH200485*, MCHRTF****, CONVONOFF*, CONV0/10A*, EVD000040*) represents a control device to be integrated into class 1 or class 2 appliances. The class of protection against electric shock depends on how the control device is integrated into the unit built by the manufacturer. Disconnect power before working on the board during assembly, maintenance and replacement. The protection against short circuits must be guaranteed by the manufacturer of the appliance that the controller will be fitted on. Maximum length of the NTC/ratiometric probe NTC/ratiometric probe connection cables digital input connection cables power output connection cables fan control output connection cables power cables 10 m 10 m 5m 5m 3m Table 10.e 10.2 Software updates 10.2.1 Notes for version 1.1 First release. 10.2.2 Notes for version 1.2 Optimised use of the programming key. 10.2.3 Notes for version 1.3 Implemented direct current operation. Use EXP. version 1.5 or higher. 10.2.4 Notes for version 1.4 Implemented a differential relating to the working set point for electric heaters in air- and water-source units. Implemented cooling only air-source unit with electrical heaters operating in heating mode only. Implemented new logic for the activation of the alarm relays. Implemented new logic for the management of the high pressure alarm. Implemented management of minimum damper opening. Implemented damper inactivity time in freecooling or freeheating mode. Optimised management of damper closing for minimum outlet temperature limit. Implemented alarm reset from µAD. 10.2.5 Notes for version 1.6 Improved Modbus communication with supervisory system 10.2.6 Notes for version 1.7 Implemented second antifreeze set point (A14) µC2SE process chiller +030220416 - rel. 1.1 - 27.04.2010 49 Notes: CAREL reserves the right to modify the features of its products without prior notice CAREL S.p.A. Via dell’Industria, 11 - 35020 Brugine - Padova (Italy) Tel. (+39) 049.9716611 - Fax (+39) 049.9716600 e-mail: carel @ carel. com - www .carel. com µC2SE chiller process +030220416 - rel. 1.1 - 27.04.2010 Agenzia/Agency:
µC
2
SE process chiller +030220416 — rel. 2.2 — 25.01.2013
E1…E4: probe error detected also with machine in Stand-by. The presence of a
probe alarm leads to the deactivation of the compressor, the condenser fan, pump
and heater; the alarm relay and display flashing are activated. In the event of
external probe fault and compensation function enabled, the unit continues to
operate correctly, the function deactivates, a warning is activated via the alarm relay
and the message appears on the display from E1 to E4 for probes B1 to B4.
Hc1, Hc2: compressors/pumps operating hour limit exceeded warning. When the
number of operating hours for the compressor exceeds the maintenance threshold
(see par. c14), the maintenance request signal is activated.
EPr, EPb: EEPROM error
It is a parameters memorisation problem in the non-volatile machine memory
(EEPROM); µC
2
SE continues to make the regulations with the data present in the
volatile memory (RAM) if it is EPr, where there is a physical copy of all data. The
configuration is lost if a power-cut occurs. The alarm relay is not activated. If the
“EPb” error occurs on switch-on, the controller remains blocked.
EL1: zero crossing error warning. If the controller detects errors in the power
supply voltage, it is possible to lose control of fan speed. In this case, the display
will show the warning, the fans will be ordered at maximum speed only if at least
one compressor is active. Reset will be automatic, so as not to penalise unit
operation. The function is enabled only with F02= 3.
A1: anti-freeze alarm. A07 establishes the minimum limit that can be used to set
the anti-freeze alarm set point (A01). The alarm is detected via the evaporator
output water probe (B2) or, if there is an electronic expansion valve driver (EVD)
connected in tLAN, on the basis of the evaporation temperature communicated by
the driver itself. The temperature of the water leaving the evaporator is compared
with the alarm threshold A01, while the evaporation temperature is compared with
the threshold A14. The compressors are switched off immediately; the condenser
fan is activated along with the alarm relay and flashing display. Whenever µC
2
SE is
in stand by the alarm condition is not detected, but just the heaters are managed.
Reset depends on parameter P05:
1. in the event of automatic reset, the unit re-starts automatically if the temperature
is above the value of A01+A02 or A14+A02.
2. in the event of manual reset, the unit re-starts manually also if the alarm is active.
After time A03, the unit blocks again if the alarm remains.
Ht: high temperature warning. Signalling is activated if the threshold is exceeded
(read by B1), which is stated in parameter P16. This is delayed on switch-on by the
parameter P17 and causes switch-on of the alarm relay without deactivation of the
outputs and reset is automatic when the conditions that generated it have been
removed.
Lt: low temperature warning. This alarm can be reset manually or automatically
and this depends on parameter P05. The effect of the Ht/Lt alarms on the
compressor depends on parameter H24.
Par. Description
Def
Min
Max
U.M.
P01 Flow switch alarm delay at pump
start-up
20 0 150 s
P02 Flow alarm delay in normal
conditions
5 0 120 s
P03 Low pressure alarm delay at
compressor start-up
40 0 200 s
ON
OFF
ON
OFF
t
AL
FL
P01, P02
OFF
ON
CMP
Key
time
Par. Description
Def
Min
Max
U.M.
01
nti-freeze alarm set poin
3,0
A07
04 °C/°F
07
nti-freeze alarm threshold limi
-40
-40 176 °C/°F
02
nti-freeze alarm differential
5,0
0,3 122 °C/°F
03
nti-freeze alarm delay time
from switch-on
0
0 150 s
ON
OFF
t
A1
B2
A01+A02
A01
ON
OFF
t
A1
S3
A14+A02
A14
Key
B2 Evaporator output probe S3
EVD
4
driver evaporation probe
Par. Description
Def
Min
Max
U.M.
P16 High temperature
threshold alarm
28
-40 176 °C/°F
P16 Relative high temperature
threshold alarm
16
0 100 °C/°F
P17 High temperature on
switch-on alarm delay
30
0 250 min
ON
OFF
t
Ht
B1
P16
P16 — 2
P17
Unit
Power ON
Key
P16 High temperature alarm
threshold
H
High temperature alarm
B1 Temperature probe
Time
инструкцияCarel µC2 SE
High Efficiency Solutions
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
μC
2
SE
Электронное управление
Руководство пользователя
Посмотреть инструкция для Carel µC2 SE бесплатно. Руководство относится к категории без категории, 1 человек(а) дали ему среднюю оценку 9. Руководство доступно на следующих языках: русский. У вас есть вопрос о Carel µC2 SE или вам нужна помощь? Задайте свой вопрос здесь
Нужна помощь?
У вас есть вопрос о Carel а ответа нет в руководстве? Задайте свой вопрос здесь Дай исчерпывающее описание проблемы и четко задайте свой вопрос. Чем детальнее описание проблемы или вопроса, тем легче будет другим пользователям Carel предоставить вам исчерпывающий ответ.
Олег • 11-5-2023Нет комментариев
Здравствуйте. Не реагирует на установленные параметры С. Нет паузы между двумя последователями включениями компрессора.С1-10С2-60С-3-180С4-10С5-0С6-0С7-20С8-01С9-0
Количество вопросов: 1
Главная
Не можете найти ответ на свой вопрос в руководстве? Вы можете найти ответ на свой вопрос ниже, в разделе часто задаваемых вопросов о Carel µC2 SE.
Инструкция Carel µC2 SE доступно в русский?
Не нашли свой вопрос? Задайте свой вопрос здесь
26.02.2013
•
Views
Share
Embed
Flag
Carel uC2 SE.pdf
Carel uC2 SE.pdf
Carel uC2 SE.pdf
SHOW MORE
SHOW LESS
ePAPER READ
DOWNLOAD ePAPER
- TAGS
- compressor
- probe
- circuit
- digital
- integer
- defrost
- heating
- condenser
- cooling
- analog
- carel
- webmanuals.lennoxeurope.com
webmanuals.lennoxeurope.com
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
START NOW
-
More documents
-
Recommendations
-
Info
ENGLISH Key: 1 condenser fan overload 2 fan 3 condenser probe 4 compressor 1 5 high pressure 1 and 2 6 compressor overload 1 and 2 7 low pressure 1 and 2 8 compressor 2 9 compressor 3 10 compressor 4 11 reversing valve Key: 1 fl ow switch 2 water cond. temperature probe 3 condenser 4 compressor 1 5 high pressure 6 compressor overload 7 low pressure 8 compressor 2 22 3.9.2 Two circuits with one condenser fan circuit 3 3 4 5 6 7 8 1 2 11 11 1 1 1 5 2 2 6 7 2 2 1 3 Fig. 3.i.b 3.10 Water-cooled condensing unit without reverse cycle 3.10.1 Single circuit 4 5 6 7 1 8 Fig. 3.j.a 11 9 10 µC 2 <strong>SE</strong> — +030220426 — rel. 1.2 — 05.11.2007
3.10.2 Two circuits 2 2 1 3 3 4 5 1 1 6 7 1 5 6 7 µC 2 <strong>SE</strong> — +030220426 — rel. 1.2 — 05.11.2007 8 1 11 Fig. 3.j.b 3.11 Reverse-cycle water-cooled condensing unit 3.11.1 Single circuit 3 2 4 B7 5 6 7 8 Fig. 3.k.a 9 10 9 2 2 2 23 Key: 1 fl ow switch 2 water cond. temperature probe 3 condenser 4 compressor 1 5 high pressure 6 compressor overload 7 lw pressure 8 compressor 2 9 compressor 3 10 compressor 4 11 water pump Key: 1 condenser probe 2 condenser 3 antifreeze heater 4 compressor 1 5 high pressure 6 compressor overload 7 low pressure 8 compressor 2 9 reversing valve ENGLISH
- Page 1: µC 2 SE electronic control User ma
- Page 4 and 5: ENGLISH 4 µC 2 SE — +030220426 — r
- Page 6 and 7: ENGLISH 6 µC 2 SE — +030220426 — r
- Page 8 and 9: ENGLISH 8 1.2.3 Functions associate
- Page 10 and 11: ENGLISH Key: 1 condernser fan overl
- Page 12 and 13: ENGLISH Key: 1 condenser fan overlo
- Page 14 and 15: ENGLISH Key: 1 condenser fan overlo
- Page 16 and 17: ENGLISH Key: 1 water condensing tem
- Page 18 and 19: ENGLISH Key: 1 water condensing tem
- Page 20 and 21: ENGLISH Key: 1 external 2 internal
- Page 24 and 25: ENGLISH Key: 1 condenser probe 2 co
- Page 26 and 27: ENGLISH 26 4.3 Parameter tables The
- Page 28 and 29: ENGLISH 4.3.6 Defrost setting param
- Page 30 and 31: ENGLISH 30 4.3.9 Firmware parameter
- Page 32 and 33: ENGLISH 32 4.3.12 Timer setting par
- Page 34 and 35: ENGLISH — Signals from the expansio
- Page 36 and 37: ENGLISH CAREL NTC probe (mode H1= 2
- Page 38 and 39: ENGLISH 1 2 3 4 1 2 3 4 1 2 3 1 2 3
- Page 40 and 41: ENGLISH 1 2 Defrost by temperature
- Page 42 and 43: ENGLISH Key: 1. speed %; 2. condens
- Page 44 and 45: ENGLISH 44 — Fan management mode in
- Page 46 and 47: ENGLISH 46 H11= 12: associated devi
- Page 48 and 49: ENGLISH Part load in low pressure a
- Page 50 and 51: ENGLISH 50 — High temperature alarm
- Page 52 and 53: ENGLISH 1 50 40 30 20 10 r01 time r
- Page 54 and 55: ENGLISH Key: 1. chiller; 2. chiller
- Page 56 and 57: ENGLISH Duty cycle differential exa
- Page 58 and 59: ENGLISH 6. TABLE OF ALARMS 58 Key t
- Page 60 and 61: ENGLISH 60 Hc1 to Hc4: compressor o
- Page 62 and 63: ENGLISH 7. CONNECTIONS, ACCESSORIES
- Page 64 and 65: ENGLISH 2 1 GND Y — + LOAD LINE 3 2
- Page 66 and 67: ENGLISH Fig. 7.k Fig. 7.l Fig. 7.m
- Page 68 and 69: ENGLISH D A 8 e 12 A B E 4A 68 C Mo
- Page 70: ENGLISH 70 Functional characteristi
Delete template?
Are you sure you want to delete your template?
Save as template?
Title
Description
no error
products
- FREE
- adFREE
- WEBKiosk
- APPKiosk
- PROKiosk
Resources
- Blog
- API
- Help & Support
- Status
- tuxbrain.com
- ooomacros.org
- nubuntu.org
Company
- Contact us
- Careers
- Terms of service
- Privacy policy
- Cookie policy
- Cookie settings
- Imprint
Terms of service
Privacy policy
Cookie policy
Cookie settings
Imprint
Change language
Made with love in Switzerland
© 2023 Yumpu.com all rights reserved
Table of Contents for Carel µC2SE:
-
9 EV driver EV driver EV driver ESP. ENGLISH µC 2 SE — +030220426 — rel. 2.1 — 09.06.2010 Fig. 2.a Fig. 2.b Fig. 2.c 2. CONNECTIONS 2.1 General diagram 2.2 Network layout EVD*40*: driver for electronic expansion valve MCH200002*: I/O expansion board for µ 2 SE EVD*40*: driver for electronic expansion valve Optional board CONVONOFF*: PWM/digital converter CONV0/10A0*: PWM/analogic converter MCH2*T*: terminal PW/Modbus ® RTU CAREL Supervisory NTC: temperature probes MCH200485* RS485 seri
-
54 r01 r01 + r29 on off r01 r01 + r02 on off r03 — r04 r03 on off r03 — r30 r03 on off 1 2 3 5 5 5 5 4 r32-r33 hoot keep hoot start r32 ON OFF 1 2 ENGLISH µC 2 SE — +030220426 — rel. 2.1 — 09.06.2010 — Cooling set point in dehumidi cation r26: Alternative set point to r01 when the dehumidi cation function is active, as sent to the µC2SE by the terminal. The di erential remains the same as for chiller mode (r02). — Bu er tank suppression (low load) r27:
-
50 ENGLISH µC 2 SE — +030220426 — rel. 2.1 — 09.06.2010 — High temperature alarm delay on power-up P17: High temperature alarm delay when the control is switched on (power ON), from the remote ON/OFF contact or from the keypad. — High pressure alarm from transducer set point P18: Sets the value beyond which the high pressure alarm is generated. Each circuit will be managed by its own transducer. P18= 0: the function is disabled. For all other values greater than 3.0, due to the hysteres
-
59 ENGLISH µC 2 SE — +030220426 — rel. 2.1 — 09.06.2010 HP1: High pressure circuit 1 The alarm is detected irrespective of the status of the pump and the compressors. The compressors corresponding to circuit 1 are immediately stopped (ignoring the set protection times), the buzzer and alarm relay are activated, and the display starts ashing. The fans corresponding to the condenser in circuit 1 are activated at maximum speed for 60 s, so as to oppose the alarm situation, after
-
45 ENGLISH µC 2 SE — +030220426 — rel. 2.1 — 09.06.2010 — Number of evaporators H03: This establishes the number of evaporators present when there are 2 or 4 compressors, obviously with 2 circuits (including the expansion). With one evaporator (H03=0), the management of the heaters and the antifreeze function is performed only on B2. Vice-versa, with 2 evaporators (H03=1) antifreeze control will be performed using B2 and B6, w
-
73 ENGLISH µC 2 SE — +030220426 — rel. 2.1 — 09.06.2010
-
28 ENGLISH µC 2 SE — +030220426 — rel. 2.1 — 09.06.2010 4.3.6 Defrost setting parameters (d*) display indicat. parameter and description default level min. max. U.O.M. variat. default visibility supervis. variable Modbus variable type d01 Defrosting cycle/Condenser antifreeze 0= no; 1= yes, with shared defrosting U 0 1 Flag 1 0 — 7 (R/W) 7 Digital d02 Time-or temperature-based defrosting 0= time 1= temp. — press 2= pressure start, temperature end 3=
-
19 2 1 2 1 3 3 5 4 6 7 8 9 10 11 12 13 14 15 2 1 2 1 111 1 1 1 2 2 2 2 2 222 3 3 4 5 6 16 17 18 18 19 20 7 7 8 8 9 9 1 1 10 11 12 10 13 1314 1415 15 11 ENGLISH µC 2 SE — +030220426 — rel. 2.1 — 09.06.2010 Fig. 3.g.a Fig. 3.g.b 3.7 WATER/WATER heat pump with reversal on water circuit 3.7.1 Single circuit 3.7.2 Two circuits, H02= 1 and H21= 4 Key: 1 external 2 internal 3 reversing valve 4 ow switch 5 outle
-
57 ENGLISH µC 2 SE — +030220426 — rel. 2.1 — 09.06.2010 — RTC year t05: RTC year The alarms are only shown on the local display. The controller saves the signi cant events that stop (alarms) or limit (warnings) the operation of the unit. Up to 25 events can be saved, highlighting: — Event code; — Start hours; — Start minutes; — Start day; — Start month; — End hours; — End minutes; — End day; — End month. The log is accessed by pressing PRG+SEL for 5s and entering the password 44. The alarms saved are complete, as they
-
12 B2 2 2 1 3 3 5 1 6 7 7 9 1 1 10 11 12 14 11 1 1 4 1 2 5 2 6 8 13 2 2 10 11 12 222 15 15 17 16 2 1 3 4 5 5 1 1 2 2 6 6 7 7 8 9 13 1 1 2 2 10 11 12 222 10 11 12 14 11 1 15 15 16 17 3 ENGLISH µC 2 SE — +030220426 — rel. 2.1 — 09.06.2010 Fig. 3.b.b Fig. 3.b.c 3.2.2 Two circuits 3.2.3 Two circuits, 1 condenser fan circuit Key: 1 condenser fan overload 1 and 2 2 fan 3 condernser probe 4 supply probe 5 electrical heater 1 e 2 6 evaporator 1 and 2 7 supply fan overload 8 supply fan 9 compressor 1 10 high pressure 1 e 2 11 compressor
Questions, Opinions and Exploitation Impressions:
You can ask a question, express your opinion or share our experience of Carel µC2SE device using right now.