HLP-A100 Series

Chapter 10 Warnings/Alarms and Fault Handling

The HLP-A100 drive has three different fault types: Warning, alarm and

error. When a fault happens, the drive shows a specific code to indicate it.

When a warning happens, it means that the drive is close to its design

limits for some reason, but the drive still works. If the drive fault disappear,

the warning will also disappear.

An alarm means that the drive has exceeded its design limits for some

reason. When this happens, the drive will trip. Af ter an alarm the driver must

be reset in order to re-run. When some alarms happen, the drive will lock itself.

These alarms are called trip-lock alarm. The Trip-lock alarm offers additional

protection, the default setting is that the main power should be cut off before

resetting the alarm. But by setting parameters C14.23 = 0, the trip-lock alarm

can be reset without cutting the main power off. But there is a risk of accident

when choosing this f unction. Before using this f unction, it is important to be

familiar with the drive and the whole system in order to be safe when dealing

with the drive.

Error means the drive is in a state and unable to carry out an operation.

Warning

Alarm

A.03

E.03

A.04

E.04*

A.07

E.07

A.08

E.08

A.09

E.09

A. 1 0

E. 1 0

164

Error Fault Description

Motor Loss

Mains Phase Loss

Over Voltage

Under Voltage

Inverter

Overload

Motor ETR Over

Temperature

HLP-A100 Series Operating Manual

Reason analysis

Motor cable connection

problems

Missing phase on supply

side or too high voltage

imbalance. The allowed

power imbalance of

HLP-C100 serials inverter

is 3% of the rated voltage.

(IEC Standard)

Intermediate circuit voltage

exceeds limit.

Intermediate circuit voltage

drops below «voltage

warning low» limit.

More than 100% overload

for too long time.

Motor temperature

calculated by ETR exceeds

upper limit

  • Contents

  • Table of Contents

  • Troubleshooting

  • Bookmarks

Quick Links

loading

Related Manuals for Holip HLP-A100 Series

Summary of Contents for Holip HLP-A100 Series

  • Page 2
    HLP-A100 Series Operating Manual…
  • Page 4: Table Of Contents

    Chapter 6 Parameter Description 6.1 Parameter Group 00: Operation/Display 6.2 Parameter Group 01: Load and Motor 6.3 Parameter Group 02: Brakes 6.4 Parameter Group 03: Reference/Ramps 6.5 Parameter Group 04: Limits/warnings 6.6 Parameter Group 05: Digital Input/Output HLP-A100 Series Operating Manual…

  • Page 5: Table Of Contents

    10.2 Fault Indication and Trouble Shooting Chapter 11 Maintenance 11.1 Note 11.2 Storage and Transport Chapter 12 Communication protocol 12.1 Format specification 12.2 Coil addressing 12.3 Read Coil Status 12.4 Read Holding Registers 12.5 Force Single Coil HLP-A100 Series Operating Manual…

  • Page 6: Table Of Contents

    HLP-A100 Series 12.6 Preset Single Register 12.7 Force Multiple Coils 12.8 Preset Multiple Regs 12.9 Read/Write array 12.10 Exception code HLP-A100 Series Operating Manual…

  • Page 7
    HLP-A100 Series HLP-A100 Series Operating Manual…
  • Page 8: Introduction

    Introduction Thank you f or purchasing and using the general-pur pose vector inverter of HLP-A100 series. Please read caref ully the operation manual before putting the inverter to use so as to correctly install and operate the inverter, give f ull play to its f unctions and ensure the safety.

  • Page 9
    ● Don’t install the drive in a space with explosive gas, otherwise, they lead to explosion. ● R, S, T terminals are power input terminals, never mixed with U.V.W terminals. Be sure that the wiring of the main circuit is HLP-A100 Series Operating Manual…
  • Page 10: During The Power-Up

    Danger ● Never connect or disconnect the motor set while the inverter is in running. Otherwise it will cause over-current trip and even burn up the main circuit of the inverter. HLP-A100 Series Operating Manual…

  • Page 11: After The Power-Off

    The user must strictly follow the instruction to operate and make wire connection. Otherwise HOLIP will not responsible for the damages due to wrong operation. The user will responsible for the damages themselves.

  • Page 12: Chapter 2 Standards And Specifications

    Control panel with LED display and potentiometer With coating on PCB Reserved Domestic sale Overseas sale 25-27 Reserved 28-3 1 VXXX Indicate sof tware version number, such as V235 means the version number is 2.35 . HLP-A100 Series Operating Manual…

  • Page 13: Particular Specifications

    3×380-440V50/60Hz HLP-A100003743 25.4 3×440-480V50/60Hz 3×380-440V50/60Hz HLP-A100004543 3×440-480V50/60Hz 3×380-440V50/60Hz HLP-A100005543 3×440-480V50/60Hz 3×380-440V50/60Hz HLP-A100007543 3×440-480V50/60Hz 3×380-440V50/60Hz HLP-A100009043 3×440-480V50/60Hz 3×380-440V50/60Hz HLP-A10001 1043 3×440-480V50/60Hz 3×380-440V50/60Hz HLP-A100013243 3×440-480V50/60Hz 3×380-440V50/60Hz HLP-A100016043 3×440-480V50/60Hz 3×380-440V50/60Hz HLP-A10001 8543 3×440-480V50/60Hz 3×380-440V50/60Hz HLP-A100020043 3×440-480V50/60Hz 3×380-440V50/60Hz HLP-A100022043 3×440-480V50/60Hz HLP-A100 Series Operating Manual…

  • Page 14: Technical Specifications

    Wobble Function; Cascade cont roller; Winder; Jogging Application ; Multi-speed Cont rol via Digital input; Multi-speed Functions Control via Ref erence; SLC ( including Order Control 、 Parallel Control ) ; Mechanical Braking;UP/DOW N;Catch up /Slow down; Relative Scaling Reference etc. HLP-A100 Series Operating Manual…

  • Page 15
    Pulse accuracy input Resolution 1 1bit; Scanning 16ms; time Output 2 digital outputs ( DO1 、 DO2 ) number Digital Relay 2 relay outputs ( KA-KB 、 FA-FB- output output FC ) ; Scanning 1ms; time HLP-A100 Series Operating Manual…
  • Page 16
    , analogue output, 1-10 f ault records and accumulated working time etc.; Remote mounting Available when the control panel for external use; Accessory Copy parameters f rom one inverter Copy card to another ; HLP-A100 Series Operating Manual…
  • Page 17
    1000m the ambient temperature or the maximum output current should be decreased. Dcrease the output by 1% per 100m altitude above 1000m or reduce the max. ambient temperature by 1 degree per 200m. HLP-A100 Series Operating Manual…
  • Page 18: Chapter 3 Installation And Wiring

    ● Check if the inverter has got any damage or deformation during the transportation and handling; ● Check if there is one piece of HLP-A100 series inverter and one copy of the instruction manual available when unpacking it; ● Check the information on the label to see if the specifications meet your order (Operating voltage and KW value);…

  • Page 19: Dimensions Of The Inverter

    HLP-A100 Series 3.2.2 Dimensions of the inverter Item Model Frame size and Installation Dimension HLP-A100001 143 HLP-A100001543 HLP-A1001 8D543 HLP-A100002243 HLP-A100003043 HLP-A100003743 HLP-A100004543 HLP-A100005543 HLP-A100007543 HLP-A100009043 HLP-A10001 1043 HLP-A100013243 HLP-A100016043 HLP-A10001 8543 HLP-A100020043 HLP-A100 Series Operating Manual…

  • Page 20: Installation And Wiring

    480V Brake terminals 1 1-22 0. 1 5-0.4 30-75 0. 1 5-0.4 90-220 0. 1 5-0.4 3.3.2 Fuse and Main Circuit Terminals Specifications Model Fuse(Rated current/A) Main Circuit Terminals HLP-A100001 143 HLP-A100001543 HLP-A1001 8D543 HLP-A100002243 HLP-A100003043 HLP-A100 Series Operating Manual…

  • Page 21: Installation And Direction

    3.3.3 Installation and Direction Single Installation Side by Side Installation T he i nver ter must be i nst alled HLP-A100 series inver ter can be vertically with smooth ventilation. mounted side by side, a minimum Enough space must be lef t around…

  • Page 22: Wiring Terminal

    Note: Install the unit and make sure that it is f ree f rom high moisture 、 high temperature 、 heavy dust 、 metal f ragments and high oil mist. 3.3.4 Wiring terminal 3.3.4.1 Main Circuit Terminals Terminals of the main circuit: 11-22kW: -UDC +UDC/ 30-220KW: -UDC +UDC HLP-A100 Series Operating Manual…

  • Page 23
    Connect the brake resistor, make sure to set C02. 1 0 、 -BR 、 +BR C02. 1 1 etc. +UDC 、 -UDC DC bus Ground terminal 3.3.4.2 I/O Control Terminals 30-75kW Control and Relay Terminals: +10V 11-22kW & 90-220kW Control and Relay Terminals: +10V HLP-A100 Series Operating Manual…
  • Page 24
    Analog 、 Isolated f rom internal digital communication communication ground(COM) (GND) ground 1 、 Pulse input: 0.001-100.000KHz; Pulse setting/ Pulse input DI4 2 、 Voltage range: 24V ± 20%; Feedback 3 、 Input duty ratio: 40%-60%; HLP-A100 Series Operating Manual…
  • Page 25
    1 、 Pulse output range: 0.001-5.000KHz Pulse output (range f rom 0.001-100.000KHz is optional); Pulse output 2 、 Voltage range: 0-24V; 3 、 Duty ratio: 40%-60%; 4 、 Resistive load >1kΩ, capacitive load < 10nF; HLP-A100 Series Operating Manual…
  • Page 26: Wiring

    0. 1 A(cosφ= 0.4); RS485 comm- RS+ 、 RS- Max baud rate: 1 15200bit/s; unication 3.3.5 Wiring Basic Connection Diagram of HLP-A100 series inverter: M OtOR p Ow e R R f I IN p u t R f I…

  • Page 27
    PE line, its cross sectional area and the main power cable should be the same, must be separate grounded. ● Make sure reliable ground of the inverter in accordance with IEC 61800-5-1. ● Please refer to 9.2 for the use of RFI SWITCH. HLP-A100 Series Operating Manual…
  • Page 28: Chapter 4 Operation And Display Interface

    C00.04 basic C00.03 Turn clockwise to select C03.00 parameter group C03 Press key to shif t to f ractional C03.00 part Turn clockwise to select C03. 1 0 parameter C03. 1 0 HLP-A100 Series Operating Manual…

  • Page 29: Fwd/Rev Status

    20.5 4.2.2 FWD/REV Status Confirm the direction of the motor according to the set value, as shown in the following table: Reference Running status Indicator Display ≥0 STOP < 0 STOP ≥0 HLP-A100 Series Operating Manual…

  • Page 30: Data Read-Outs

    (C16. 1 3) Frequency interface is 50.0Hz, display accuracy : 0. 1 Show the preset reference (C16.01) is Reference (%) 50%, display accuracy: 0.001 Show the motor current (C16. 1 4) is Motor Current 9.00A, display accuracy: 0.01 HLP-A100 Series Operating Manual…

  • Page 31
    Show value of counter Counter A A is (C16.72) 65535, display accuracy : 1 Show counter B(C16.72) Counter B is 65535, diaplay accuracy : 1 Show analog in VI Analog in VI (C16.62) is 10.00V, display accuracy: 0.01 HLP-A100 Series Operating Manual…
  • Page 32: View Alarm Record

    Key-press LCP Display Action Description Press key to display the first C00.04 basic C00.03. Turn clockwise to select par. C15.00 group No. C15. Press to select parameter C15.00 number. Turn clockwise to select C15.30 C15.30 HLP-A100 Series Operating Manual…

  • Page 33: View State Parameter

    Press to display the first basic C00.03 parameter C00.03. Turn clockwise to select Par. C16.00 group No. C16 C16.00 Press to select parameter No. C16.01 Press select C16.01 Turn clockwise to finish browse value of C16.01. HLP-A100 Series Operating Manual…

  • Page 34: Led Display

    LCP Display Action Description C16.60 Press to select C16.60. Press to view the value in 0000 C16.60, 0100 indicates status of FOR 、 DI1 、 DI2 is 0, and status of REV is 1. 4.2.6 LED Display HLP-A100 Series Operating Manual…

  • Page 35: Chapter 5 Parameter Overview

    ; 2: Copy *C00.51 Set-up Copy f rom set-up2; 9: Copy f rom factory set-up; Menu 0: Disabled; C00.60 Password 1 : Enabled; 0: Speed open loop; Configuration C01.00 3: Process closed loop; Mode 4: Torque Open loop; HLP-A100 Series Operating Manual…

  • Page 36
    (AMA) AMA; Stator *C01.30 Resistance Dep.on motor data Ω (Rs) Stator Leakage *C01.33 Dep.on motor data Ω Reactance (XI) Main *C01.35 Reactance Dep.on motor data Ω (Xh) *C01.39 Motor poles 2~100 Motor Cable *C01.42 0~150 Length HLP-A100 Series Operating Manual…
  • Page 37
    0.005~0.050 0.005 Time Constant C01.71 Start Delay 0.0~10.0 0: DC hold/delay C01.72 Start Function time; 2: Coast/Delay time; 0: Disabled; *C01.73 Flying start 1 : Enabled; Function at C01.80 0: Coast; 1 : DC Hold; Stop HLP-A100 Series Operating Manual…
  • Page 38
    Max current Over-voltage 0: Disabled; C02. 1 7 Control 2: Enabled; Release Brake C02.20 0.00~100.00 0.00 Current Activate C02.22 Brake Speed 0.0~400.0 [Hz] Reference 0: Min-Max; 1 : -Max- C03.00 Range +Max; Minimum C03.02 -4999.000~4999.000 0.000 Reference HLP-A100 Series Operating Manual…
  • Page 39
    1 : Stopsave; 2: Power Value down save; 0: Linear; 2: Sine2 C03.40 Ramp 1 Type ramp; Ramp 1 Ramp C03.41 0.05~3600.00 up Time Ramp 1 Ramp C03.42 0.05~3600.00 Down Time 0: Linear; 2: Sine2 C03.50 Ramp 2 Type ramp; HLP-A100 Series Operating Manual…
  • Page 40
    *C04. 1 2 Low Limit 0.0~400.0 [Hz] Motor Speed *C04. 1 4 High Limit 0.0~400.0 65.0 [Hz] C04. 1 8 Current Limit 0~300 Max. Output *C04. 1 9 0.0~400.0 65.0 Frenquency Max Output C04.21 Frequency 0~21 Resource HLP-A100 Series Operating Manual…
  • Page 41
    50.000 High Warning C04.56 -4999.000~4999.000 0.000 Feedback Low Warning C04.57 Feedback -4999.000~4999.000 50.000 High Missing *C04.58 Motor Phase 0: Off; 1 : On; Function Bypass Speed C04.61 0.0~400.0 From [Hz] Bypass Speed C04.63 0.0~400.0 To [HZ] HLP-A100 Series Operating Manual…
  • Page 42
    62: Reset counterA; 63: CounterB (up); 65: Reset counterB; Terminal DI3 70: Wobble start C05. 1 4 Digital Input command; 71 : Wobble reset; 72: Wobble initialization; 90: Low water level; 91 : High water level; HLP-A100 Series Operating Manual…
  • Page 43
    23: Remote ready, no Terminal thermal warning;24: C05.3 1 DO2 Digital Ready, voltage ok; 25: Output Reverse; 26: Bus ok; 28: Brake, no brake warning; 29: Brake ready, no fault; 30: Brake fault (IGBT); 32: Mech brake control; HLP-A100 Series Operating Manual…
  • Page 44
    100: Start pump1 ; 101 : Start pump2; 102: Below water level, low; 103: Above water level, high; 104: Low water warning; 105: High water warning; 106: Low voltage warning; 107: Over voltage warning; 108: sleep; HLP-A100 Series Operating Manual…
  • Page 45
    AI input; Pulse Output C05.61 0.020~49.999 0.020 Min Freq Pulse Output C05.62 0.021~50.000 KHz 50.000 Max Freq Pulse Output C05.63 0.00~200.00 0.00 Min Scale Pulse Output C05.64 0.00~200.00 100.00 Max Scale Live Zero C06.00 1~99 Timeout Time HLP-A100 Series Operating Manual…
  • Page 46
    0.07 Low Voltage Terminal AI C06.21 0.01~10.00 10.00 High voltage Terminal AI C06.22 0.00~19.99 0. 1 4 Low Current Terminal AI C06.23 0.01~20.00 20.00 High Current Terminal AI C06.24 Low Ref./ -4999.000~4999.000 0.000 Feedb. V alue HLP-A100 Series Operating Manual…
  • Page 47
    Output Max 0.00~200.00 100.00 Scale LCP Potmeter C06.81 -4999.000~4999.000 0.000 Low Ref. LCP Potmeter C06.82 -4999.000~4999.000 50.000 High Ref. Terminal AO 0: 0~20mA; C06.90 Mode 1 : 4~20mA; Terminal C06.91 AO Analog See also C06.71 . output HLP-A100 Series Operating Manual…
  • Page 48
    0.0~10.00 0.01 Gain Process PI C07.34 0. 1 0~9999.00 9999.00 Integral time Process PI C07.38 Feed Forward 0~400 Factor On Reference C07.39 0~200 Bandwidth Process PI C07.41 -100-100 Output Low Process PI C07.42 -100-100 Output High HLP-A100 Series Operating Manual…
  • Page 49
    0: Even Parity, 1 Stop bit; 1 : Odd Parity, 1 stop C08.33 FC Port Parity bit; 2: No Parity, 1 Stop bit; 3: No Parity,2 Stop bits; Minimum C08.35 Response 0.001~0.500 0.010 Delay Max. C08.36 Response 0.010~10.000 5.000 Delay HLP-A100 Series Operating Manual…
  • Page 50
    1 : Reset Sample PLC; Comparator C13. 1 0 0~3 1 1 13 Operand Comparator C13. 1 1 1 13 Operator Comparator C13. 1 2 -9999.0~9999.0 1 14 Value SL Controller C13.20 0.0~3600 1 14 Timer HLP-A100 Series Operating Manual…
  • Page 51
    15; 1 19 12: Automatic reset x 13: Infinite auto reset; Automatic C14.21 0~600 1 19 Restart Time 0: Normal Operation; 2: Initialisation; Operation C14.22 3: Backup user 1 19 Mode settings;4: Recover user settings; HLP-A100 Series Operating Manual…
  • Page 52
    C14.52 Fan Control low temperature; 5-8: Reserved; 0: Off; 1 : Sine-Wave *C14.55 Output Filter Filter; 3: Sine-Wave Filter with feedback; 2~6: 2kHz~6kHz; Min Switch *C14.63 7: 8kHz; 8: 10 kHz; Frequency 9: 12kHz; 10: 16kHz; HLP-A100 Series Operating Manual…
  • Page 53
    NO. View power card Power Card C15.47 ordering No. of the Ordering NO. drive C15.48 LCP ID NO. View LCP ID NO. Sof tware ID View sof tware ID C15.49 Control Card control card HLP-A100 Series Operating Manual…
  • Page 54
    C16. 1 4 0.00~655.35 Current Frequency C16. 1 5 0.0~200.0 Motor C16. 1 8 0~100 Thermal DC Link C16.30 0~65535 Voltage Heat sink C16.34 0~255 ¡ æ Temp. Inverter C16.35 0~255 Thermal Inv. Nom. C16.36 0.00~655.35 Current HLP-A100 Series Operating Manual…
  • Page 55
    Pulse Output C16.69 0.020~50.000 13 1 Relay Output C16.71 0~65535 13 1 [bin] C16.72 Counter A 0~2147483647 13 1 C16.73 Counter B 0~2147483647 13 1 Analog C16.78 0.00~20.00 13 1 Output AO C16.86 FC Port REF -32768~32767 HLP-A100 Series Operating Manual…
  • Page 56
    Cascade High C25.25 0.000~400.000 50.000 Frequency High C25.26 Frequency 0.0~3600.0 20.0 Delay Time Low Pressure C25.30 Warning 0.000~99.999 3.000 Level Low Pressure C25.3 1 Warning 0.0~3600.0 10.0 Delay Time Recovery C25.32 Low Pressure 0.000~99.999 4.000 Level HLP-A100 Series Operating Manual…
  • Page 57
    0~150.0 Level Sleep Pressure C25.52 0.0~300.0 20.0 Delay Time Sleep C25.53 0.0~400.0 20.0 Frequency Sleep C25.54 Frequency 0.0~300.0 20.0 Delay Time C25.57 Awake Level 0.0~150.0 Pump Type 0: Feed pump; C25.60 Selection 1 : Drain pump; HLP-A100 Series Operating Manual…
  • Page 58
    1 ¡ ¢ 2 running; Wobble Start C30.00 0: Auto; 1 : Manual; Mode Dwell C30.01 0.000~200.000 0.000 Frequency C30.02 Dwell Time 0.0~3600.0 Centre C30. 1 0 Frequency 0.000~30.000 0.500 Rate Centre C30. 1 1 Frequency 0.000~200.000 10.000 Low Limit HLP-A100 Series Operating Manual…
  • Page 59
    0.01~600.00 1.00 Meter Setting C30.32 0.000~60.000 Km 10.000 Length Length Reach C30.33 0: No action; 1 : Stop; Mode 0: Operate at centre Wobble C30.38 f requency; 1 : Operate Restore Mode at preset f requency; HLP-A100 Series Operating Manual…
  • Page 60
    Note: Reference signed with “*”in parameter No. column means this parameter can’t be modified when the motor is running. In factory setting column, “*” means the default setting for this parameter is determined by the drive type. HLP-A100 Series Operating Manual…
  • Page 61: Chapter 6 Parameter Description

    Local reference is set to 0. Thus motor will not start running before local reference has been increased. Attention: If LCP with potentiometer is mounted, reference is set according to actual potentiometer value. HLP-A100 Series Operating Manual…

  • Page 62
    Description of choice: HLP-B series inverter contains 2 set-ups: set-up1 and set-up 2, which can be switched via digital inputs or serial communication commands. Binary code of the digital input terminals correspond with set-ups as follows: HLP-A100 Series Operating Manual…
  • Page 63
    Function Description Range Unit Default Setting Custom Readout Min 0~9999.00 0.00 Value Function: This parameter occurs at 0 Speed. Description of the choice: This parameter allows the choice of the min. value of the custom defined readout. HLP-A100 Series Operating Manual…
  • Page 64
    Description of the choice: The frequency converter can operate in the following three mode: HAND OFF/RESET and AUTO. When running in Hand-on mode, the frequency converter is locally operated and does not allow any remote control. By activating hand a start signal is given. HLP-A100 Series Operating Manual…
  • Page 65
    C00.6* Protection C00.60 Function Description Range Unit Default Setting Menu Password Option: [0] Disabled; [1]Enabled, none of parameter can be changed except this; Function: This feature used to prevent non-commissioning person to HLP-A100 Series Operating Manual…
  • Page 66: Parameter Group 01: Load And Motor

    Torque Characteristics Option: [0] Constant torque, used for constant torque load; [1] Variable torque, used for variable torque load, such as fan applications ¡ ¢ centrifugal pump etc; [3]Auto Energy optimization, see C14.41 AEO minimum magnetisation. HLP-A100 Series Operating Manual…

  • Page 67
    Attention: Changing the value of this parameter affects the setting of C01.22-C01.25 and C01.30-C01.35. *C01.22 Function Description Range Unit Default Setting Motor Voltage 50~1000 Function: Select a value that equals the nameplate data on the motor. Description of choice: Default setting depends on the inverter size. HLP-A100 Series Operating Manual…
  • Page 68
    For the best possible adaptation of the frequency converter, it is recommended to run AMA on a cold motor. This function is disabled when the motor is running. HLP-A100 Series Operating Manual…
  • Page 69
    Unit Default Setting Motor Cable Length 0~150 Function: Enter the motor cable length connected between the motor and the frequency converter. Description of the choice: Set correct cable length can suppress noises resulted from the motor. HLP-A100 Series Operating Manual…
  • Page 70
    Description of choice: This parameter is only functional when par. C01.01, Motor Control Principle is set to V/F [0]. Attention: V0 factory setting is set to 0V, and U1-U5 factory setting is set to Un (motor rated voltage) . HLP-A100 Series Operating Manual…
  • Page 71
    Function: Use this parameter to compensate voltage in relation to load when motor runs at low speed. Description of choice: Enter a percentage value to compensate voltage when motor needs running at low speed. Change-over point is automatically calculated based on motor size. HLP-A100 Series Operating Manual…
  • Page 72
    Description of Choice: This function is only active when par. C01.00, Configuration Mode, is set to Speed Open Loop [0], and when par. C01.01, Motor Control Principle, is set to VVC+ [1]. Slip compensation is calculated automatically based on rated motor speed, nM,N. HLP-A100 Series Operating Manual…
  • Page 73
    Start Function Option: [0] DC Hold/delay time; [2] Coast/delay time; Function: Select [0], Motor is energized with DC holding current (par. C02.00) during start delay time; Select [2], Motor is coasted during start delay time (inverter off). HLP-A100 Series Operating Manual…
  • Page 74
    Option: [0] Coast, the inverter is off; [1] DC Hold, the motor is energized with a DC current. See par. C02.00 DC Hold Current for more information. Function: Here it is possible to select the stop function according to different applications. HLP-A100 Series Operating Manual…
  • Page 75
    Function: Running ETR (Electronic Terminal Relay) function, motor temperature is calculated based on frequency, speed and time. Holip recommends performing the ETR function, if a thermistor is not present. *C01.93 Function Description…
  • Page 76: Parameter Group 02: Brakes

    IM, N set in C01.24. Description of Choice: Parameters related to the DC brake current are as follows: DC-brake command, see C05.1* choice (5); DC brake cut in speed, see C02.04; HLP-A100 Series Operating Manual…

  • Page 77
    C02.11 Function Description Range Unit Default Setting Brake Resistor (ohm) 5~65535 Ω Function: Set brake resistor value. C02.16 Function Description Range Unit Default Setting AC Brake, Max Current 0~150 HLP-A100 Series Operating Manual…
  • Page 78
    Function: The mechanical brake is activated when motor speed is less than Activate Brake Speed. Description of Choice: This feature occurs in the following situations: ● A start command is removed; ● A stop command is activated; ● Quick-stop is activated (Q-stop function is used); HLP-A100 Series Operating Manual…
  • Page 79: Parameter Group 03: Reference/Ramps

    Function: Enter value for Maximum Reference. Description of Choice: The sum of all internal and external references is clamped (limited) to the maximum reference value. Attention: The maximum reference can not be less than C03.02 (Minimum Reference). HLP-A100 Series Operating Manual…

  • Page 80
    Selection of preset reference indicates with a four-digital binary code. If the f requency converter detects the corresponding terminals connected, then the bit is “1”, otherwise, the bit is “0”. Digital input terminal binary code and the corresponding relationship between pre-set values as follows: HLP-A100 Series Operating Manual…
  • Page 81
    Description of Choice: The Catch up/Slow down function is activated by a digital input terminal (See C05.1*, choose [28]/ [29] ). If this function is active, the catch up/slow down value will be added HLP-A100 Series Operating Manual…
  • Page 82
    Reference + Actual reference * Relative Scaling Reference Example: Preset Relative Preset Output Relative Scaling Reference/ Reference/ Reference/ Frequency Reference/ Reference C03.02 C03. 1 0 C03.03 (Hz) C03. 1 4 VI/C03. 1 8=1 10+0+10= 20 10+1+8=19 10+2+5=17 10+3+3= 16 10+4+0=14 HLP-A100 Series Operating Manual…
  • Page 83
    C08.9*; [21] LCP potentiometer, select LCP potentiometer as relative scaling ref. source, see par. C06.8*; Function: The Relative Scaling Ref. Resource can be set via Analog input terminals ¡ ¢ Local bus reference and LCP potentiometer. HLP-A100 Series Operating Manual…
  • Page 84
    If the drive detects the corresponding digital input terminals connected, then the bit is”1”, on the contrary is”0”. The corresponding relationship between state of the digital input terminals ¡ ¢ binary code and the selected ramp type are as follows: HLP-A100 Series Operating Manual…
  • Page 85
    C03.50 Function Description Range Unit Default Setting Ramp2 Type Option: [0] Linear: Motor ramp up to the preset f requency with a constant acceleration; [2] S-ramp: Motor ramp to the preset f requency with non-linear acceleration.. HLP-A100 Series Operating Manual…
  • Page 86
    Attention: Choose a ramp-down time such that no over-voltage arises in the inverter due to regenerative operation of motor and such that the generated current does not exceed the current limit set in C04. 1 8. HLP-A100 Series Operating Manual…
  • Page 87
    See C05. 1 , choose [14]. C03.81 Function Description Range Unit Default Setting Quick Stop Ramp Time 0.05~3600.00 Function: Enter the Quick Stop Ramp Time f rom the rated motor speed (C01.25) to 0Hz. HLP-A100 Series Operating Manual…
  • Page 88: Parameter Group 04: Limits/Warnings

    C04.18 Function Description Range Unit Default Setting Current Limit 0~300 Function: Set the output current high limit. Attention: If a setting in C01.20 to C01.25 is changed, this parameter is not automatically reset to default setting. HLP-A100 Series Operating Manual…

  • Page 89
    [1 1] Open loop running; Function: Select which reaction the f requency converter should take if a feedback fault is detected. Attention: When in HAND mode, and Speed-closed loop is selected, options [1] [3] [4] are invalid. HLP-A100 Series Operating Manual…
  • Page 90
    Function: Enter the n value, when the motor speed falls below this limit, the display reads Speed Low. Attention: This setting must be within normal motor f requency range, otherwise, it may trigger an error warning. HLP-A100 Series Operating Manual…
  • Page 91
    *C04.58 Function Description Range Unit Default Setting Missing Motor Phase Function Option: [0] Off, f unctoin is disabled; [1] On, f unction is enabled; Attention: Missing motor phase causes motor torque to decrease. This f unction HLP-A100 Series Operating Manual…
  • Page 92
    HLP-A100 Series may be disabled for special purpose (e.g. small motor running pure U/f mode). However, choosing [0] Off, f unction disabled, may lead to overheating, Holip strongly recommends to make an active setting to avoid motor damage. C04.6* Speed Bypass C04.61…
  • Page 93: Parameter Group 05: Digital Input/Output

    Default Setting Terminal DI3Digital 0~93 Input C05.15 Function Description Range Unit Default Setting Terminal DI4 Digital 0~93 Input Option: [0] No operation, the f requency converter will not to react to signals transmitted to the terminal; HLP-A100 Series Operating Manual…

  • Page 94
    Freeze output. When Speed up is activated for less than 400 ms. the resulting reference will be increased by 0. 1 %. If Speed up is activated for more than 400 ms. the resulting reference will ramp according to ramp 2 ; HLP-A100 Series Operating Manual…
  • Page 95
    Attention: Because the DO1 also can be used as pulse output, so select [0] digital output in C05.60 to make this parameter active; C05.31 Function Description Range Unit Default Setting Terminal DO2 Digital 0~108 output C05.4* Relay C05.40 Function Description Range Unit Default Setting Relay Function 0~108 5, 9 HLP-A100 Series Operating Manual…
  • Page 96
    [23] Remote ready, no Thermal Warning. Frequency converter is ready for operation in remote control, and no over-temperature warning is present; [24] Ready-Voltage OK. Frequency converter is ready for operation, main voltage is within specified voltage range; [25] Reverse. Motor runs in counter clockwise; HLP-A100 Series Operating Manual…
  • Page 97
    [91] Up to Wobble ref., see par. C30*; [100] Start Pump 1, see C25*; [101] Start Pump 2, see C25*; [102] Below water level, low. See par. C25*; [103] Above water level, high. See par. C25*; HLP-A100 Series Operating Manual…
  • Page 98
    HLP-A100 Series [104] Low water warning. See par. C25*; [105] High water warning. See par. C25*; [106] Low voltage warning. See par. C25*; [107] Over-voltage warning. See par. C25*; [108] Sleep, see par. C25*; HLP-A100 Series Operating Manual…
  • Page 99
    Function: Enter the high f requency corresponding to the high motor shaf t speed in C05.58 Terminal DI4 High Ref./feedback Value. Default C05.57 Function Description Range Unit Setting Terminal DI4 Low 4999.000~4999.000 0.000 Ref./feedback Function: Enter low f requency /feedback corresponding to value in C05.55. HLP-A100 Series Operating Manual…
  • Page 100
    C05.55-C05.56 entered via DI4; [22] Values on analog input VI, 0.020-50.000KHz corresponding to references in C06. 1 0 C06. 1 2 and C06. 1 1 C06. 1 3; [23] Values on analog input AI, 0.020-50.000KHz corresponding to HLP-A100 Series Operating Manual…
  • Page 101
    Function: Enter pulse output min. scale, set as a percentage value of max. signal . C05.64 Function Description Range Unit Default Setting Pulse Output Max. Scale 0.00~200.00 100.00 Function: Enter pulse output max. scale, set as a percentage value of max. signal . HLP-A100 Series Operating Manual…
  • Page 102: Parameter Group 06: Analog In/Out

    [1] Freeze output, f rozen at the present value; [2] Stop, overruled to stop; [3] Jogging, overruled to jog speed; [4] Max. speed, overruled to Max.speed; [5] Stop and trip, overruled to stop with subsequent trip. HLP-A100 Series Operating Manual…

  • Page 103
    C06. 1 5. Default C06.14 Function Description Range Unit Setting Terminal VI Low -4999.000~4999.000 0.000 Ref. /Feedb. Function: Enter VI Low Ref./Feedb. Corresponding to Min. voltage or min. current set in C06. 1 0 or C06. 1 2. HLP-A100 Series Operating Manual…
  • Page 104
    0. In order to prevent the set point jitter at zero point due to analog interference, this parameter should be set properly. HLP-A100 Series Operating Manual…
  • Page 105
    Function: This reference signal should correspond to max. reference/feedback value set in C06.25. C06.22 Function Description Range Unit Default Setting Terminal AI Low Current 0.00~19.99 0.14 Function: This ref erence signal should correspond to min. ref erence / feedback value set in C06.24. HLP-A100 Series Operating Manual…
  • Page 106
    This parameter can’t be adjusted while the motor is running. C06.28 Function Description Range Unit Default Setting Terminal AI Zero Dead 0.00~20.00 0.00 Band Function: Set the dead band for terminal AI at zero, see C06. 1 8. HLP-A100 Series Operating Manual…
  • Page 107
    C1.22; [20] Bus control (0-10V) or (0/4-20mA) corresponding to 0.0% — 100.0%, 100% equals to reference in C03.03; [21] Pulse input (0-10V) or (0/4-20mA) corresponding to reference f rom C05.55 to C5.56 transmitted via terminal DI4; HLP-A100 Series Operating Manual…
  • Page 108
    The LCP potmeter can be select either as reference resource or relative reference resource. Default C06.81 Function Description Range Unit Setting LCP Potmeter Low Ref. -4999.000~4999.000 0.000 Function: This reference value corresponding to potentiometer turned f ully counterwise . HLP-A100 Series Operating Manual…
  • Page 109
    Function: Select choices of analog output VO. C06.93 Function Description Range Unit Default Setting Terminal AO Output 0.00~200.00 0.00 Min. Scale Function: Scale minmum output of selected analog signal at terminal AO as percentage of maximum signal value. See fig. below: HLP-A100 Series Operating Manual…
  • Page 110: Parameter Group 07: Controller

    [8] Pulse input DI4 (0.020 – 50.000 KHz); [1 1] Local Bus (0 ~ ± 200%); Function: Select resource of feedback signal. C07.3* Process PI Ctrl. This parameter is active in closed loop process control mode. HLP-A100 Series Operating Manual…

  • Page 111
    Thereaf ter, when the Process PI Start Speed is reached, the f requency converter will change over to Process PI Control. HLP-A100 Series Operating Manual…
  • Page 112
    On reference Band Width f unction is active. C07.41 Function Description Range Unit Default Setting Process PI Output Low -100-100 Function: Process PI controller output low limit, 100% corresponds to C04. 1 9. HLP-A100 Series Operating Manual…
  • Page 113: Parameter Group 08: Comm. And Options

    [1] Freeze output, Freeze output until communication resumes. [2] Stop, Stop with auto restart when communication resumes; [3] Jogging, Run motor at jog f requency until communication resumes; [4] Max. speed, Run motor at max.f requency until communication HLP-A100 Series Operating Manual…

  • Page 114
    RTU range is 1-247. C08.32 Function Description Range Unit Default Setting FC Port Baud Rate bit/s Option: [0] 2400; [1] 4800; [2] 9600; [3] 19200; [4] 38400; [5]Reserved; [6]Reserved; [7]Reserved; [8]Reserved; [9]Reserved; Function: Select baud rate for FC Port. HLP-A100 Series Operating Manual…
  • Page 115
    Function: Select control of coasting f unction via digital input or bus. C08.51 Function Description Range Unit Default Setting Quick Stop Select Option: [0] Digital input, Aciviate via a digital input; [1] Bus, Activate via serial communication port; HLP-A100 Series Operating Manual…
  • Page 116
    Function Description Range Unit Default Setting Set-up Select Option: [0] Digital input, Aciviate via a digital input; [1] Bus, Activate via serial communication port; [2] Logic and, Activate via serial communication port and a digital input; HLP-A100 Series Operating Manual…
  • Page 117: Parameter Group 13: Simple Plc

    Attention: Simple PLC f unction is only valid in auto mode. C13.0* Simple PLC Settings Use the Sample PLC settings to active disable or reset simple PLC. C13.00 Function Description Range Unit Default Setting Sample PLC Mode Option: [0] *Disabled; HLP-A100 Series Operating Manual…

  • Page 118
    [22] Comparator 0, output of comparator 0 is used in logic rules; [23] Comparator 1, output of comparator 1 is used in logic rules; [24] Comparator 2, output of comparator 2 is used in logic rules; HLP-A100 Series Operating Manual…
  • Page 119
    Function Description Range Unit Default Setting Reset simple PLC Option: [0] Do not reset, Simple PLC doesn’t reset; [1] Reset Simple PLC, reset Simple PLC, references in parameter group C13 will all be restored to factory setting; HLP-A100 Series Operating Manual…
  • Page 120
    [1] Approx. Equal, if the variable selected in C13. 1 0 equals the set value in parC13. 1 2, the comparator output is true; [2] Greater than, opposite with option [0]; Function: Select the operator to be used in the comparison. HLP-A100 Series Operating Manual…
  • Page 121
    Function Description Range Unit Default Setting Logic Rule Operator 1 Array: [4] ; Option: [0] Disabled, ignoring C13.40 and C13.42 ; [1] And, evaluates the expression [C13.40] AND [C13.42]; [2] Or, evaluates the expression [C13.40] OR [C13.42]; HLP-A100 Series Operating Manual…
  • Page 122
    Function: Select the second logic operator to be used on the boolean input calculated in C13.40 Logic Rule Boolean 1 ¡ ¢ C13.42 Logic Rule Operator 1 and C13.43 Logic Rule Boolean 2 and the boolean input coming f rom C13.44 Logic Rule Boolean 3. HLP-A100 Series Operating Manual…
  • Page 123
    [19] Select ramp 2; [20] Select ramp 3; [21] Select ramp 4; [22] Run, issues a start command to the f requency converter; [23] Run reverse, issues a start reverse command to the f requency converter; HLP-A100 Series Operating Manual…
  • Page 124
    [66] Start timer 4; [67] Start timer 5; [68] Start timer 6; [69] Start timer 7; Function: Select the action corresponding to the Simple PLC events (C13.51). Actions are executed when the corresponding event is evaluated as true. HLP-A100 Series Operating Manual…
  • Page 125: Parameter Group 14: Special Functions

    Function Description Range Unit Default Setting Damping Gain Factor 0~200 Function: Damping gain factor can help to improve the response speed of the DC link of the f requency converter making the DC loop signal more smooth. HLP-A100 Series Operating Manual…

  • Page 126
    Attention: If the auto reset mode is selected, the f requency converter may possibly restart automatically af ter the alarm disappear. C14.21 Function Description Range Unit Default Setting Automatic Restart Time 0~600 HLP-A100 Series Operating Manual…
  • Page 127
    C14.3* Current Limit Control The driver contains a current limit controller. The controller will be enabled when the current is over C04. 1 8 current limit. HLP-A100 Series Operating Manual…
  • Page 128
    AEO Min. Magnetisation 40~75 Function: Enter the minimum allowable magnetization for AEO, selection of a low value reduces energy loss in the motor, but can also reduce resistance to sudden load changes, and the output power increases. HLP-A100 Series Operating Manual…
  • Page 129
    [4] Run in low temperature, the inverter will not report low temperature alarm in this mode; [5-8] Reserved; *C14.55 Function Description Range Unit Default Setting Output Filter Option: [0] Off; [1] Sine-wave filter; [3] Sine-wave filter with feedback; Function: Select desired output filter. HLP-A100 Series Operating Manual…
  • Page 130: Parameter Group 15: Drive Information

    Function Description Range Unit Default Setting Power Up’s 0~2147483647 Function: View the number of times the drive has been powered up. This parameter can’t be reset. C15.04 Function Description Range Unit Default Setting Over Temperatures 0~65535 HLP-A100 Series Operating Manual…

  • Page 131
    Function: This parameter contains internal f ault reasons, mostly used in combination with alarm 38. C15.4* ¡ ¢ C15.5*Drive Identification This parameter contains read only information about the hardware and sof tware configuration of the f requency converter. HLP-A100 Series Operating Manual…
  • Page 132
    Description of Choice: View ordering number of the power card. C15.48 Function Description Range Unit Default Setting LCP IDNo. Description of Choice: View LCP ID number. C15.49 Function Description Range Unit Default Setting Software ID Control Card HLP-A100 Series Operating Manual…
  • Page 133
    Unit Default Setting Power Card Serial Number Description of Choice: View power card serial number. C15.5* Defined parameters C15.92 Function Description Range Unit Default Setting Parameter List 0~255 Function: View drive parameters that has been defined. HLP-A100 Series Operating Manual…
  • Page 134: Parameter Group 16: Data Readouts

    No Function Reversing Default C16.01 Function Description Range Unit Setting Reference -4999.000~4999.000 Function: View the total remote reference, the total reference is sum of pulse, analog, preset, LCP Potmeter, local bus and f reeze reference. HLP-A100 Series Operating Manual…

  • Page 135
    No terminal warning Terminal warning C16.04 Function Description Range Unit Default Setting Active Set-up Function: View the drive active set-up. Select 0 indicates set-up 1, Select 1 indicates set-up 2, and select 2 indicates multi-set-up. HLP-A100 Series Operating Manual…
  • Page 136
    Motor Voltage 0~65535 Function: View motor phase voltage. C16.13 Function Description Range Unit Default Setting Frequency 0.0~400.0 Function: View output f requency. C16.14 Function Description Range Unit Default Setting Motor Current 0.00~655.35 Function: View motor phase current. HLP-A100 Series Operating Manual…
  • Page 137
    Unit Default Setting Inv.Max. Current 0.00~655.35 Function: View intermittent maximum inverter current. C16.38 Function Description Range Unit Default Setting Simple PLC State 0~255 Function: View the state of the event under execution by the SL Controller. HLP-A100 Series Operating Manual…
  • Page 138
    Term. Term. Binary Binary Binary Term. No. Binary Term. No. bit0 bit4 bit8 bit12 Reserved bit1 bit5 bit9 bit13 Reserved bit2 bit6 bit10 Reserved bit14 Reserved bit3 bit7 bit1 1 Reserved bit15 Reserved HLP-A100 Series Operating Manual…
  • Page 139
    4-bit binary code; If the digital output terminal is active, the corresponding position is set to “1”, otherwise “0”. Corresponding relationship between state of the digital output terminals and the binary code are as below: Binary bit3 bit2 bit1 bit0 Term. No. Reserved HLP-A100 Series Operating Manual…
  • Page 140
    Function Description Range Unit Default Setting Counter B 0~2147483647 Function: View present value of counter B . C16.78 Function Description Range Unit Default Setting Analog Output AO 0.00~20.00 Function: View output current in analog output AO . HLP-A100 Series Operating Manual…
  • Page 141
    DC Under Volt Undefined DC Over Volt Undefined DC Over Volt Undefined External Short Circuit Undefined Undefined Interlock Undefined Undefined Undefined Undefined Mains ph. loss Undefined Mains ph. loss Undefined AMA Error Undefined No motor Undefined HLP-A100 Series Operating Manual…
  • Page 142
    Function: View the Alarm Word sent via serial communication port in hex code. Default C16.92 Function Description Range Unit Setting Warning Word 1 0~0x7FFFFFFFUF Function: View the Warning Word 1 sent via serial communication port in hex code. HLP-A100 Series Operating Manual…
  • Page 143: Parameter Group 25: App. Functions Cascade

    Preset Time 0.00~23.59 0.00 Option: Choose dif ferent pressure reference at dif ferent times in cascade control systems, the active time need to be set. Attention: If the FC powers off, this parameter needs setting again. HLP-A100 Series Operating Manual…

  • Page 144
    “cascade low f requency” and it lasts more than “low f requency delay time”, the corresponding multi-f unction terminals (relay) acts, auxiliary pump is stopped. C25.21 Function Description Range Unit Default Setting Low Frequency Delay 0.0~3600.0 20.0 Time Function: This parameter used together with “Cascade Low Frequency”. HLP-A100 Series Operating Manual…
  • Page 145
    Function Description Range Unit Default Setting Recovery Low 0.000~99.999 4.000 Pressure Level Function: when the actual pressure rise above “Recovery Low Pressure Level” and continue more than “Recovery Low Pressure Delay Time”, Low Pressure Warning is cancelled. HLP-A100 Series Operating Manual…
  • Page 146
    “Recovery High Pressure Delay Time”, then, over pressure warning is cancelled, the inverter starts to run. C25.37 Function Description Range Unit Default Setting Recovery High 0.0~3600.0 10.0 Pressure Delay Time Function: This parameter used in conjunction with “Recovery High Pressure Level”. HLP-A100 Series Operating Manual…
  • Page 147
    Function: If [0] is selected, the inverter can’t enter sleep mode. C25.51 Function Description Range Unit Default Setting Sleep Pressure Level 0~150.0 95.0 Function: Define the sleep pressure level of the main pump. Sleep Pressure = Target Pressure*Sleep Pressure Level. HLP-A100 Series Operating Manual…
  • Page 148
    Function: Set the sleep f requency duration before the main pump go to sleep mode. C25.57 Function Description Range Unit Default Setting Awake Level 0.0~150.0 80.0 Function: Set the pressure level f rom sleep mode to awake mode. Awake pressure=Set point*Sleep mode awake level. HLP-A100 Series Operating Manual…
  • Page 149
    C25.61 Function Description Range Unit Default Setting Water Level Signal Source Option: [0]: Digital input; [1]: VI; [2]: AI; [8]: Pulse input; Function: Define the source of the water level signal. HLP-A100 Series Operating Manual…
  • Page 150
    Function: To prevent the velocity of the inlet pipe is less than the outlet pipe, leaving the pool water level decreases too f ast, and even form under-voltage condition, pressure 2 is an reserved requirement to run. HLP-A100 Series Operating Manual…
  • Page 151
    Default Setting Alarm Handl Selection Option: [0]: Stop all; [1]: Lag pump 1 Running; [2]: Lag pump 2 Running; [3]: Lag pump 1 2 Running; Function: Set action of the auxiliary pump when drive fault occurs. HLP-A100 Series Operating Manual…
  • Page 152: Parameter Group 30: App. Functions Wobble

    (lantched input type can be accepted also), dwell stage will end; If[1] is selected, dwell stage will end when wobble cycle start command issued, and if wobble cycle start command HLP-A100 Series Operating Manual…

  • Page 153
    Default Setting Centre Frequency Mode Option: [0]: Fixed, center f requency is unchangable ; [1]: Auto Decrease, center f requency of auto decrement. Function: If [1] is selected, center f requency will decrease by the “Center HLP-A100 Series Operating Manual…
  • Page 154
    Function Description Range Unit Default Setting Wobble Down Time 1.0~1000.0 10.0 Function: During the wobble cycle, this parameter used to set the time within which the drive ramp down to wobble down reference (fcenter — fdelta). HLP-A100 Series Operating Manual…
  • Page 155
    Function: This parameter is used to select wobble length source. C30.31 Function Description Range Unit Default Setting Count Per Meter 0.01~600.00 1.00 Fu nction: Wobble Lengt h= (Digital input Encoder input or Pulse input)*Count per meter. HLP-A100 Series Operating Manual…
  • Page 156
    Unit Default Setting Wobble Stage Store Option: [0]: Disable; [1]: Power stop save; [2]: Power saves; [3]: Stop saves; Function: This parameter is used to select in which way the wobble f unction saves the information. HLP-A100 Series Operating Manual…
  • Page 157: Chapter 7 Quick Application Guide

    Note: Control panel potentiometer is used as the only source of the f requency conver ter in HAND mode. (For LCP without potentiometer, use ar row key to set the f requency); Set the lower or upper potentiometer limit via C06.81 and C06.82. HLP-A100 Series Operating Manual…

  • Page 158: Using Digital In Terminals To Control The Drive [Auto]

    5. Disconnect the digital input terminal FOR and VDD to stop the f requency converter. 7.4 Set-up selection Select the menu with digital input DI1 : Par. Code Reference Parameter Description C00. 1 0 Multi Set-up C05. 1 3 Set-up select HLP-A100 Series Operating Manual…

  • Page 159: Potentiometer Reference

    Parameter Description C01 .00 Process closed loop C07.20 Select Analog In AI C06.24 Terminal AI Low Ref./Feedb. value C06.25 Terminal AI high Ref. / Feedb. value Note: **indicates this parameter is set according to the actual situation. HLP-A100 Series Operating Manual…

  • Page 160: Reference For Pulse Input

    C05. 1 5 Reference/feedback resource 7.8 Multi-speed Par. Code Reference Parameter Description C05. 1 2 Preset reference bit0 C05. 1 3 Preset reference bit1 C05. 1 4 Preset reference bit2 C05. 1 5 Preset reference bit3 HLP-A100 Series Operating Manual…

  • Page 161: Speed Up/Down

    HLP-A100 Series Correspondence between speed and the binary code as below: bit3 bit2 bit1 bit0 -Speed 7.9 Speed up/down Par. Code Reference Parameter Description C05. 1 2 Ramp bit0 C05. 1 3 Ramp bit1 HLP-A100 Series Operating Manual…

  • Page 162: Pulse Start/Stop

    Corresponding relation between ramp time and the binary code as below: BIT1 BIT0 RAMP 7.10 Pulse start/stop Par. Code Reference Parameter Description C05. 1 0 Lantched start C05. 1 1 Stop inverse 7.11 Digital speed up/down HLP-A100 Series Operating Manual…

  • Page 163: Configuration Mode

    Motor Speed High Limit C07.02 Speed PID Proportional Gain C07.03 Speed PID Integral Time C07.04 Speed PID Differentiation Time C07.05 Speed PID Diff Gain Time C07.06 Speed PID Low Pass Time C07.08 Speed PID Feed forward Factor HLP-A100 Series Operating Manual…

  • Page 164
    Motor Speed Low Limit C04. 1 4 Motor Speed High Limit C07.33 Process Proportional Gain C07.34 Process PI Integral Time C07.38 Process PI Feed forward Factor Note: **indicates this parameter is set according to the actual situation. HLP-A100 Series Operating Manual…
  • Page 165: Simple Plc

    Timer 2 time reference 2 Preset C03. 1 0[3] C13.20[3] Timer 3 time reference 3 Preset C03. 1 0[4] -100 C13.20[4] Timer 4 time reference 4 Preset C03. 1 0[5] C13.20[5] Timer 5 time reference 5 HLP-A100 Series Operating Manual…

  • Page 166
    Select Preset ref 5 out 4 C13.51 [17] C13.52[17] Select Ramp 2 C13.51 [1 8] C13.52[1 8] Start Timer 6 Simple C13.51 [19] PLC Time- C13.52[19] Select Preset ref 6 out 5 C13.51 [20] C13.52[20] Select Ramp 3 HLP-A100 Series Operating Manual…
  • Page 167: Parallel Execution

    ¡ ¢ local bus excites the inverter to stop, action 3 will be executed. 3. Stop Event: If stop event /C13.02 is true, Simple PLC will be disabled, and C16.38 will be reset to 0. HLP-A100 Series Operating Manual…

  • Page 168: Chapter 8 Accessory Specification

    Model Specification Motor(KW) HLP-A100001 143 HLP-A100001543 HLP-A1001 8D543 1 8.5 HLP-A100002243 HLP-A100003043 HLP-A100003743 HLP-A100004543 13.6 HLP-A100005543 HLP-A100007543 13.6 HLP-A100009043 HLP-A10001 1043 1 10 HLP-A100013243 HLP-A100016043 2. 1 HLP-A100018543 2. 1 1 85 HLP-A100020043 1.65 HLP-A100022043 1.65 HLP-A100 Series Operating Manual…

  • Page 169
    Step 4: Install the exter nal LCP Step 3: The LCP is installed in the communication cable, insert into cradle, according to the direction of RJ45 terminal f rom the bottom of the arrow. hole. HLP-A100 Series Operating Manual…
  • Page 170: Chapter 9 Emc

    ● To reduce the noise and the leakage current, use the motor cable as short as possible; ● The entire system need to have a good earthling; ● RFI Switch screw must be tightened up (≤22kW). HLP-A100 Series Operating Manual…

  • Page 171: Chapter 10 Warnings/Alarms And Fault Handling

    “voltage warning low” limit. Inverter More than 100% overload A.09 E.09 Overload for too long time. Motor temperature Motor ETR Over A. 1 0 E. 1 0 calculated by ETR exceeds Temperature upper limit HLP-A100 Series Operating Manual…

  • Page 172
    Motor phase W Motor phase W is E.32* missing missing,check the phase. Contact the local distributor E.38* Internal Fault or Holip Company. Discharge f rom output E.44* Earth Fault phases to ground(22KW or more) HLP-A100 Series Operating Manual…
  • Page 173
    Heat sink low Temperature may be A.66 temperature damaged. Power Card Power card is over A.69 E.69* temperature. temperature. Rectifier Rectifier Temperature A.74 E.74 Temperature Sensor Error Sensor Error Rectifier A.75 E.75 Temperature Rectifier Temperature High High HLP-A100 Series Operating Manual…
  • Page 174
    Parameter value Invalid parameter value to Er.91 is invalid in this write. mode Parameter is f reezed or Unchangbale can’t be changed during running. Note: Trip-lock alarm is with *. HLP-A100 Series Operating Manual…
  • Page 175: Fault Indication And Trouble Shooting

    4. No fault message Suppose control card is overload, and 24V is shorted, or screen display please remove the connection of control terminal; Make sure if any fault message is displayed, and if no, please contact Holip Company; HLP-A100 Series Operating Manual…

  • Page 176
    If operation of the display screen is normal, please without fault make sure connection between motor and the message f requency converter is correct and then operate the drive in hand mode. Please contact Holip Company if motor can’t rotate. HLP-A100 Series Operating Manual…
  • Page 177: Chapter 11 Maintenance

    If it needs to be stored for a long time make sure to power it up one time within a year and the power-up time should be at least above five hours. When powering up, supply voltage must be increased slowly with a voltage regulator to the rated voltage value. HLP-A100 Series Operating Manual…

  • Page 178: Chapter 12 Communication Protocol

    HLP-A100 Series Chapter 12 Communication protocol HLP-A100 series inverter follows the standard Modbus RTU protocol. 12.1 Format specification Address Function code Data 8 bits 8 bits N*8 bits 16 bits 1)Address: 1-247 2)Function: HLP-A100 support following f unction code 01 : Read Coil Status…

  • Page 179
    Frequency converter ready not ready Coasting stop Satety closed No alarm Alarm Reserved Reserved Reserved No warning Warning Not at reference At reference Hand mode Auto mode Out of f req range In f req range Stopped Running HLP-A100 Series Operating Manual…
  • Page 180: Read Coil Status

    Coil address (ADDRH ADDRL).0x0030 convert to decimal 00 30 number is 48. Coil address 49 is f requency converter output f requency. Data bits number is 16. 0x 0010 convert to decimal number is 00 10 3D C9 CRC check HLP-A100 Series Operating Manual…

  • Page 181: Read Holding Registers

    CRC check Receive data Field Description FC address Function The byte number of received data 0x0000EA60 convert to decimal number is 60000.So the 00 00 EA 60 value of C03.03 is 60000*0.001=60.000 B5 7B CRC check HLP-A100 Series Operating Manual…

  • Page 182: Force Single Coil

    FF00- Parameter changes are written to the RAM and EEPROM; 8D EE CRC check 12.6 Preset Single Register Example: set C01 .01 = 1 Transmit: 01 06 03 F1 00 01 19 BD(Hexadecimal) Receive: 01 06 03 F1 00 01 19 BD(Hexadecimal) HLP-A100 Series Operating Manual…

  • Page 183: Force Multiple Coils

    The byte number is 4 Control word. “7C 04”swap high byte and low byte, the value is 0x047C 7C 04 Note: 0x047C convertes to binary is: 0000 0100 01 1 1 1 100 are corresponding to the coil address 0-15 HLP-A100 Series Operating Manual…

  • Page 184: Preset Multiple Regs

    The register address of C03.03 is 303* 10-1=3029(0x0BD5) 00 02 Register number The byte number of data is 4 0x0000EA60 convert to decimal number is 60000. So the 00 00 EA 60 value of C03.03 is 60000*0.001=60.000 02 B4 CRC check HLP-A100 Series Operating Manual…

  • Page 185: Read/Write Array

    The index is 2(0x0002) 89 C9 CRC check Receive data 1 Field Description FC address Function Register address(ADDRH ADDRL),the register address of 00 08 parameter index is 0x0008 00 02 The index is 2(0x0002) 89 C9 CRC check HLP-A100 Series Operating Manual…

  • Page 186: Exception Code

    Parameter number does not exist 0x01 Defined parameters can not be written 0x02 The value exceeds the upper limit of the parameter 0x03 Index does not exist 0x04 The parameter is not array type 0x05 Data type exception HLP-A100 Series Operating Manual…

  • Page 187
    0x12 Other exception 0x40 Invalid data address 0x41 Invalid length 0x42 Invalid length and value 0x43 Invalid parameter 0x82 The parameters has no bus connection 0x83 Factory settings, cannot be changed. HLP-A100 Series Operating Manual…

alexandrkz

Рекомендуемые сообщения

  •  #1

здравствуйте .частотник холип.хлп а 105.проблема такая завис . а96..на сброс на заводские пишет error.я так понимая активировали 0062-63-64.. как . сделать сброс  ? кто встечался  с такой проблемой  ? прошу помощи . подсказки . 

Поделиться сообщением


Ссылка на сообщение

  •  #2

e4bbea37-8f03-4574-a323-d104466e7ee9.jpg 

c37645c4-a51d-4ba7-81f0-812f7ca0310a (1).jpg 

сброс 51-9 пишет error-60 -80=  (a96 моргает 00 )( 0 можно изменить )

Поделиться сообщением


Ссылка на сообщение

  •  #3

доброе утро .подниму тему — нужна помощь !. у кого какие мысли ? 

Поделиться сообщением


Ссылка на сообщение

  •  #4

Да нету никаких мыслей и цифры странные.

Поделиться сообщением


Ссылка на сообщение

  •  #5

на некоторых горит просто 96 на других А96. перевый регистор( например С) не высвечивается .но примерно зная по конечным цифрам выбираеш  код .заходиш изменяеш .но не прописывается . С0060 изменял .после вода 0051-9 и запретом на 0060пишет r91.

Поделиться сообщением


Ссылка на сообщение

  •  #6

Er.91 это Invalid parameter value to write.

Не правильно выбрали параметр, он не может иметь такое значение.

2 часа назад, alexandrkz сказал:

0051-9

это загрузить параметры по умолчанию, заводские, я б  0060 поставил бы  1 — Enabled, зазрешено грузить параметры.

Поделиться сообщением


Ссылка на сообщение

  •  #7

12 часов назад, сергей св сказал:

я б  0060 поставил бы  1 — Enabled, зазрешено грузить параметры.

Вот да, а потом уж и на заводские по умолчанию.

Поделиться сообщением


Ссылка на сообщение

  •  #8

я пробывал и 0 и 1 . пишит или error или r91 .. мне тут ответели .на почту . что была подобная ситуация . в один день встали все частотники . китай . они связывались с китаем они помогали их перепрошивать . 

Поделиться сообщением


Ссылка на сообщение

  •  #9

пытаюсь разузнать как это делали . но человек уволился кто занимался .там солидная  контора . переводчики итд…. .ну что делать .будем пробывать учится .собирать инфу,я так понимаю нужно подключится к компу . и искакть дамп.

Поделиться сообщением


Ссылка на сообщение

  •  #10

Поделиться сообщением


Ссылка на сообщение

  •  #11

Ну микросхема найдена, а дальше то что, где дамп взять правильный, как её прошить правильно?

Поделиться сообщением


Ссылка на сообщение

  •  #12

Поделиться сообщением


Ссылка на сообщение

  •  #13

Дак вот не слышал я не разу что кто то китайские частотники прошивает и это возможно. И сам бы хотел услышать , а лучше увидеть что кто то это делает и как и чем  это делается.


Изменено 02.04.2023 13:16 пользователем Pavel47

Поделиться сообщением


Ссылка на сообщение

  •  #14

Китайцы часто не дают программы даже на оборудование, мотивируя это тем, что програмное обеспечение это собственность компании. Купили оборудование — пользуйтесь, сломалось вызывайте  специалиста или покупайте новое.

Не думаю, что на частотник можно найти программу для прошивки и саму прошивку. Не для настроек, а именно прошивку микроконтроллера.

Поделиться сообщением


Ссылка на сообщение

  •  #15

я с вами согласен . но есть пословица не боги горшки обжигают . я согласен . что на сегоднешний день это красивые коробочки . ( железо целое . ) все проблемы в програме . ( как мне сказали это демо версия . чтоб прибить на сервис. все говорят не партись купите новые ( что и сделали купили новые и все работает  ). но всетаки хочется разобрать . ( когда время есть занимаюсь . ради спортивного интереса. )я думая что я не один такой .согласитесь . железо хорошое . нужно разобраться с програмой..

Поделиться сообщением


Ссылка на сообщение

  •  #16

46 минут назад, alexandrkz сказал:

. железо хорошое

Сдать в металлолом и получить деньги. 

А по контроллеру и программированию, даташит есть, все в ваших руках, только говорят защита на считывание программ стоит, вот и узнаем.


Изменено 06.04.2023 15:52 пользователем Pavel47

Поделиться сообщением


Ссылка на сообщение

  •  #17

33 минуты назад, alexandrkz сказал:

нужно разобраться с програмой..

Напишите в  Zhejiang Holip Electronic Technology Co., Ltd

интересно, что у вас получится из этого

Поделиться сообщением


Ссылка на сообщение

  •  #18

41 минуту назад, alexandrkz сказал:

железо хорошое . нужно разобраться с програмой..

Всё в ваших руках.

42 минуты назад, alexandrkz сказал:

не боги горшки обжигают

В 10.03.2023 в 15:45, alexandrkz сказал:

подключится к компу . и искакть дамп.

Даже если , допустим , чип не залочен от чтения памяти — что далее ?

Поделиться сообщением


Ссылка на сообщение

Для публикации сообщений создайте учётную запись или авторизуйтесь

Вы должны быть пользователем, чтобы оставить комментарий

Войти

Уже есть аккаунт? Войти в систему.

Войти


  • Последние посетители

      0 пользователей онлайн

    Ни одного зарегистрированного пользователя не просматривает данную страницу

Specifications:

668/668857-hlpa100_series.pdf file (17 Feb 2023)

Accompanying Data:

Holip HLP-A100 Series Inverter PDF Operating Manual (Updated: Friday 17th of February 2023 06:28:42 AM)

Rating: 4.4 (rated by 13 users)

Compatible devices: SOLAR LITE DE96268F, HLP-NV Series, E2000-0004 S2B, CONVERGYS 300, W16650, QP-1800, hlp-c+, HLP-P Series.

Recommended Documentation:

Text of Operating Manual

(Ocr-Read Version Summary of Contents, UPD: 17 February 2023)

  • 49, Holip HLP-A100 Series HLP-A100 Series Operating Manual HLP-A100 Series — 42 — Item Parameter No. Function Description Setting range Unit Def ault setting Page No. Parameter Group 08: FC Port Settings C 0 8.01 Cont rol Site 0: Digital and ctrl. word; 1: Digital only; 2: Control Word only; 0 10 6 C08.02 Control Word Source 0: None; 1: FC RS485; 1 106 C08.03 Control Word Timeout Time 0.1~ 6500.…

  • 137, Holip HLP-A100 Series HLP-A100 Series Operating Manual HLP-A100 Series — 130 — C16.15 Function Description Range Unit Default Setting Frequency(%) 0.0~200.0 % Function: View actual output f requency that is set in percentage. C16.18 Function Description Range Unit Default Setting Motor Thermal 0~100 % Function: View calculated thermal motor load which is set as percentage of estimat…

  • 94, HLP-A100 Series HLP-A100 Series Operating Manual — 87 — [1] Reset, reset the f requency converter af ter a Trip/Alarm; [2] Coast Inverse, no output, leaving the motor coasting to stop; [3] Coast and reset Inverse, the f requency converter resets leaving the motor coasting to stop. [4] Quick stop Inverse, generates a stop in accordance with the quick- stop ramp time set in C03.81; [5]…

  • 74, HLP-A100 Series HLP-A100 Series Operating Manual — 67 — C01.8* Stop Adjustments C01.80 Function Description Range Unit Default Setting Function at Stop 0~1 0 Option: [0] Coast, the inverter is off; [1] DC Hold, the motor is energized with a DC current. See par. C02.00 DC Hold Current for more information. Function: Here it is possible to select the stop function according to different…

  • 167, HLP-A100 Series Operating Manual HLP-A100 Series — 160 — 7.13.2 Parallel Execution The following gure shows parallel execution mode of four events/actions: Exa m ple: 1. S t a r t e v e n t C13.01 = [33] Enter the start event via digital input terminal FOR; C13.00) = [2] Simple PLC parallel control mode; C13.02= [20] the inverter issues an alarm and trips to stop. …

  • 179, HLP-A100 Series Operating Manual HLP-A100 Series — 172 — Status word Coil address 0 1 00 Preset reference bit0 01 Preset reference bit1 02 DC brake No DC brake 03 Coast stop No coast stop 04 Quick-Stop Ramp 05 Freeze f req No f reeze f req 06 Ramp stop Start 07 No reset Reset 08 No jog Jog 09 Ramp 1 Ramp 2 10 Data invalid Data valid 11 R el a y1 of f R el a y1 o n…

  • 169, HLP-A100 Series Operating Manual HLP-A100 Series — 162 — 8.2 LCP Mounting Kit External LCP Communication Cable is network cable. Length should not exceed 15m. More than ve types of shielded cable is recommended for use in the presence of electromagnetic interference environment. An external LCP mounting kit is provided; users need to open a hole (size as shown bel…

  • 141, HLP-A100 Series Operating Manual HLP-A100 Series — 134 — Function: View the last received reference f rom the FC port. C16.86 Function Description Range Unit Default Setting FC Port Reference -32768~32767 C16.8* Field bus/FC Port Function: View the alarm word sent via the serial communication port in hex code. Convert this parameter to a 32-bit binary code, denition of the bit…

  • 72, Holip HLP-A100 Series HLP-A100 Series HLP-A100 Series Operating Manual — 65 — C01.62 Function Description Range Unit Default Setting Slip Compensation -400~399 % 100 Function: Dynamically adjust the output frequency of the motor, maintain the motor approaching a constant speed, and doesn’t vary with load changes. Description of Choice: This function is only active when par. C01.00, Conguration …

  • 51, HLP-A100 Series Operating Manual HLP-A100 Series — 44 — Item Parameter No. Function Description Setting range Unit Def ault setting Page No. Parameter Group 13: Simple PLC C13.4 0 Logic Rule Boolean 1 0~64 0.0 11 4 C13.41 Logic Rule Operator 1 0~8 0 114 C13.42 Logic Rule Boolean 2 Same to C13.40 0 115 C13.43 Logic Rule Operator 2 0~8 0 115 C13.4 4 Logic Rule Boolean 3 Same to C13…

  • Holip HLP-A100 Series User Manual

  • Holip HLP-A100 Series User Guide

  • Holip HLP-A100 Series PDF Manual

  • Holip HLP-A100 Series Owner’s Manuals

Holip HLP-A100 Series Recommended Instructions:

ZX-M, OPAL EL, 1750, XN120, A-711

  • AIMS

    PWRINV2.5K24V

    AIMS POWER INVERTER2500 WATT / 5000 WATT PEAK INPUT VOLTAGE 24 VOLTS DCASSEMBLY AND OPERATING INSTRUCTIONSPWRINV2.5K24VTO PREVENT SERIOUS INJURY,READ AND UNDERSTAND ALL WARNINGSAND INSTRUCTIONS BEFORE USE. …

    PWRINV2.5K24V 9

  • WEG

    DeviceNet CFW500

    USB Communication Plug-in ModuleMódulo Plug-in de Comunicación USB Módulo Plug-in de Comunicação USBCFW500Installation, Configuration and Operation Guide Guía de Instalación, Configuración y Operación Guia de Instalação, Configuração e OperaçãoMotors | Automation | Energy | Transmission & Distribution | Coatings …

    DeviceNet CFW500 32

  • Schumacher Electric

    PI-750

    00-99-000348/0308OWNER’S MANUAL750 Watt DC to AC Power InverterConverts 12V DC Battery Power into 110-120V AC Home Power– SAVE THESE INSTRUCTIONS –Use Schumacher inverters to convert low-voltage, direct-current (DC) to 110-volt alternating household current (AC). Two sources of power are:  Standard 12-volt automobile and marine batteries  Portable …

    PI-750 16

  • Kaco

    Powador

    Operating InstructionsEnglish translation of German original Powador. TL M/XL | . TL M/XL. TL M/XL | . TL M/XL. TL M/XL | . TL Park. TL M/XL | . TL Park …

    Powador 60

  • Omron

    SYSDRIVE 3G3JVS ERIES

    Artisan Technology Group is your source for quality new and certied-used/pre-owned equipment• FAST SHIPPING AND DELIVERY• TENS OF THOUSANDS OF IN-STOCK ITEMS• EQUIPMENT DEMOS• HUNDREDS OF MANUFACTURERS SUPPORTED• LEASING/MONTHLY RENTALS• ITAR CERTIFIED SECURE ASSET SOLUTIONSSERVICE CENTER REPAIRSExperienced engineers and technici …

    SYSDRIVE 3G3JVS ERIES 164

  • SG GROUP

    3100W

    0 Español GENERADOR INVERTER INVERTER GENERATOR GERADOR INVERSOR …

    3100W 104

Additional Information:

Popular Right Now:
Operating Impressions, Questions and Answers:

  • 21 Фев 2017

Добрый день.
В эксплуатации находится такой частотник:

img_20170221_114508_151.jpg

Ссылка на мануал:
 ссылка скрыта от публикации 
Периодически вываливается ошибка: «E.Fb.S» или «E.Fb.A» или «E.Fb.n» или «E.Fb.d» (последний символ указывает, в каком режиме обнаружена ошибка: стоп, разгон, постоянная скорость или торможение).
Есть почти уверенность в «усыхании» электролитов, но не в этом вопрос, а в том, что в мануале отсутствует описание таких ошибок. Никто не сталкивался?

img_20170221_114508_151.jpg

  • 1 Апр 2019

У вас с частотником получилось разобраться?


Информация
Неисправность
Прошивки
Схемы
Справочники
Маркировка
Корпуса
Сокращения и аббревиатуры
Частые вопросы
Полезные ссылки

  • Справочная информация

    Этот блок для тех, кто впервые попал на страницы нашего сайта. В форуме рассмотрены различные вопросы возникающие при ремонте бытовой и промышленной аппаратуры. Всю предоставленную информацию можно разбить на несколько пунктов:

    • Диагностика
    • Определение неисправности
    • Выбор метода ремонта
    • Поиск запчастей
    • Устранение дефекта
    • Настройка

    Учитывайте, что некоторые неисправности являются не причиной, а следствием другой неисправности, либо не правильной настройки. Подробную информацию Вы найдете в соответствующих разделах.

  • Неисправности

    Все неисправности по их проявлению можно разделить на два вида — стабильные и периодические. Наиболее часто рассматриваются следующие:

    • не включается
    • не корректно работает какой-то узел (блок)
    • периодически (иногда) что-то происходит

    Если у Вас есть свой вопрос по определению дефекта, способу его устранения, либо поиску и замене запчастей, Вы должны создать свою, новую тему в соответствующем разделе.

  • О прошивках

    Большинство современной аппаратуры представляет из себя подобие программно-аппаратного комплекса. То есть, основной процессор управляет другими устройствами по программе, которая может находиться как в самом чипе процессора, так и в отдельных микросхемах памяти.

    На сайте существуют разделы с прошивками (дампами памяти) для микросхем, либо для обновления ПО через интерфейсы типа USB.

    • Прошивки ТВ (упорядоченные)
    • Запросы прошивок для ТВ
    • Прошивки для мониторов
    • Запросы разных прошивок
    • … и другие разделы

    По вопросам прошивки Вы должны выбрать раздел для вашего типа аппарата, иначе ответ и сам файл Вы не получите, а тема будет удалена.

  • Схемы аппаратуры

    Начинающие ремонтники часто ищут принципиальные схемы, схемы соединений, пользовательские и сервисные инструкции. Это могут быть как отдельные платы (блоки питания, основные платы, панели), так и полные Service Manual-ы. На сайте они размещены в специально отведенных разделах и доступны к скачиванию гостям, либо после создания аккаунта:

    • Схемы телевизоров (запросы)
    • Схемы телевизоров (хранилище)
    • Схемы мониторов (запросы)
    • Различные схемы (запросы)

    Внимательно читайте описание. Перед запросом схемы или прошивки произведите поиск по форуму, возможно она уже есть в архивах. Поиск доступен после создания аккаунта.

  • Справочники

    На сайте Вы можете скачать справочную литературу по электронным компонентам (справочники, таблицу аналогов, SMD-кодировку элементов, и тд.).

    • Справочник по транзисторам
    • ТДКС — распиновка, ремонт, прочее
    • Справочники по микросхемам
    • … и другие …

    Информация размещена в каталогах, файловых архивах, и отдельных темах, в зависимости от типов элементов.

  • Marking (маркировка) — обозначение на электронных компонентах

    Современная элементная база стремится к миниатюрным размерам. Места на корпусе для нанесения маркировки не хватает. Поэтому, производители их маркируют СМД-кодами.

    • Справочники по SMD компонентам
    • Опознать элемент в телевизоре (вопросы)
    • Справочники по SMD кодам компонентов
    • Маркировка SMD транзисторов от PHILIPS

  • Package (корпус) — вид корпуса электронного компонента

    При создании запросов в определении точного названия (партномера) компонента, необходимо указывать не только его маркировку, но и тип корпуса. Наиболее распостранены:

    • DIP (Dual In Package) – корпус с двухрядным расположением контактов для монтажа в отверстия
    • SOT-89 — пластковый корпус для поверхностного монтажа
    • SOT-23 — миниатюрный пластиковый корпус для поверхностного монтажа
    • TO-220 — тип корпуса для монтажа (пайки) в отверстия
    • SOP (SOIC, SO) — миниатюрные корпуса для поверхностного монтажа (SMD)
    • TSOP (Thin Small Outline Package) – тонкий корпус с уменьшенным расстоянием между выводами
    • BGA (Ball Grid Array) — корпус для монтажа выводов на шарики из припоя

  • Краткие сокращения

    При подаче информации, на форуме принято использование сокращений и аббревиатур, например:

      Сокращение   Краткое описание
    LED Light Emitting Diode — Светодиод (Светоизлучающий диод)
    MOSFET Metal Oxide Semiconductor Field Effect Transistor — Полевой транзистор с МОП структурой затвора
    EEPROM Electrically Erasable Programmable Read-Only Memory — Электрически стираемая память
    eMMC embedded Multimedia Memory Card — Встроенная мультимедийная карта памяти
    LCD Liquid Crystal Display — Жидкокристаллический дисплей (экран)
    SCL Serial Clock — Шина интерфейса I2C для передачи тактового сигнала
    SDA Serial Data — Шина интерфейса I2C для обмена данными
    ICSP In-Circuit Serial Programming – Протокол для внутрисхемного последовательного программирования
    IIC, I2C Inter-Integrated Circuit — Двухпроводный интерфейс обмена данными между микросхемами
    PCB Printed Circuit Board — Печатная плата
    PWM Pulse Width Modulation — Широтно-импульсная модуляция
    SPI Serial Peripheral Interface Protocol — Протокол последовательного периферийного интерфейса
    USB Universal Serial Bus — Универсальная последовательная шина
    DMA Direct Memory Access — Модуль для считывания и записи RAM без задействования процессора
    AC Alternating Current — Переменный ток
    DC Direct Current — Постоянный ток
    FM Frequency Modulation — Частотная модуляция (ЧМ)
    AFC Automatic Frequency Control — Автоматическое управление частотой

  • Частые вопросы

    Как мне дополнить свой вопрос по теме Ошибка частотника HOLIP.?

    После регистрации аккаунта на сайте Вы сможете опубликовать свой вопрос или отвечать в существующих темах. Участие абсолютно бесплатное.

    Кто отвечает в форуме на вопросы ?

    Ответ в тему Ошибка частотника HOLIP. как и все другие советы публикуются всем сообществом. Большинство участников это профессиональные мастера по ремонту и специалисты в области электроники.

    Как найти нужную информацию по форуму ?

    Возможность поиска по всему сайту и файловому архиву появится после регистрации. В верхнем правом углу будет отображаться форма поиска по сайту.

    По каким еще маркам можно спросить ?

    По любым. Наиболее частые ответы по популярным брэндам — LG, Samsung, Philips, Toshiba, Sony, Panasonic, Xiaomi, Sharp, JVC, DEXP, TCL, Hisense, и многие другие в том числе китайские модели.

    Какие еще файлы я смогу здесь скачать ?

    При активном участии в форуме Вам будут доступны дополнительные файлы и разделы, которые не отображаются гостям — схемы, прошивки, справочники, методы и секреты ремонта, типовые неисправности, сервисная информация.

  • Полезные ссылки

    Здесь просто полезные ссылки для мастеров. Ссылки периодически обновляемые, в зависимости от востребованности тем.

    • Блок питания RIDEN RD606 и другие
    • Программатор Postal — сборка, настройка
    • Жесткие диски (HDD). Ссылки, софт, рекомендации по ремонту
    • Расшифровка сигналов БИОС
    • Сервис Центры по ремонту ноутбуков
    • Замена МИКРОСХЕМ — аналоги, доработки
    • Книги, журналы, справочная литература в сети
    • ВАРИСТОРЫ, ПРЕДОХРАНИТЕЛИ применение, справочные данные
    • Фотоприемники, оптопары
    • ПАЙКА — технология, советы, секреты

  • 1 Апр 2019

Был подобный случай, мучил долго, чистили контакты, поменяли реле шунтирующее, бывает неделю проработает, бывает через день. У них там стоит блок-контакт при включении шунтирующего реле он замыкается и сигнал идет в процессор, грешил на него, если его не замыкать, то ошибка эта вообще не пропадает. Так и не смогли заставить работать ,пока он не сгорел(силовой модуль бахнул)
И заменили на другую марку ПЧ, с другим ПЧ проблем не было.

Поделиться:

Twitter

Reddit

Pinterest

Tumblr

Ссылка

Понравилась статья? Поделить с друзьями:
  • Частотник advanced m420 ошибки
  • Частотник fuji electric ошибки
  • Частотник abb ошибка а5011
  • Частотник frenic 5000g11 ошибки
  • Частотник abb ошибка а2010