Частотник commander sk emerson коды ошибок

Struggling with troubleshooting and repair? Keep your equipment running smoothly by using the following guide to diagnose any trip codes. The following are some of the common errors you might encounter:

Emerson Commander SK Fault & Trip Codes by Control Techniques

Trip Code Condition Possible Cause
UU DC Bus under voltage Low AC Supply Voltage

Low DC Bus voltage when supplied by an external DC power supply

OU DC Bus over voltage Deceleration rate set too fast for the inertia of the machine

Mechanical load driving the motor

OI.AC** Drive output instantaneous over current Insufficient ramp times

Phase to phase or phase to ground short circuit on the drives output

Drive requires autotuning to the motor

Motor or motor connections changed, re-autotune drive to motor

OI.br** Braking Resistor instantaneous over current Excessive current in braking resistor

Braking resistor value to small

O.SPd Over Speed Excessive motor speed (typically caused by a mechanical load driving the motor
tunE Autotune stopped before completion Run command removed before autotune compelte
It.br I2t on Braking Resistor Excessive braking resistor energy
lt.AC l2t on drive output current Excessive Mechanical load

High impedance phase to phase or phase to ground short circuit at drive output

Drive requires re-autotuning to motor

O.ht1 IGBT over heat based on dries thermal model Over heat software thermal module
O.ht2 Over heat based on drives heatsink Heatsink temperature exceeds maximum allowable
th Motor thermistor trip Excessive motor temperature
O.Ld1* User +24v or digital output overload Excessive load or short circuit on +24v output
cL1 Analogue input 1 current mode, current loss Input current less than 3mA when 4-20 or 20-4mA modes selected
SCL Serial communication loss time-out Loss of communication when drive is under remote control
EEF Internal Drive EEPROM trip Possible loss of parameter values
PH Input phase imbalance or input phase loss One of the input phases has become disconnected from the drive (applies to 200/400v three phase drives only, not dual rated drives.
rS Failure to measure motors stator resistance Motor too small for drive

Motor cable disconnected during measurement

C.Err SmartStick data error Bad connection or memory corrupt within SmartStick
C.dAt SmartStick data does not exist New/empty SmartStick being read
C.Acc SmartStick read/write error fail Bad connection or faulty SmartStick
C.rtg SmartStick/drive rating change Already programmed SmartStick read by a drive of a different rating
O.cL Overload on current loop input Input current exceeds 25mA
HFxx trip Hardware faults Internal drive hardware fault

HF01 to HF03
Not used
HF04
Low DC bus at power up- may indicate an AC Input or pre-charge problem
HF05
No internal handshake signal from second processor (DSP) at start up
HF06
Unexpected interrupt
HF07
Watchdog failure
HF08
Interrupt crash (code overrun)
HF09 to HF10
Not used
HF11
Access to the EEPROM failed- tried to read stored parameter data but failed
HF12 to HF19
Not used
HF20
Power stage – code error Tried to read power board and read back erroneous
HF21
Power stage – unrecognized frame size
HF22
Overcurrent detection at power up- possible output short or bridge failure
HF23
DSP software overrun
HF24
Not Used
HF25
DSP Communications failure- communication from main to 2nd processor
HF26
Soft start relay failed to close; or soft start monitor failed; or braking
IGBT short circuit at power up
HF27
Power stage thermistor fault
HF28
Power circuit thermistor 2 or 3 fault Internal fan fault on size 3 only
HF29
Fan failure (current too high – only on drives with a fan) see note below
HF30
Not used
HF31
Internal Cap Bank Fan failure- check for fan rotation/blockage Size 4 and up
HF32
Power circuit temperature feedback multiplexer failure

Looking for more information about Control Techniques equipment? Read on here. 

Shopping for new or refurbished Control Techniques parts? Shop for the parts you’re looking for here, or find out more about how MRO Electric can help you repair your equipment

Joe Kaminski is an industrial automation specialist at MRO Electric. He has a background in industrial engineering and supply chain management. Joe has worked in the automation industry for over 10 years providing support to some of the largest companies in the world. For more info, visit www.mroelectric.com.

Частотные преобразователи Emerson, равно как и частотники других производителей, предназначены для изменения параметров тока под рабочую частоту промышленной техники. Их используют в управлении насосными станциями, системами водоснабжения, производственными линиями, вентиляторами и т. д. Плавную работу частотников обеспечивает микропроцессор и электронные модули (транзисторы или тиристоры).

Emerson — широко известный и очень надежный американский бренд, но даже такая электроника подвержена неисправностям. На это влияют многие факторы: нарушение норм эксплуатации, механические повреждения, нестабильное электропитание, естественный износ и т. д. Инженерная компания 555 специализируется на ремонте частотных преобразователей Emerson и готова справиться со сложной задачей в кратчайшие сроки.

Основные виды неисправностей и их причины

Наиболее распространенными являются следующие неполадки в работе частотных преобразователей тока:

  1. Перегрев электродвигателя. Вероятная причина — система охлаждения не справляется с оборотами, на которых работает двигатель. Возможно, что дело в неподходящих климатических условиях (слишком высокая температура в рабочем цехе) или в неисправности воздушных вентиляторов.
  2. Двигатель не вращается или вращается с неизменной скоростью. Причиной могут послужить некорректно настроенные параметры выходной или опорной частоты тока. Более точную информацию можно получить, если на дисплее преобразователя высветится код с ошибкой.
  3. Устройство не реагирует на команды с пульта управления. Наиболее вероятная причина — некорректно заданная частота тока.
  4. Низкий уровень напряжения на входе или выходе преобразователя. Тут необходимо откалибровать напряжение до допустимого уровня.

Причинами неполадок в работе частотника также зачастую становятся: нарушение правил монтажа, эрозия и масляные загрязнения, агрессивная внешняя среда, попадание внутрь влаги и пыли, неисправность клемм входа/выхода и др.

Высвечивающиеся на дисплее ошибки частотника Emerson позволяют быстро и точно диагностировать характер неполадок в его работе. Предлагаем вашему вниманию некоторые из типичных ошибок устройства:

Код Ошибки Диагностика неисправности
cL.A1 28 Потеря тока в одном из аналоговых входов. В этой ситуации следует проверить корректность подключения и отсутствие повреждений в электропроводке управления.
FAN.F 173 Не запускается внутренний вентилятор. Рекомендуется проверить правильность подключения вентилятора и отсутствие механических препятствий его вращению. Если по первым двум пунктам нарекания отсутствую, требуется замена вентилятора.
FI.In 237 Несовместимость пользовательской микропрограммы с микропрограммой силового блока. В такой ситуации следует перепрограммировать электропривод.
Oht.r 102 Перегрев выпрямителя. Рекомендованные действия: проверить изоляцию кабеля двигателя; усилить вентиляцию; снизить нагрузку на двигатель и т. д.
OI.SC 222 Короткое замыкание на выходе фазы. Рекомендуется проверить отсутствие замыкания в выходном кабеле и целостность изоляции электромотора.
Pb.HF 235 Отказ силовой платы. С такой проблемой следует обращаться в сервисный центр.
th.br 10 Перегрузка тормозного резистора. Рекомендованные действия: проверить проводку, сопротивление и изоляцию неисправного элемента.
thS 25 Замыкание термистора электромотора. Следует проверить целостность его цепи. При необходимости — заменить термистор или двигатель.
Oht.C 219 Перегрев платы в блоке управления. Рекомендуется оптимизировать вентиляцию с помощью настроек системы охлаждения.

Особенности ремонта частотников Emerson

Непреложное правило, которого необходимо придерживаться, — ремонт частотного преобразователя следует доверять профессионалам. Квалифицированные специалисты смогут провести комплексную диагностику устройства и выявить неисправные элементы в его механизме. Следующий этап работы — компонентный ремонт. Поврежденные узлы ремонтируются или заменяются новыми. Финальный шаг — проверка программных настроек. Ее следует выполнять в соответствии с инструкцией по эксплуатации, которую выпускает завод-изготовитель.

Преимущества ремонта частотных преобразователей в Инженерной компании 555

  1. Солидный опыт в ремонте частотников Emerson.
  2. Использование в работе только оригинальных комплектующих.
  3. Гарантия 12 месяцев.
  4. Экономия свыше 50 % средств по отношению к покупке нового оборудования.
  5. Доступные цены.
  6. Оперативное выполнение работы (в течение двух недель).

Обращайтесь в Инженерную компанию 555 прямо сейчас, чтобы как можно скорее получить отремонтированное оборудование.

Каталог

Показывать по элементов

Заявка на ремонт

Инженерная компания 555 осуществляет ремонт промышленной электроники EMERSON в Москве, Санкт-Петербурге, Челябинске и других регионах России. Чтобы узнать о ремонте в вашем регионе, позвоните по телефону +7 (800) 555-89-01 или оставьте заявку:

Звоните +7 (800) 555-89-01

Работать с нами просто, схема взаимодействия

1

Консультация по телефону

2

Отправка оборудования на осмотр

3

Оценка стоимости ремонта

4

Оплата счета

5

Ремонт и отправка оборудования

1Консультация по телефону

2Отправка оборудования на осмотр

3Оценка стоимости ремонта

4Оплата счета

5Ремонт и отправка оборудования

Преимущества сотрудничества с нами

Оплата только за результат — работающий блок

Гарантия на работоспособность блока целиком 12 месяцев

Срок ремонта от 5 до 15 дней

Бесплатный предварительный осмотр на предмет ремонтопригодности

Не вносим конструктивных изменений

Ремонт на компонентном уровне

Наша лаборатория расположена в Санкт-Петербурге, но обратиться за помощью вы можете из любой точки России.
Закажите обратный звонок или наберите в рабочее время многоканальный телефон

+7 (800) 555-89-01 (звонок по России бесплатный).

Расскажите о своей проблеме и получите инструкцию к дальнейшим действиям.

Компания ООО «Барс-Гидравлик Групп»

Компания ООО «Барс-Гидравлик Групп» на протяжении нескольких лет успешно сотрудничает с ООО «Инженерная компания 555» в вопросах ремонта сложного промышленного оборудования. За время работы наш партнер зарекомендовал себя с самой лучшей стороны. Заказы выполняются в кротчайшие сроки при соблюдении высокого качества работ. Организация приема и выдачи заказов четкая. Гарантийные обязательства выполняются в полном объеме.

Выражаем благодарность Вашим специалистам за профессионализм и оперативное решение поставленных задач.

Особенно хочется отметить высокую клиентоориентированность персонала Вашей компании, готовность помочь в самых сложных ситуациях.

Мы высоко ценим сложившиеся между нашими компаниями открытые и доверительные партнерские отношения и искренне желаем «Инженерной компании «555» долгих лет успеха и процветания.

Читать весь
отзыв

ООО «СоюзМашМеталл»

ООО «Инженерная компания «555» оказывала нашей компании услуги по ремонту электродвигателей и проявила пунктуальность, аккуратность и ответственность в работе.

Результат выполненных работ говорит о качественном оборудовании и высококвалифицированных кадрах.

Сотрудники компании готовы выполнить новые для себя виды работ и оказать консультационные услуги, что характеризует их как профессионалов своего дела.

Рекомендуем ООО «ИК «555» как ответственного и надежного поставщика услуг.

Читать весь
отзыв

ООО «РСК»

Сообщаем, что наша организация сотрудничает с ООО «Инженерная компания «555» с мая 2016 года по настоящее время.

За этот период мы обращались к услугам компании более 10 раз.

Благодаря серьезному и квалифицированному подходу сотрудников ООО «Инженерная компания «555» ремонтные работы произведены качественно с учетом сроков, и обеспечены гарантийным сопровождением.

Планируем в дальнейшем работать с ООО «Инженерная компания «555»

Читать весь
отзыв

ОАО «Октябрьский электровагоноремонтный завод»

Уважаемый Дмитрий Васильевич!

ОАО «Октябрьский электровагоноремонтный завод» успешно работает с ООО «Инженерная компания «555» несколько лет, очень довольны данным сотрудничеством. В работе компании наибольшую ценность для нас представляет готовность работать на условиях, удобных Заказчику, качественный ремонт оборудования в заявленные сроки и самое главное, финансовая защищенность Заказчика. В инженерной компании работают внимательные, доброжелательные сотрудники, готовые в любой момент решить проблему Заказчика. Мы рады, что выбрали ООО «Инженерная компания «555» в качестве партнера. Гарантируем дальнейшее сотрудничество!

Читать весь
отзыв

ЗАО «ОХТИНСКОЕ»

ЗАО «Охтинское» выражает глубокую признательность и истинную благодарность ООО Инженерной компании «555» за качественную работу компании по ремонту сложного оборудования промышленной электроники, оперативность и технически грамотное отношение к работе в течении всего периода сотрудничества.

Мы надеемся на дальнейшее успешное развитие деловых отношений в сфере ремонта промышленной электроники.

Читать весь
отзыв

Техническое обслуживание оборудования

Помимо ремонта, компания ik555 предлагает услугу по техническому обслуживанию оборудования нашими инженерами на вашем предприятии, либо в нашей лаборатории

  • Крупнейшая лаборатория в России по ремонту промышленной электроники на компонентном уровне
  • Международный сертификат стандарта IPC
  • Более 10 000 отремонтированных электронных блоков
  • Более 2 000 заказчиков от малого бизнеса до крупнейших корпораций

Подробнее

Как мы работаем

Understanding trip codes is an important part of keeping your equipment running smoothly.  Below are some of the more common codes you may come across:

Trip Code Condition Possible Cause
UU DC Bus under voltage Low AC Supply Voltage
Low DC Bus voltage when supplied by an external DC power supply
OU DC Bus over voltage Deceleration rate set too fast for the inertia of the machine
Mechanical load driving the motor
OI.AC** Drive output instantaneous over current Insufficient ramp times
Phase to phase or phase to ground short circuit on the drives output
Drive requires autotuning to the motor
Motor or motor connections changed, re-autotune drive to motor
OI.br** Braking Resistor instantaneous over current Excessive current in braking resistor
Braking resistor value to small
O.SPd Over Speed Excessive motor speed (typically caused by a mechanical load driving the motor
tunE Autotune stopped before completion Run command removed before autotune compelte
It.br I2t on Braking Resistor Excessive braking resistor energy
lt.AC l2t on drive output current Excessive Mechanical load
High impedance phase to phase or phase to ground short circuit at drive output
Drive requires re-autotuning to motor
O.ht1 IGBT over heat based on dries thermal model Over heat software thermal module
O.ht2 Over heat based on drives heatsink Heatsink temperature exceeds maximum allowable
th Motor thermistor trip Excessive motor temperature
O.Ld1* User +24v or digital output overload Excessive load or short circuit on +24v output
cL1 Analogue input 1 current mode, current loss Input current less than 3mA when 4-20 or 20-4mA modes selected
SCL Serial communication loss time-out Loss of communication when drive is under remote control
EEF Internal Drive EEPROM trip Possible loss of parameter values
PH Input phase imbalance or input phase loss One of the input phases has become disconnected from the drive (applies to 200/400v three phase drives only, not dual rated drives.
rS Failure to measure motors stator resistance Motor too small for drive
Motor cable disconnected during measurement
C.Err SmartStick data error Bad connection or memory corrupt within SmartStick
C.dAt SmartStick data does not exist New/empty SmartStick being read
C.Acc SmartStick read/write error fail Bad connection or faulty SmartStick
C.rtg SmartStick/drive rating change Already programmed SmartStick read by a drive of a different rating
O.cL Overload on current loop input Input current exceeds 25mA
HFxx trip Hardware faults Internal drive hardware fault

* The Enable/Reset terminal will not reset an O.Ld1  trip. Use the Stop/Reset key

**These trips cannot be reset for 10 seconds after they occur

If you have an AC / DC drive module breakdown or stability issue our engineers are able to analyse the whole machine to identify where the control issues lie. Our extensive experience in retrofit and new projects means we have the knowledge to look deep into the control system where we commonly find the peripheral devices are faulty rather than the drive module.

Our team of engineers are able to offer on site service and breakdown support throughout the UK to get you up and running again quickly.

Заказать продукцию Control Techniques

Главные приоритеты преобразователя частот Commander SK фирмы Control Techniques

Частотные преобразователи – достаточно распространенное и популярное промышленное оборудование. Их можно встретить практически на любом современном производстве. Спектр применения данной техники включает в себя множество отраслей хозяйственной деятельности. Преобразователи частот нужны в промышленности (тяжелой и легкой), в медицинской сфере и в транспортной отрасли. Электроприводы можно встретить в лифтовом, насосном и вентиляционном оборудовании. Их применяют механизаторы, фермеры и частные предприниматели. Поэтому проще назвать те области хозяйственной деятельности, где частотники не используются.

commander sk ошибки Control Techniques

Экономичный и многофункциональный Commander SK

На сегодня выбор преобразователей частот немаленький. Впору растеряться перед обилием современных агрегатов для преобразования параметров частот электротока. Лучше ориентироваться на проверенные фирмы, существующие десятилетиями такие, как Control Techniques. Британский бренд заслужил доверие потребителей, работая на рынке уже свыше 40 лет. Многие предприятия СНГ и всего мира оснастили свои производства преобразователями частоты Commander SK.

Этот электропривод – безотказный в работе, надежный и износоустойчивый. Сейчас частотники серии SK сняты с производства, но их можно купить у проверенного официального поставщика продукции Control Techniques.

Преобразователь частоты Commander SK имеет массу отличительных свойств, которые сделали его конкурентоспособным продуктом на рынке. Очень важно, что у commander sk ошибки практически исключены. Поэтому многие потребители стремятся приобрести именно данный аппарат, а не его аналоги, несмотря на прекращение выпуска продуктов серии SK.

Назовем основные приоритеты покупки частотников Commander SK. Это:

  • — низкий уровень потребления энергии промышленным оборудованием, если к нему подключен преобразователь частот;
  • — повышается стойкость к износу агрегатов на предприятии;
  • — обеспечивается хорошая защита от перепадов напряжения в сети, перегрузки линии;
  • — оборудование при наличии частотника имеет большую продуктивность, его коэффициент полезного действия значительно повышается.

Уже доказано, что применение частотного преобразователя не только защищает оборудование от износа, что уже само по себе является хорошей экономией средств. Но с его помощью можно также примерно в два раза меньше затрачивать энергии  на технологические процессы, включая операции большой сложности. Все это существенно повышает рентабельность предприятий, учитывая то, что первоначальные затраты на покупку электроприводов не являются особенно высокими. А если еще и добавить к этому, что вам не придется искать в сети commander sk коды ошибок, то ценность таких частотников становится очевидной.

Где купить электропривод серии Commander SK

Преобразователь частоты Commander SK вы всегда можете заказать на сайте официального поставщика. Компания ОЛНИСА – ведущая мультибрендовая фирма, работающая напрямую с мировыми брендами, производителями промышленной электроники. Поставки производятся напрямую из стран ЕС, Америки и Азии. Если вам требуется приобрести снятый с производства Commander SK или другую продукцию Control Techniques, менеджеры компании ОЛНИСА всегда готовы помочь. Делая заказ на сайте поставщика, вы гарантировано получаете:

commander sk ошибки Control Techniques

  • — оперативную доставку по России и СНГ сроком от 1-го дня, есть также и доставка прямо к порогу клиента;
  • — гарантия на все оборудование;
  • — низкие цены без завышения.

Сотрудничая с компанией ОЛНИСА, Вы получаете гарантированно качественный товар, т.к. вся продукция дополнительно проверяется перед отправкой.

Struggling with troubleshooting and repair? Keep your equipment running smoothly by using the following guide to diagnose any trip codes. The following are some of the common errors you might encounter:

Emerson Commander SK Fault & Trip Codes by Control Techniques

Trip Code Condition Possible Cause
UU DC Bus under voltage Low AC Supply Voltage

Low DC Bus voltage when supplied by an external DC power supply

OU DC Bus over voltage Deceleration rate set too fast for the inertia of the machine

Mechanical load driving the motor

OI.AC** Drive output instantaneous over current Insufficient ramp times

Phase to phase or phase to ground short circuit on the drives output

Drive requires autotuning to the motor

Motor or motor connections changed, re-autotune drive to motor

OI.br** Braking Resistor instantaneous over current Excessive current in braking resistor

Braking resistor value to small

O.SPd Over Speed Excessive motor speed (typically caused by a mechanical load driving the motor
tunE Autotune stopped before completion Run command removed before autotune compelte
It.br I2t on Braking Resistor Excessive braking resistor energy
lt.AC l2t on drive output current Excessive Mechanical load

High impedance phase to phase or phase to ground short circuit at drive output

Drive requires re-autotuning to motor

O.ht1 IGBT over heat based on dries thermal model Over heat software thermal module
O.ht2 Over heat based on drives heatsink Heatsink temperature exceeds maximum allowable
th Motor thermistor trip Excessive motor temperature
O.Ld1* User +24v or digital output overload Excessive load or short circuit on +24v output
cL1 Analogue input 1 current mode, current loss Input current less than 3mA when 4-20 or 20-4mA modes selected
SCL Serial communication loss time-out Loss of communication when drive is under remote control
EEF Internal Drive EEPROM trip Possible loss of parameter values
PH Input phase imbalance or input phase loss One of the input phases has become disconnected from the drive (applies to 200/400v three phase drives only, not dual rated drives.
rS Failure to measure motors stator resistance Motor too small for drive

Motor cable disconnected during measurement

C.Err SmartStick data error Bad connection or memory corrupt within SmartStick
C.dAt SmartStick data does not exist New/empty SmartStick being read
C.Acc SmartStick read/write error fail Bad connection or faulty SmartStick
C.rtg SmartStick/drive rating change Already programmed SmartStick read by a drive of a different rating
O.cL Overload on current loop input Input current exceeds 25mA
HFxx trip Hardware faults Internal drive hardware fault

HF01 to HF03
Not used
HF04
Low DC bus at power up- may indicate an AC Input or pre-charge problem
HF05
No internal handshake signal from second processor (DSP) at start up
HF06
Unexpected interrupt
HF07
Watchdog failure
HF08
Interrupt crash (code overrun)
HF09 to HF10
Not used
HF11
Access to the EEPROM failed- tried to read stored parameter data but failed
HF12 to HF19
Not used
HF20
Power stage – code error Tried to read power board and read back erroneous
HF21
Power stage – unrecognized frame size
HF22
Overcurrent detection at power up- possible output short or bridge failure
HF23
DSP software overrun
HF24
Not Used
HF25
DSP Communications failure- communication from main to 2nd processor
HF26
Soft start relay failed to close; or soft start monitor failed; or braking
IGBT short circuit at power up
HF27
Power stage thermistor fault
HF28
Power circuit thermistor 2 or 3 fault Internal fan fault on size 3 only
HF29
Fan failure (current too high – only on drives with a fan) see note below
HF30
Not used
HF31
Internal Cap Bank Fan failure- check for fan rotation/blockage Size 4 and up
HF32
Power circuit temperature feedback multiplexer failure

Looking for more information about Control Techniques equipment? Read on here. 

Shopping for new or refurbished Control Techniques parts? Shop for the parts you’re looking for here, or find out more about how MRO Electric can help you repair your equipment

Joe Kaminski is an industrial automation specialist at MRO Electric. He has a background in industrial engineering and supply chain management. Joe has worked in the automation industry for over 10 years providing support to some of the largest companies in the world. For more info, visit www.mroelectric.com.

emerson commander sk error codes

There are various Error codes that you may encounter while using your Emerson Commander SK. If you are experiencing any of them, you should know how to troubleshoot them and solve them. In this article, you will learn about these codes and how to fix them.

Troubleshooting

Troubleshooting Emerson Commander SK errors is a process of troubleshooting your SK’s performance. The error codes are typically caused by several different problems. For example, your SK might not be running as efficiently as it should, or it may be overheating. In this case, you should perform a power cycle, allowing the drive to discharge completely. During this process, the SK’s temperature may be monitored and recorded.

Заказать продукцию Control Techniques

Главные приоритеты преобразователя частот Commander SK фирмы Control Techniques

Частотные преобразователи – достаточно распространенное и популярное промышленное оборудование. Их можно встретить практически на любом современном производстве. Спектр применения данной техники включает в себя множество отраслей хозяйственной деятельности. Преобразователи частот нужны в промышленности (тяжелой и легкой), в медицинской сфере и в транспортной отрасли. Электроприводы можно встретить в лифтовом, насосном и вентиляционном оборудовании. Их применяют механизаторы, фермеры и частные предприниматели. Поэтому проще назвать те области хозяйственной деятельности, где частотники не используются.

commander sk ошибки Control Techniques

Экономичный и многофункциональный Commander SK

На сегодня выбор преобразователей частот немаленький. Впору растеряться перед обилием современных агрегатов для преобразования параметров частот электротока. Лучше ориентироваться на проверенные фирмы, существующие десятилетиями такие, как Control Techniques. Британский бренд заслужил доверие потребителей, работая на рынке уже свыше 40 лет. Многие предприятия СНГ и всего мира оснастили свои производства преобразователями частоты Commander SK.

Этот электропривод – безотказный в работе, надежный и износоустойчивый. Сейчас частотники серии SK сняты с производства, но их можно купить у проверенного официального поставщика продукции Control Techniques.

Преобразователь частоты Commander SK имеет массу отличительных свойств, которые сделали его конкурентоспособным продуктом на рынке. Очень важно, что у commander sk ошибки практически исключены. Поэтому многие потребители стремятся приобрести именно данный аппарат, а не его аналоги, несмотря на прекращение выпуска продуктов серии SK.

Назовем основные приоритеты покупки частотников Commander SK. Это:

  • — низкий уровень потребления энергии промышленным оборудованием, если к нему подключен преобразователь частот;
  • — повышается стойкость к износу агрегатов на предприятии;
  • — обеспечивается хорошая защита от перепадов напряжения в сети, перегрузки линии;
  • — оборудование при наличии частотника имеет большую продуктивность, его коэффициент полезного действия значительно повышается.

Уже доказано, что применение частотного преобразователя не только защищает оборудование от износа, что уже само по себе является хорошей экономией средств. Но с его помощью можно также примерно в два раза меньше затрачивать энергии  на технологические процессы, включая операции большой сложности. Все это существенно повышает рентабельность предприятий, учитывая то, что первоначальные затраты на покупку электроприводов не являются особенно высокими. А если еще и добавить к этому, что вам не придется искать в сети commander sk коды ошибок, то ценность таких частотников становится очевидной.

Где купить электропривод серии Commander SK

Преобразователь частоты Commander SK вы всегда можете заказать на сайте официального поставщика. Компания ОЛНИСА – ведущая мультибрендовая фирма, работающая напрямую с мировыми брендами, производителями промышленной электроники. Поставки производятся напрямую из стран ЕС, Америки и Азии. Если вам требуется приобрести снятый с производства Commander SK или другую продукцию Control Techniques, менеджеры компании ОЛНИСА всегда готовы помочь. Делая заказ на сайте поставщика, вы гарантировано получаете:

commander sk ошибки Control Techniques

  • — оперативную доставку по России и СНГ сроком от 1-го дня, есть также и доставка прямо к порогу клиента;
  • — гарантия на все оборудование;
  • — низкие цены без завышения.

Сотрудничая с компанией ОЛНИСА, Вы получаете гарантированно качественный товар, т.к. вся продукция дополнительно проверяется перед отправкой.

Понравилась статья? Поделить с друзьями:
  • Частотник kinco коды ошибок
  • Частотник baumuller коды ошибок
  • Частотник schneider electric altivar 212 ошибки
  • Частотник j1000 ошибки
  • Частотник atv312 ошибка scf