Alert Code
Normal Run
Normal operation, no trip.
Solid Yellow
Code1
Long run time. Compressor is on running for more
than 18 hours. (Code1 is disabled in Heat Pump
Yellow Flash 1
mode.)
Code2
Compressor (pressure) trip. Compressor runs for
12 sec to 15 min followed by a compressor trip
Yellow Flash 2
condition lasting longer than 7 min.
Code3
Pressure switch cycling. Compressor runs for 12
sec to 15 min followed by a compressor trip lasting
Yellow Flash 3
between 35 sec to 7 min.
Code4
Locked rotor. Compressor trips within a compressor
run time of 12 sec and does not start within 35 sec.
Yellow Flash 4
Code5
Compressor (moderate run) trip. Compressor runs
for 15 min to 18 hrs followed by a compressor trip
Yellow Flash 5
lasting longer than 7 min.
Code9
The current to the PROT terminal is greater than 2A
Red Flash 9
Trip
Demand is present, but compressor is not running
Solid Red
© 2015 Emerson Climate Technologies
Table 1 — Quick Reference Table
Alert Condition
9
AE8-1379 R2
Lock
Lock Level
Indication
N/A
N/A
Red: Flash 2
4x consecutive
Yellow: Off
4x consecutive
Red: Flash 3
or 10x total
Yellow: Off
Red: Flash 4
10x consecutive
Yellow: Off
4x consecutive
Red: Flash 5
or 10x total
Yellow: Off
Red: Flash 9
Current >2A
for 40ms
Yellow: Off
N/A
N/A
N/A
N/A
1
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
Application Engineering
BULLETIN
Safety
Safety Instructions ………………………………………………………..2
Safety Icon Explanation ……………………………………………….. 2
Instructions Pertaining to Risk of Electrical Shock, Fire,
or Injury to Persons ………………………………………………………3
Safety Statements ………………………………………………………..3
Introduction
Overview …………………………………………………………………….4
Application Restrictions and Types ………………………………… 4
Product Specifi cations …………………………………………………..4
Installation
Mounting …………………………………………………………………….4
Terminal Description ……………………………………………………..4
Operation
Compressor Protection …………………………………………………4
Module LED Description ………………………………………………. 5
Module Operation/Code Description ……………………………….5
Resetting Alert Codes ………………………………………………….. 6
Service
Module History Download …………………………………………….. 6
Warranty Information ……………………………………………………. 6
Support ………………………………………………………………………. 6
Figures and Tables
Wires Pulled Through Module ……………………………………….. 6
Module Dimensions in Millimeters ………………………………….. 7
Terminal Locations ……………………………………………………….7
Wiring Diagram …………………………………………………………… 8
Flash Code Description ………………………………………………… 9
LED Troubleshooting Information ……………………………….. 10-12
TABLE OF CONTENTS
AE8-1385
CoreSense™ Diagnostics
for Copeland Scroll® UltraTech® Air Conditioning Compressors
October 2011
2
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
Safety Instructions
Copeland Scroll® compressors with CoreSense™ Diagnostics technology are manufactured according to the latest
U.S. and European Safety Standards. Particular emphasis has been placed on the user’s safety. Safey icons are
explained below and safety instructions applicable to the products in this bulletin are grouped on Page 3. These
instructions should be retained throughout the lifetime of the compressor. You are strongly advised to follow
these safety instructions.
Safety Icon Explanation
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION, used with the safety alert symbol, indicates a hazardous
situation which, if not avoided, could result in minor or moderate injury.
NOTICE is used to address practices not related to personal injury.
CAUTION, without the safety alert symbol, is used to address practices
not related to personal injury.
DANGER
WARNING
CAUTION
NOTICE
CAUTION
3
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
ELECTRICAL SHOCK HAZARD
• Disconnect and lock out power before servicing.
• Discharge all capacitors before servicing.
• Use compressor with grounded system only.
• Molded electrical plug must be used when required.
• Refer to original equipment wiring diagrams.
•
• Failure to follow these warnings could result in serious personal injury.
PRESSURIZED SYSTEM HAZARD
• System contains refrigerant and oil under pressure.
• Remove refrigerant from both the high and low compressor side before
removing compressor.
•
• Never install a system and leave it unattended when it has no charge,
a holding charge, or with the service valves closed without electrically
locking out the system.
• Use only approved refrigerants and refrigeration oils.
• Personal safety equipment must be used.
• Failure to follow these warnings could result in serious personal injury.
BURN HAZARD
• Do not touch the compressor until it has cooled down.
• Ensure that materials and wiring do not touch high temperature areas of
the compressor.
• Use caution when brazing system commponents.
• Personal safety equipment must be used.
• Failure to follow these warnings could result in serious personal injury or
property damage.
COMPRESSOR HANDLING
• Use the appropriate lifting devices to move compressors.
• Personal safety equipment must be used.
• Failure to follow these warnings could result in personal injury or
property damage.
Safety Statements
• Refrigerant compressors must be employed only for their intended use.
•
install, commission and maintain this equipment.
•
• All valid standards and codes for installing, servicing, and maintaining electrical and
refrigeration equipment must be observed.
Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons
WARNING
WARNING
WARNING
CAUTION
4
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
INTRODUCTION
Overview
CoreSense™ Diagnostics is a breakthrough innovation
for troubleshooting residential air conditioning and heat
pump systems. The CoreSense Diagnostics module
is easily installed in the unit electrical panel near the
compressor contactor. By using the compressor as
a sensor, CoreSense Diagnostics helps the service
technician more accurately troubleshoot system and
compressor fault conditions.
CoreSense Diagnostics also provides compressor
and system protection through its proprietary lockout
feature. Depending on the severity and frequency of
the fault that caused the trip condition, the CoreSense
Diagnostics module can lockout the compressor
contactor to prevent damage to the compressor and
system components. Less severe fault conditions
resulting in an occasional trip will not result in a lockout
condition.
Flashing LEDs communicate ALERT and LOCK codes
to the service technician.
Application Restrictions and Types
The CoreSense Diagnostics (571-0072-00) module
is designed and qualifi ed for use with ZPS*K5 single-
phase Copeland Scroll® UltraTech™ compressors.
Product Specifi cations
Operating Temp: — 40° to 150°F (- 40° to 65°C)
Storage Temp: — 40° to 175°F (- 40° to 80°C)
Supply Voltage: 18 to 28VAC , 48 to 62Hz
Module Current Sensing Range: 2 to 30A
Maximum Power Consumption: 2.5 VA (Excluding
solenoid load)
INSTALLATION
Mounting
Four #8 or #10 self tapping or sheet metal screws are
required for installation of the module. The maximum
mounting screw torque is 20 in.lbs. Locate the
module near the compressor contactor (wire routing
for compressor run, common, and start wires will be
easier in this position). The module can be mounted
in any orientation and LEDs should be visible for ease
of service.
The compressor’s run (R), common (C), and start (S)
wires are routed through the holes in the CoreSense
module marked “R”,”C”, and “S”. See Figure 1.
Terminal Description
The terminals for the CoreSense Diagnostics module
are ¼” spade terminals.
• COMMON (C)
The 24 volt common terminal for module power.
• DEMAND (Y)
The demand terminal requires a 24VAC signal
measured with respect to the COMMON (C)
terminal when there is a call for heating or
cooling. A signal above 6VAC indicates the
thermostat wants the compressor to be on, while
0-6VAC signal indicates the thermostat wants
the compressor to be off.
• SECOND STAGE DEMAND (Y2)
The demand (Y) and second stage demand
(Y2) terminals require a 24VAC signal measured
with respect to the COMMON (C) terminal when
there is a call for heating or cooling. A signal
above 10VAC indicates the thermostat wants the
Ultratech solenoid to be energized, while 0-10VAC
signal indicates the thermostat wants the Ultratech
solenoid to be deenergized.
• PROTECTION (PROT)
The protection terminal is internally connected
to the COMMON terminal through a solid state
switch.
• POWER (R)
The module requires a constant 24VAC supply
power to this terminal. The module must receive
an independent power supply in order to operate
properly. See Figure 4.
• Thermostat Communication (L)
Provides a 24V signal to an indoor thermostat
indicating the number of ALERT fl ashes displayed
on the module. (Reference thermostat manual for
available capability)
• Solenoid (DC SOL)
Provides a connection to the Copeland Scroll
UltraTech second stage compressor solenoid. This
solenoid is internal to the compressor, and has
a voltage range of 18 to 28VDC. Please refer to
bulletin AE-1311 for information on the Copeland
Scroll® UltraTech® compressor.
5
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
OPERATION
Compressor Protection
The CoreSense Diagnostics module utilizes proprietary
algorithms to protect the compressor and system from
repeated trips of system pressure controls and the
compressor internal overload. The protection terminal
of the module should be wired in series with the system
low pressure and high pressure cutouts, as well as
the compressor contactor. When the module detects
a series of trips as described below, it will activate a
lockout feature that opens the solid state switch in the
module, thereby cutting power to the contactor and de-
energizing the compressor.
Module LED Description
POWER LED (Green): indicates the module is
powered with 18 to 28 volts.
ALERT LED (Yellow): communicates an abnormal
system condition through a unique fl ash code. The
ALERT LED will fl ash a number of times consecutively,
pause and then repeat the process. The number of
consecutive fl ashes, defi ned as the Flash Code,
correlates to a particular abnormal condition. Detailed
descriptions of specifi c ALERT Flash Codes are
shown in Table 1.
TRIP/LOCK LED (Red): indicates either a TRIP or
LOCK condition.
• TRIP: is indicated by a solid illumination of the
LED. This means the compressor is not running
and demand is present at the module.
• LOCK: is indicated by a fl ashing LED correlating to
a LOCK condition in which the module will prevent
the compressor from starting.
Module Operation/Code Description
Code 1 – Long Run Time
The module will fl ash yellow one time when the
compressor operates for longer than 18 continuous
hours. This is an alert code only, and the module will
not lockout the compressor for this condition. This
code is inactive for heat-pumps.
Code 2 – Compressor (Pressure) Trips
The module will fl ash yellow two times when the
compressor operates from 12 seconds to 15 minutes
followed by a trip condition lasting longer than 7
minutes. When four consecutive or ten total Code
2 events are recorded, the module will lockout the
compressor and fl ash red two times.
Code 3 – Pressure Switch Cycling
The module will fl ash yellow three times when the
compressor operates from 12 seconds to 15 minutes
followed by a trip condition lasting between 35
seconds to 7 minutes. When four consecutive or ten
total Code 3 events are recorded, the module will
lockout the compressor and fl ash red three times.
Code 4 – Locked Rotor Trip
The module will fl ash yellow four times when the
compressor trips within 12 seconds of operation and
does not reset and start within 35 seconds. When ten
consecutive Code 4 events are recorded the module
will lockout the compressor and fl ash red four times.
Code 5 – Compressor (Moderate Run) Trip
The module will fl ash yellow fi ve times when the
compressor has operated between 15 minutes and
18 hours, followed by a compressor trip lasting longer
than 7 minutes. When four consecutive or ten total
Code 5 events are recorded, the module will lockout
the compressor and fl ash red fi ve times.
Code 6 – Open Start Circuit
The module will lockout the compressor and fl ash
red six times if the module detects a demand signal
in the “Y” terminal and current in the “R” winding of
the compressor, but no current is detected in the “S”
winding of the compressor for 2 seconds.
Code 7 – Open Run Circuit
The module will lockout the compressor and fl ash red
seven times if the module detects a demand signal
in the “Y” terminal and current in the “S” winding of
the compressor, but no current is detected in the “R”
winding of the compressor for 2 seconds.
Code 8 – Welded Contactor
The module will fl ash yellow eight times if it has
detected line currents in the “S” and “R” windings and
demand is absent for 15 seconds.
Code 9 – Low Voltage
The module will fl ash nine times if the module supply
voltage drops below 17VAC for 2 seconds. The
module will prevent the compressor from starting until
adequate voltage is established.
Code 10 – Over-Current Protection
When the current at the PROT terminal is greater than
2A for 40ms, the module will fl ash a Code 10. The red
LED will fl ash 10 times with the yellow LED remaining
6
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
off. This event will cause a lockout of the compressor
and indicates that the module is mis-wired or the
contactor coil is shorted to ground.
NOTICE
Code 10 is not specifi ed on the module label.
Resetting Alert Codes
When the CoreSense Diagnostics module has detected
a series of adverse conditions that have caused it to
lockout the compressor, and after the issue has been
resolved, it is necessary to manually reset the module
in order to clear the present alert code.
The primary way of clearing the code and resetting
the ALERT or TRIP/LOCK is to cycle the power to the
module by disengaging the COMMON (C) Terminal.
This will not clear the seven day operating history
contained in the module memory. It will only clear the
present ALERT or TRIP/LOCK and allow for normal
operation.
SERVICE
WARNING
Always disconnect and lockout the power supply
before beginning electrical troubleshooting.
Module History Download
The CoreSense Diagnostics module is capable of
communicating with a personal computer, tablet, or
laptop, via Emerson Climate Technologies computer
Figure 1
Wires Pulled Through Module
software interface and USB connection, in order to
download and store fault history and module operation
time. This information can be used to help diagnose
and review data from troubled systems in the fi eld. For
more information, please contact your Emerson Climate
Application Engineer.
Warranty Information
Emerson Climate Technologies, Inc. warrants its
diagnostic module to be free from defects in materials
and workmanship under normal use for a period of one
year from the date of purchase or twenty months from
manufacture, whichever comes fi rst. During this period,
Emerson Climate Technologies, Inc. will replace any
defective diagnostic module without charge.
For more information on product warranty please visit
www.EmersonClimate.com
Support
For more information visit www.EmersonClimate.com,
or contact Emerson Climate Technologies, Inc. at 1-888-
EMR-9950.
7
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
ALERT
TRIP / LOCK
POWER
1 Long Run Time
2 Compressor (Pressure) Trip
3 Pressure Switch Cycling
4 Locked Rotor
5 Compressor (Mod Run) Trip
6 Open Start Circuit
7 Open Run Circuit
8 Welded Contactor
9 Low Voltage
DC SOL operating range: 18-28VDC
Compressor second stage is
energized when Y & Y2 are 24VAC
PROT breaks 24VAC common
leg of compressor contactor coil
Reset codes and PROT lockout
by removing 24VAC to module
Flash Event
Two Stage Control
Active Protection
C
S
R
47
37
62 112
67
Figure 2 – Module Dimensions in Millimeters
Y2
Y
Data Port
L
R
C
PROT
Solenoid
For Use With
Copeland Scroll
UltraTech
Compressors
P/N: 543-XXXX-XX
065312345
Patent: 6,615,594
Use With Class 2
Circuits Only
Supply 24VAC
50/60Hz
Power 1.5VA
Figure 3 – Terminal Locations
8
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
2-Stage
Thermostat
Indoor
Unit
Outdoor
Unit
C
R
Y1
Y2
C
R
L
Y
Y2
L
DC
Solenoid Solenoid
CoreSense
High/Low
Pressure Switch
CC
Compressor
Contactor
C
R
Y1
Y2
L
C
R
Y1
Y2
L
Prot
Figure 4
Wiring Diagram
9
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
Alert Code Alert Condition Lockout Level Lockout
Indication
Normal Run
Solid Green Normal operation, no trip. N/A N/A
Code1
Yellow Flash 1
Long run time. Compressor is running for more than
18 hours at full load. (Code1 is disabled in Heat Pump
mode.)
N/A N/A
Code2
Yellow Flash 2
Compressor Pressure trip. Compressor runs for 12sec
to 15min followed by a compressor trip condition lasting
longer than 7min.
4x consecutive,
10x total Red: Flash 2
Code 3
Yellow Flash 3
Pressure switch cycling. Compressor runs for 12sec to
15min followed by a compressor trip lasting between
35sec to 7min.
4x consecutive,
10 total Red: Flash 3
Code4
Yellow Flash 4
Locked rotor. Compressor trips within a compressor run
time of 12sec and does not start within 35sec. 10x consecutive Red: Flash 4
Code5
Yellow Flash 5
Compressor moderate run trip. Compressor runs for
15min to 18hrs followed by a compressor trip lasting
longer than 7min.
4x consecutive,
10x total Red: Flash 5
Code6
Red Flash 6
Open start circuit. Module has detected Y or Y1, and
current in the R winding of the compressor and no
current in the S winding of the compressor for 2 seconds.
1 occurrence Red: Flash 6
Code7
Red Flash 7
Open run circuit. Module has detected Y or Y1, and
current in the S winding of the compressor and no current
in the R winding of the compressor for 2 seconds.
1 occurrence Red: Flash 7
Code8
Yellow Flash 8
Welded Contactor. Module has detected line currents
in R and S windings, and Y or Y1 is at 0 VAC for 15
seconds.
N/A N/A
Code9
Yellow Flash 9
Low Voltage. Module has detected a 24 VAC supply
voltage below 17 VAC +/- 1 VAC for 2 seconds
N/A N/A
Code10
Red Flash 10
Over Current Protection. PROT terminal has above a 2A
input for more than 40 milliseconds. 1 occurrence Red: Flash 10
Table 1 – Flash Code Description
10
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
Status Description Troubleshooting Information
Solid Green “RUN” Module has power and
operating normally Supply voltage is present at module terminals
Solid Red “TRIP”
Thermostat demand signal Y is
present, but the compressor is
not running
1. Compressor protector is open
• Check for high head pressure
• Check compressor supply voltage
2. Outdoor unit power disconnect is open
3. Compressor circuit breaker or fuse(s) is open
4. Broken wire or connector is not making contact
5. High pressure switch open if present in system
6. Compressor contactor has failed open
“ALERT” Flash Codes
Yellow “ALERT”
Flash Code 1
Long Run Time
Low Refrigerant Charge
Compressor is running extremely
long run cycles
1. Low refrigerant charge
2. Evaporator blower is not running
• Check blower relay coil and contacts
• Check blower motor capacitor
• Check blower motor for failure or blockage
• Check evaporator blower wiring and connectors
• Check indoor blower control board
• Check thermostat wiring for open circuit
3. Evaporator coil is frozen
• Check for low suction pressure
• Check for excessively low thermostat setting
• Check evaporator airfl ow (coil blockages or return air fi lter)
• Check ductwork or registers for blockage
4. Faulty metering device
• Check TXV bulb installation (size, location and contact)
• Check if TXV/fi xed orifi ce is stuck closed or defective
5. Liquid line restriction (fi lter drier blocked if present in system)
6. Thermostat is malfunctioning
• Check thermostat sub-base or wiring for short circuit
• Check thermostat installation (location, level)
Yellow “ALERT”
Flash Code 2
Compressor (Pressure) Trip
High Refrigerant Charge
Discharge pressure out of limits
or compressor overloaded
1. Condenser fan is not running
• Check fan capacitor
• Check fan wiring and connectors
• Check fan motor for failure or blockage
2. High head pressure
• Check high pressure switch if present in system
• Check if system is overcharged with refrigerant
• Check for non-condensable in system
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Return air duct has substantial leakage
Yellow “ALERT”
Flash Code 3
Pressure Switch Cycling
Compressor is running only
briefl y due to pressure switch
cycling
1. Time delay relay or control board defective
2. If high pressure switch present go to Flash Code 2 information
Table 2 – CoreSense Diagnostics LED Troubleshooting Information
Flash Code number corresponds to the number of LED fl ashes, followed by a pause and then repeated.
TRIP and ALERT LEDs fl ashing at same time means control circuit voltage is too low for operation (brown-out conditions).
11
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
Yellow “ALERT”
Flash Code 4 Locked Rotor
1. Run capacitor has failed
2. Low line voltage (contact utility if voltage at disconnect is low)
• Check wiring connections
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
• Measure compressor oil level
Yellow “ALERT”
Flash Code 5
Compressor (Moderate Run)
Trip
1. Evaporator blower is not running
• Check blower relay coil and contacts
• Check blower motor capacitor
• Check blower motor for failure or blockage
• Check evaporator blower wiring and connectors
• Check indoor blower control board
• Check thermostat wiring for open circuit
2. Faulty metering device
• Check TXV bulb installation (size, location and contact)
• Check if TXV/fi xed orifi ce is stuck closed or defective
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Low refrigerant charge
Yellow “ALERT”
Flash Code 8
Welded Contactor
Compressor always runs
1. Compressor contactor has failed closed
2. Thermostat demand signal not connected to module
Yellow “ALERT”
Flash Code 9
Low Supply Voltage
Voltage below 18V
1. Control Circuit transformer is overloaded
2. Low line voltage (contact utility if voltage at disconnect is low)
“LOCKOUT” Flash Codes
Red “LOCKOUT”
Flash Code 2
Yellow Off
Compressor (Pressure) Trip
Compressor is locked out
after 4 consecutive or 10 total
compressor (pressure) trip events
1. Condenser fan is not running
• Check fan capacitor
• Check fan wiring and connectors
• Check fan motor for failure or blockage
2. High head pressure
• Check high pressure switch if present in system
• Check if system is overcharged with refrigerant
• Check for non-condensable in system
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Return air duct has substantial leakage
Red “LOCKOUT”
Flash Code 3
Yellow Off
Pressure Switch Cycling
Compressor is locked out after 4
consecutive or 10 total pressure
cycling events
1. Time delay relay or control board defective
2. If high pressure switch present go to Flash Code 2 information
Red “LOCKOUT”
Flash Code 4
Yellow Off
Locked Rotor
Compressor is locked out after 10
consecutive locked rotor events
1. Run capacitor has failed
2. Low line voltage (contact utility if voltage at disconnect is low
• Check wiring connections
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
• Measure compressor oil level
Table 2 Continued
12
© 2011 Emerson Climate Technologies
Printed in the U.S.A.
AE8-1385
Application Engineering
BULLETIN
Red “LOCKOUT”
Flash Code 5
Yellow Off
Compressor (Moderate Run)
Trip
Compressor is locked out
after 4 consecutive or 10 total
compressor (moderate run) trip
events
1. Evaporator blower is not running
• Check blower relay coil and contacts
• Check blower motor capacitor
• Check blower motor for failure or blockage
• Check evaporator blower wiring and connectors
• Check indoor blower control board
• Check thermostat wiring for open circuit
2. Faulty metering device
• Check TXV bulb installation (size, location and contact)
• Check if TXV/fi xed orifi ce is stuck closed or defective
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Low refrigerant charge
Red “LOCKOUT”
Flash Code 6
Yellow Off
Open Start Circuit
Current only in run circuit
1. Run capacitor has failed
2. Open circuit in compressor start wiring or connections
• Check wiring and connectors between supply and the
compressor “S” terminal
3. Compressor start winding is damaged
• Check compressor motor winding resistance
Red “LOCKOUT”
Flash Code 7
Yellow Off
Open Run Circuit
Current only in start circuit
1. Open circuit in compressor run wiring or connections
• Check wiring and connectors between supply and the
compressor “R” terminal. Confi rm proper wire routing per
Figure 1.
2. Compressor run winding is damaged
• Check compressor motor winding resistance
Red “LOCKOUT”
Flash Code 10
Over Current Protection
Current to PROT is greater than
2A mps
1. Check for contactor shorted to ground
2. Check for mis-wiring to the PROT terminal
Table 2 Continued
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or
services described herein or their use or applicability. Emerson Climate Technologies, Inc. reserves the right to modify the designs or specifi cations of such products at any time without
notice. Emerson Climate Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of
any Emerson Climate Technologies, Inc. product remains solely with the purchaser and end-user.
Specifications:1755/1755944-coresense_diagnostics.pdf file (27 Dec 2022) |
Accompanying Data:
Emerson Coresense Diagnostics Diagnostic Equipment PDF Bulletin (Updated: Tuesday 27th of December 2022 09:51:44 AM)
Rating: 4.6 (rated by 86 users)
Compatible devices: FilmArray Pneumonia Panel, Comfort Alert, FDS-5200, CRT511, CRP229, V007, 91648, MP720775.
Recommended Documentation:
Text of Bulletin
(Ocr-Read Version Summary of Contents, UPD: 27 December 2022)
-
4, AE8-1379 R2 Introduction CoreSense ™ Diagnostics is a breakthrough innovation for troubleshooting residential air-conditioning and heat pump systems. The CoreSense Diagnostics module is easily installed in the unit electrical panel near the compressor contactor. By using the compressor as a sensor, CoreSense Diagnostics helps the…
-
8, AE8-1379 R2 Current Sensor Opening Reset Bu on Yellow LED Red LED PROT Y (3 Wire Only) C Data Port (Not Present on 2 Wire) R (3 Wire Only) Y (2 Wire Only) Figure 4 Dimensions are in Millimeters © 2015 Emerson Climate Technologies 8
… -
5, AE8-1379 R2 Compressor Protection The CoreSense Diagnostics module utilizes proprietary algorithms to protect the compressor and system from repeated trips of system pressure controls and the compressor internal overload. The protection terminal of the module should be wired in series with the system low pressure and high pressure …
-
1, Emerson Coresense Diagnostics AE8-1379 R2 February 2015 CoreSense ™ Diagnostics for Copeland Scroll ™ Air Conditioning Compressors TABLE OF CONTENTS Section Page Introduction ……………………………………………………………………………………. 4 CoreSense Diagnostics Part Numbers ……………………………………….…
-
3, Emerson Coresense Diagnostics AE8-1379 R2 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons WARNING WARNING WARNING CAUTION ELECTRICAL SHOCK HAZARD • Disconnect and lock out power before servicing. • Discharge all capacitors before servicing. • Use compressor with grounded system only. •…
-
10, AE8-1379 R2 Table 2 CoreSense Diagnostics LED Troubleshooting Information Flash Code number corresponds to the number of LED flashes, followed by a pause and then repeated. TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation. Status Description Troubleshooting Information Solid Yellow “RUN” Module has power and oper…
-
11, AE8-1379 R2 Status Description Troubleshooting Information 1. Run capacitor has failed 2. Low line voltage (contact utility if voltage at disconnect is low) Yellow “ALERT” Flash Code 4 Locked Rotor • Check wiring connections 3. Excessive liquid refrigerant in compressor 4. Compressor bearings are seized • Measure compressor oil level 1.…
-
6, Emerson Coresense Diagnostics AE8-1379 R2 lockout the compressor, and after the issue has been resolved, it is necessary to manually reset the module in order to clear the present alert code. The primary way of clearing the code and resetting the alert is to press the reset button located on the module. Note: Pressing the reset will require a pin or mini/electronics screwdr…
-
9, AE8-1379 R2 Table 1 — Quick Reference Table Alert Code Alert Condition Lock Level Lock Indication Normal Run Solid Yellow Code1 Yellow Flash 1 Normal operation, no trip. Long run time. Compressor is on running for more than 18 hours. (Code1 is disabled in Heat Pump mode.) N/A N/A N/A N/A Code2 Compressor (pressure)…
Emerson Coresense Diagnostics Recommended Instructions:
F700, DVD6500, duet GEW9250PL0, VT-PTFMK, D-E770
-
MSW Motor Technics
MSW-DENTPULLER.L01
EXPONDO.DEDENT REPAIR LINE BOARD REFLECTORMSW-DENTPULLER.L01BEDIENUNGSANLEITUNGUser manual | Instrukcja obsługi | Návod k použití | Manuel d´utilisation | Istruzioni per l‘uso | Manual de instrucciones …
MSW-DENTPULLER.L01 11
-
Whale
PE-12-025
1.00ENG This user manual includes detailed usage instructions for PortableUltrasound Diagnostic Scanner. Please read this manual …
PE-12-025 298
-
Sealey
VS2076
Thank you for purchasing a Sealey product. Manufactured to a high standard, this product will, if used according to these instructions, and properly maintained, give you years of trouble free performance.IMPORTANT: PLEASE READ THESE INSTRUCTIONS CAREFULLY. NOTE THE SAFE OPERATIONAL REQUIREMENTS, WARNINGS & CAUTIONS. USE THE PRODUCT CORRECTLY AND WITH CARE FOR THE PURPOSE FO …
VS2076 3
-
Launch
X-431 PADII
X-431 HD Module ( )Android-basedUser ManualLAUNCH了解 诊 断盒2 Download and Install X-431 HD Module App1. Visit the LAUNCH website and download the application corresponding to the X-431 HD module;Note: If downloading using the diagnostic tool, please be sure that Wi-Fi has good or strong signals. For details on Wi-Fi connection, refer to the user ’s manual of the diagnostic too …
X-431 PADII 3
-
Toshiba
e-STUDIO2010AC
1 SYS Board Diagnosis Tool User’s Guide Version 01 10/2021 e-STUDIO2010AC/2510AC e-STUDIO2515AC/3015AC/3515AC/4515AC5015AC e-STUDIO2018A/2518A/3018A/3518A/4518A/5018A e-STUDIO5516AC/6516AC/7516AC e-STUDIO5518A/6518A/7518A/8518A …
e-STUDIO2010AC 20
-
Matco Tools
MaxLiteA
IMDMAXLITEA WARNING 1. Always perform automotive testing in a safe environment.2. Do not connect or disconnect any test equipment while the ignition is on or the engine is running.3. DO NOT attempt to operate the tool while driving the vehicle. Have second personal operate the tool. Any distraction may cause an accident.4. Before starting the engine, put the gear lever in th …
MaxLiteA 25
-
Eaton
Crouse-hinds series
Explosionsgeschützte LED-Rettungszeichenleuchte Serie: Ex-Lite, Ex-Lite V-CG-S, Ex-Lite 24 V, Ex-Lite LTExplosion protected LED exit luminaire Series: Ex-Lite, Ex-Lite V-CG-S, Ex-Lite 24 V, Ex-Lite LTPanneau de signalisation de sortie de secours lumineux antidéflagrant à diodes électroluminescentes Series: Ex-Lite, Ex-Lite V-CG-S, Ex-Lite 24 V, Ex-Lite LTCZ: &qu …
Crouse-hinds series 8
-
Protec
PRS 500 X
PROTEC GmbH & Co. KG In den Dorfwiesen 14, 71720 Oberstenfeld, Germany Telephone: +49 (0) 7062/92 55-0 E-Mail: [email protected] Version: 2.0 Issued: 2019-07-31 Subject to alterations PRS 500 X Basic diagnostic X-ray system Model/ID: 7066-9-8050L User Manual Ident. Nr. 5066-0-8002 PRS 500 X i …
PRS 500 X 38
-
Launch
Creader Professional 909
iLAUNCH Professional 909 User ManualCopyright InformationCopyright © 2019 by LAUNCH TECH CO., LTD. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, photocopying and recording or otherwise, without the prior written …
Creader Professional 909 58
Additional Information:
Popular Right Now:
Operating Impressions, Questions and Answers:
Table of Contents for Emerson Coresense Diagnostics:
-
AE8-1379 R2 Safety Instructions Copeland Scroll ™ compressors with CoreSense ™ Diagnostics technology are manufactured according to the latest U.S. and European Safety Standards. Particular emphasis has been placed on the user’s safety. Safey icons are explained below and safety instructions applicable to the products in this bulletin are grouped on Page 3. These instructions should be retained throughout the lifetime of the compressor. You are strongly adv
-
AE8-1379 R2 lockout the compressor, and after the issue has been resolved, it is necessary to manually reset the module in order to clear the present alert code. The primary way of clearing the code and resetting the alert is to press the reset button located on the module. Note: Pressing the reset will require a pin or mini/electronics screwdriver. This button must be pressed and held for a minimum of one second for the module to be reset. Pressing the reset button clears the
-
AE8-1379 R2 Table 2 CoreSense Diagnostics LED Troubleshooting Information Flash Code number corresponds to the number of LED flashes, followed by a pause and then repeated. TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation. Status Description Troubleshooting Information Solid Yellow “RUN” Module has p
-
AE8-1379 R2 Compressor Protection The CoreSense Diagnostics module utilizes proprietary algorithms to protect the compressor and system from repeated trips of system pressure controls and the compressor internal overload. The protection terminal of the module should be wired in series with the system low pressure and high pressure cutouts, as well as the compressor contactor. When the module detects a series of trips as described below, it will activate a lockout feature that opens the normally closed p
-
AE8-1379 R2 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons WARNING WARNING WARNING CAUTION ELECTRICAL SHOCK HAZARD • Disconnect and lock out power before servicing. • Discharge all capacitors before servicing. • Use compressor with grounded system only. • Molded electrical plug must be used when required.
-
AE8-1379 R2 Current Sensor Opening Reset Bu on Yellow LED Red LED PROT Y (3 Wire Only) C Data Port (Not Present on 2 Wire) R (3 Wire Only) Y (2 Wire Only) Figure 4 Dimensions are in Millimeters © 2015 Emerson Climate Technologies 8
-
AE8-1379 R2 Status Description Troubleshooting Information 1. Run capacitor has failed 2. Low line voltage (contact utility if voltage at disconnect is low) Yellow “ALERT” Flash Code 4 Locked Rotor • Check wiring connections 3. Excessive liquid refrigerant in compressor 4. Compressor bearings are seized • Measure compressor oil level 1. Evaporator blower is not running • Check blower relay coil and contacts • Check blower motor capacitor
-
AE8-1379 R2 Contactor Coil HPCO LPCO P PROT Indoor C C Unit Y Y CoreSense Module Figure 1 571-0066-00 Two-Wire Diagram HPCO LPCO T1 Defrost Board Indoor C Unit Y R ASC T2 Y C R Contactor Coil P PROT C Y R CoreSense Module Figure 2 571-0067-00 Three-Wire Diagram Contactor Coil HPCO LPCO P PROT Indoor Unit C C Y Y R R CoreSense Module Figure 3 571-0067-00 Three-Wire Diagram © 2015 Emerson Climate Technologies 7
-
AE8-1379 R2 Introduction CoreSense ™ Diagnostics is a breakthrough innovation for troubleshooting residential air-conditioning and heat pump systems. The CoreSense Diagnostics module is easily installed in the unit electrical panel near the compressor contactor. By using the compressor as a sensor, CoreSense Diagnostics helps the service technician more accurately troubleshoot system and compressor fault conditions. CoreSense Diagnostics also provides compressor and system protection through its proprieta
-
AE8-1379 R2 Table 1 — Quick Reference Table Alert Code Alert Condition Lock Level Lock Indication Normal Run Solid Yellow Code1 Yellow Flash 1 Normal operation, no trip. Long run time. Compressor is on running for more than 18 hours. (Code1 is disabled in Heat Pump mode.) N/A N/A N/A N/A Code2 Compressor (pressure) trip. Compressor runs for Red: Flash 2 Yellow Flash 2 12 sec to 15 min followed by a compressor trip 4x consecu
-
AE8-1379 R2 February 2015 CoreSense ™ Diagnostics for Copeland Scroll ™ Air Conditioning Compressors TABLE OF CONTENTS Section Page Introduction ……………………………………………………………………………………. 4 CoreSense Diagnostics Part Numbers ……………………………………………….. 4 Application Restrictions and Types …………………………………………………….. 4 Product Specifications ………
Questions, Opinions and Exploitation Impressions:
You can ask a question, express your opinion or share our experience of Emerson Coresense Diagnostics device using right now.
EMERSON
CoreSense нового поколения
Компрессоры Copeland Stream
Руководство пользователя
1. Введение
CoreSense ™ — это торговая марка компонентов компрессорной электроники, связанной с компрессорами Copeland ™. Технология CoreSense использует компрессор в качестве датчика для получения информации из компрессора, обеспечивая дополнительные функции, такие как расширенная защита двигателя, диагностика, измерение энергопотребления и обмен данными.
Благодаря активной защите, усовершенствованным алгоритмам и функциям, таким как история отказов и светодиодные индикаторы, CoreSense нового поколения (или CoreSense следующего поколения) для компрессоров марки Copeland позволяет техническим специалистам диагностировать прошлое и недавнее состояние системы, обеспечивая более быструю и точную диагностику. и меньшее время простоя. CoreSense нового поколения доступен в стандартной комплектации с 4- и 6-цилиндровыми компрессорами Stream.
АдванtagОтличительные особенности модуля CoreSense нового поколения по сравнению с другими модулями защиты — это скорость отклика и общая схема защиты. Все функции защиты работают сразу после запуска компрессора, и модуль остановит компрессор менее чем за секунду при обнаружении опасной ситуации.
Рисунок 1: Модуль CoreSense нового поколения
2. Характеристики
Модуль CoreSense нового поколения расположен в клеммной коробке и предварительно смонтирован. Все необходимые параметры мигают при изготовлении компрессора.
Источник питания для модуля управления может быть 115 В переменного тока или 230 В переменного тока.
Рисунок 2: CoreSense нового поколения внутри клеммной коробки
3. Функции CoreSense нового поколения
CoreSense нового поколения — это модульная система. Эта модульная конструкция дает клиентам возможность выбирать индивидуальные уровни защиты и / или управления. Можно расширить защиту компрессора от простых функций до высокоуровневой защиты, чтобы продлить срок службы компрессора.
Рисунок 3: Внутри view модуля CoreSense следующего поколения, с модульными платами
Таблица 2: Список основных функций
4. Предупреждения, отключения и блокировки.
CoreSense нового поколения обеспечивает 3 различных уровня защиты. Каждый из них имеет свой цвет светодиода.
- Предупреждающие сигналы: компрессор продолжит работу.
- Аварийные сигналы отключения: Компрессор выключается на определенное время с автоматическим сбросом.
Компрессор был остановлен из-за неисправности. Компрессор перезапустится, когда неисправность будет устранена и истечет заданное время выключения. - Сигнализация блокировки: компрессор выключается, необходим ручной сброс.
Компрессор был остановлен из-за неисправности. Компрессор перезапустится после устранения неисправности и выполнения ручного сброса с помощью кнопки сброса. Если установлен модуль расширения Modbus, сброс можно выполнить через Modbus.
5. Функции защиты
5.1 Защита от масла
5.1.1 Недостаточная защита от давления масла
Модуль CoreSense следующего поколения получает входные данные от датчика перепада давления масла (OPS3), расположенного в масляном насосе.
Модуль заменяет механический переключатель давления масла. Кроме того, он обеспечивает дополнительную ценность связи для предупреждения и блокировки недостаточного давления масла с помощью светодиодных мигающих кодов и / или контроллера блока управления. Общее время недостаточного давления масла для компрессора сохраняется и накапливается в памяти модуля.
Модуль выдаст предупреждение, когда перепад давления масла упадет ниже 0.95 бар в течение 4 секунд. Как только перепад давления масла упадет ниже 0.95 бар в течение 2 минут, модуль отключит компрессор и сообщит о «блокировке низкого давления масла». Перед использованием кнопки сброса необходимо выполнить устранение неполадок, чтобы понять причину сбоя. Компрессор снова включится после того, как сброс будет активирован вручную.
ПРИМЕЧАНИЕ: Эта функция не применима к компрессорам Stream CO2, которые не оснащены масляным насосом и смазываются разбрызгиванием.
Технические данные датчика реле давления масла OPS3:
- Допустимая температура окружающей среды: от -30 ° C до 90 ° C
- Класс защиты: IP45
Рисунок 4: Датчик давления масла OPS3 и электронная часть (при поставке подключены)
5.1.2 Защита уровня масла (опция)
Защита масла достигается с помощью часового устройства OW4 / 5 TraxOil и устройства контроля уровня OM3 / 4/5 TraxOil.
TraxOil использует датчик Холла для измерения уровня масла. Магнитный поплавок (не подверженный вспениванию масла) меняет свое положение в зависимости от уровня масла. Датчик Холла преобразует изменения магнитного поля в эквивалентный сигнал, который используется встроенным электронным контроллером для отслеживания и отображения фактического уровня масла с помощью светодиодов.
Рисунок 5: Устройство контроля масла TraxOil OW5 Oil
Рисунок 6: Зоны контроля уровня в смотровом стекле
Таблица 3: Легенда кода светодиода
Устройство контроля уровня масла не входит в стандартный комплект поставки компрессора; его нужно будет подключить к модулю CoreSense следующего поколения через клеммы 15 и 16.
В приложении модуля CoreSense нового поколения можно выбрать два варианта подключения:
- Закрыто, когда ОК:
o Настройка по умолчанию после активации
o Подключите синий (BU) и черный (BK) провода - Открыть, когда ОК:
o Подключите коричневый (BN) и черный (BK) провода
Пользователь имеет возможность выбирать между предупреждением или аварийным состоянием, если уровень масла ниже 25%.
5.2 Защита двигателя от перегрева
Используя термисторы с положительным температурным коэффициентом (PTC) на моделях компрессоров 4M * и 6M * Stream, CoreSense нового поколения обеспечивает защиту двигателя от перегрева.
Две цепи из трех термисторов, каждая из которых соединена последовательно, встроены в обмотки двигателя таким образом, чтобы температура термисторов могла изменяться с небольшой инерцией.
5.2.1 Защита от статического перегрева
Модуль CoreSense следующего поколения отключит компрессор, если обмотки двигателя станут слишком горячими.
Стандартное состояние:
- Общее сопротивление цепей термисторов при 25 ° C ≤ 1.8 кОм
Состояние тревоги:
- Состояние срабатывания: сопротивление PTC> 4.5 кОм;
- Условие сброса: сопротивление PTC <2.75 кОм; Задержка 5 мин.
Отключение из-за неисправности датчика:
- Короткое замыкание: сопротивление PTC <20 Ом;
- Обрыв цепи: сопротивление PTC> 20 кОм.
5.2.2 Динамическая защита от перегрева
Если температура обмотки двигателя повысится за короткий период (> 240 Ом / 400 мс), модуль отключит компрессор. Компрессор перезапустится через 5 минут.
5.3 Защита от высокой температуры нагнетания
Защита по температуре нагнетания обеспечивается датчиком PT1000 в головке блока цилиндров компрессора.
Датчик предварительно установлен на заводе и подключен к модулю CoreSense нового поколения. Модуль защитит компрессор от условий высокой температуры нагнетания. Если датчик температуры определяет температуру нагнетания выше 154 ° C, модуль отключит компрессор до тех пор, пока температура не снизится до приемлемого уровня (на 20 K ниже заданного значения).
Конфигурируемый диапазон настроек отключения составляет от 108 ° C до 154 ° C, а значение сброса составляет от 83 ° C до 134 ° C.
- Значение срабатывания ≥ 154 ° C на 0.5 сек.
- Аварийный сигнал отключения: автоматический сброс через 2 минуты; температура нагнетания <130 ° C
Технические данные датчика PT1000:
- Диапазон измерения: от -40 ° C до 155 ° C, 170 ° C в течение 30 минут макс.
- Момент затяжки: 15 Нм
- Класс защиты: IP65
Рис.7: Датчик температуры нагнетания
5.4 Токовая защита
Датчик тока находится в клеммной коробке.
Один провод питания (2 от одной фазы в случае частичной обмотки) проходит через этот датчик — см. T1 в главе 16.2 Электрические схемы.
Следует уважать направление отведений.
Рисунок 8: Датчик тока
5.4.1 Защита от заторможенного ротора
Если через 2.5 секунды после запуска компрессора ток составляет 150% от значения MOC, срабатывает аварийный сигнал и компрессор отключается. Аварийный сигнал сбрасывается через 5 минут.
После 10 отключений активируется блокировка, и модуль CoreSense нового поколения необходимо сбросить вручную с помощью кнопки сброса (без автоматического сброса).
5.4.2 Защита MOC
Значение MOC компрессора сохраняется в модуле CoreSense нового поколения. Компрессор отключается, если измеренный ток превышает значение MOC более 2 секунд.
Эта функция запускается через 4.5 секунды после запуска компрессора и автоматически сбрасывается через 5 минут после отключения.
5.4.3 Защита от превышения частоты коммутации
Количество запусков компрессора отслеживается в течение определенного периода времени. Если компрессор достигает максимального количества запусков за время короче заданного, срабатывает аварийный сигнал.
- По умолчанию установлено 10 запусков за 1 час и создание поездки.
- Время сброса рассчитывается как разница между заданным периодом времени (1 час) и фактическим временем, которое потребовалось для выполнения определенного максимального количества запусков (10).
- Exampль:
1. 10 запусков произошло за 35 минут.
2. будильник срабатывает через 35 минут
3. автоматический сброс будет выполнен через 25 минут.
Можно выбрать предупреждение или отключение компрессора.
5.4.4 Обнаружение MOC при первом запуске
Большинство компрессоров имеют два набора номинального объемаtages и частоты:
- Значение 50 Гц или 60 Гц для двигателей с частичной обмоткой (AW…)
- другой объемtages для двигателей с Δ / Y-пуском (EW…)
При первом запуске и при каждом сбросе питания модуль CoreSense нового поколения автоматически определяет источник питания компрессора (объемtage и частота) и автоматически выберет соответствующие MOC и undervol.tagэ / овервольtage уставки защиты.
Если измеренный объемtage и / или частота отличается от указанной на паспортной табличке, модуль выдаст предупреждение.
Для бывшихampТо есть, если двигатель AWM / D (400 В / 50 Гц или 460 В / 60 Гц) подключен к линии питания 230 В, зеленый светодиод будет мигать.
5.5 Фаза / об.tagэлектронный мониторинг
Есть 6 томовtagЦепи датчиков для измерения трех фаз. Благодаря 3 датчикам можно также защитить двигатели с частичной обмоткой.
Состояние каждой фазы в прямом включении и частичной обмотке контролируется на пониженное напряжение.tagе, оверволtagе и фазовая асимметрия.
5.5.1 Защита от обрыва фазы / Защита от обрыва фазы
Сравнивается объемtagе каждой фазы и их среднее значение. Если после запуска компрессора отсутствует какая-либо из трех фаз питания, значит, существует однофазное состояние.
Любой объемtagДисбаланс выше 60% является условием отключения по обрыву фазы.
Аварийные условия: возникает в случае отсутствия фазы.
- Время поездки: 5 минут с автоматическим сбросом.
Пропущенную фазу можно обнаружить при запуске и во время работы компрессора.
5.5.2 Пониженная громкостьtagэлектронная защита
Происходит, когда объем компрессораtage ниже номинального напряжения питанияtage.
Низкая громкостьtage условие предупреждения: объемtage <85% от номинальной линейной громкостиtage на 2 секунды.
Низкая громкостьtagе условия поездки: объемtage <75% от номинальной линейной громкостиtage 2 секунды.
- Время в пути: 2 минут.
5.5.3 Оверволtagэлектронная защита
Происходит, когда объем компрессораtage выше номинального напряжения питанияtage.
Высокий объемtage условие предупреждения: объемtage> 115% от номинальной линейной громкостиtage на 2 секунды.
Высокий объемtagе условия поездки: объемtage> 125% от номинальной линейной громкостиtage на 2 секунды.
- Время в пути: 2 минут.
5.5.4 томаtage защита от дисбаланса
Эта функция предназначена для защиты компрессора от перенапряжения.tagНесбалансированность, которая может привести к перегреву двигателя.
Настраиваемая настройка (по умолчанию = 5%) для об.tagДисбаланс используется для определения рабочего предела компрессора. ОбъемtagПараметр дисбаланса можно настроить в диапазоне от 2 до 8% с помощью приложения модуля CoreSense нового поколения.
Условия срабатывания сигнализации:
- Предупреждение: когда объемtage дисбаланс> 3% (настраивается).
- Поездка: когда томtage дисбаланс> 5% (настраивается).
- Сброс: автоматический сброс через 5 мин; объемtagе дисбаланс <5%.
5.5.5 Защита сварного контактора
Эта защита проверяет 3 независимых сигнала работы:
- обtagе доступно на всех терминалах;
- ток обнаружен на 1 фазе;
- сигнал запроса — сигнал от контроллера к контактору.
Если три сигнала запуска не идентичны, модуль CoreSense следующего поколения сгенерирует предупреждение.
По умолчанию защита отключена. Если модуль CoreSense следующего поколения подключен к главному контроллеру (клеммы 17 и 18) и обнаружен сигнал запроса, функция активируется.
Пользователь имеет возможность выбирать между предупреждением или аварийным состоянием. После отключения компрессор перезапустится через 2 минуты. По умолчанию установлено предупреждение.
После 10 отключений активируется блокировка, и модуль необходимо сбросить вручную с помощью кнопки сброса (без автоматического сброса).
5.5.6 Защита части обмотки
Два кабеля питания обмотки должны проходить через датчик тока в одном направлении.
При первом запуске или при перезагрузке модуля CoreSense нового поколенияtagе измеряется на обеих обмотках.
- Если объемtages идентичны:
1. компрессор включен по полной обмотке;
2. защита отключена. - Если объемtages разные, объемtages сравниваются снова через 1 секунду:
1. если объемtagе на второй обмотке такое же, как на первой обмотке:
— компрессор включен по частям обмотки;
— защита включена;
2. если объемtage на второй обмотке не то же самое, что на первой обмотке, вторая обмотка подключена неправильно и компрессор отключается.
Пользователь имеет возможность выбирать между предупреждением или аварийным состоянием. После отключения компрессор перезапустится через 2 минуты. Настройка по умолчанию — отключение.
6. Режим частотно-регулируемого привода.
При работе с частотно-регулируемым приводом все электрические аварийные сигналы отключены.
Режим частотно-регулируемого привода (VFD) можно активировать с помощью следующей процедуры:
- отключите модуль CoreSense нового поколения от источника питания;
- отсоедините клеммы 9 и 10 датчика тока;
- подключить перемычку между выводами датчика тока на модуле (короткое замыкание);
- подать питание на модуль:
1. появится предупреждение о коротком замыкании (мигающий оранжевый светодиод) датчика тока; - нажмите и удерживайте кнопку сброса более 10 секунд (может быть выполнено только в течение первых 5 минут после сброса питания):
1. зеленый / красный код быстрого мигания светодиода;
2. через 10 секунд мигание становится медленным; - после отпускания кнопки сброса активируется режим VFD.
Если датчик тока подключен снова, режим VFD можно активировать, нажав кнопку сброса более 10 секунд.
7. Аварийный режим.
Аварийный режим можно использовать в исключительных случаях для обхода расширенной защиты и работы только с базовой защитой (давление масла и температура двигателя).
Чтобы активировать аварийный режим:
- отсоедините датчик температуры линии нагнетания от модуля CoreSense следующего поколения, клеммы 7 и 8;
- подключить перемычку между выводами датчика температуры нагнетательной линии (короткое замыкание);
- нажмите и удерживайте кнопку сброса более 10 секунд.
8. Светодиоды на крышке клеммной коробки.
Светодиодные индикаторы состояния трех цветов (зеленый, оранжевый и красный) видны в верхней части Т-образного блока.
Рисунок 9: Клеммная коробка модуля CoreSense нового поколения
8.1 Коды состояния компрессора
- Горит зеленым: индикация нормальной работы. В компрессоре нет неисправностей или проблем.
- Мигающий зеленый: индикация состояния предупреждения. Компрессор продолжает работать.
- Горит оранжевым: индикация того, что компрессор находится в аварийном режиме.
- Мигающий оранжевый: индикация того, что компрессор отключился и автоматически перезапустится через определенное время (автоматический сброс).
- Горит красным: означает, что CoreSense находится в режиме параметризации.
- Мигающий красный: индикация того, что компрессор заблокирован. Для перезапуска необходим ручной сброс.
8.2 Сигналы неисправности, отображаемые светодиодами
Аварийные сигналы отображаются с помощью цветных светодиодов и мигающих последовательностей. Каждая последовательность вспышек прерывается 2-секундной паузой.
Таблица 4: Пояснения к мигающим сигналам X = отключено в стандартной поставке
9. История аварийных сигналов.
20 последних аварийных сигналов хранятся в памяти модуля и могут быть загружены с помощью приложения модуля CoreSense нового поколения.
10. Кнопка сброса
После блокировки компрессора необходимо нажать кнопку сброса. Кроме того, его можно использовать для немедленного сброса аварийного отключения (нет времени ожидания компрессора для перезапуска).
- Если условие отключения сброшено, все счетчики отключения сбрасываются на ноль, компрессор может перезапуститься.
- Если условие отключения не устранено, сигнал сброса игнорируется.
11. Управление подогревателем картера.
Модуль CoreSense следующего поколения напрямую управляет нагревателем картера, поэтому только нагреватель картера с тем же источником питания, что и модуль CoreSense (115 В переменного тока или 230 В переменного тока), может быть применен и подключен к клеммам 3 и 4.
Рисунок 10: Схема подключения — Подключения нагревателя картера
12. Измерение энергопотребления.
Мощность рассчитывается по измеренному объемуtagе, ток и коэффициент мощности.
Точность каждого измерения:
- обtagд ± 5%
- ток ± 5%
- коэффициент мощности ± 10%
Потребляемая мощность в кВтч указана в приложении модуля CoreSense нового поколения.
13. Порт данных для связи с приложением модуля CoreSense нового поколения.
Порт данных может использоваться для связи с приложением модуля CoreSense нового поколения для параметрирования или загрузки данных (история выполнения и аварийные сигналы).
Рисунок 11: Порт данных на модуле CoreSense нового поколения
13.1 Связь
Есть две возможности для связи через порт данных, USB или шлюз Bluetooth.
USB-шлюз можно использовать с любым компьютером USB типа A. Адаптеры USB типа A на USB micro-B и USB-C поставляются для подключения к устройствам Android. Подключение к устройствам iOS невозможно через шлюз USB.
Шлюз Bluetooth можно использовать с любым устройством с адаптером Bluetooth. Это также единственная возможность подключения для устройств iOS.
14. Модуль Modbus (опционально)
Модуль CoreSense нового поколения может быть оснащен модулем расширения Modbus для связи через RS485.
Данные диагностики могут быть считаны в системные контроллеры с использованием стандартного протокола Modbus RTU.
ПРИМЕЧАНИЕ: Более подробную информацию об интерфейсе Modbus можно найти в специальной технической информации TI_Stream_NGCS_02 «Next Generation CoreSense ™ — Описание интерфейса Modbus».
15. Приложение модуля CoreSense нового поколения.
Приложение можно загрузить из Google Play Store для Android, Microsoft Store для Windows или Apple Store для устройств iOS. Он обеспечивает доступ к памяти / счетчику ошибок, поэтому можно оценить текущее состояние системы и восстановить рабочие данные.viewредактор
Это приложение также позволяет анализировать измерения, выполняемые различными датчиками модуля CoreSense следующего поколения, и предоставлять информацию о работе компрессора, такую как:
- время работы в нормальных условиях / условиях предупреждения / отключения;
- количество пусков и остановок;
- потребляемая мощность;
- время работы компрессора;
- счетчик моточасов подогревателя картера.
Приложение модуля CoreSense нового поколения можно подключить к CoreSense следующего поколения с помощью шлюза DP-USB (не применяется для устройств Apple) или шлюза Bluetooth.
16. Электрические соединения
16.1 Основные подключения
Модуль CoreSense следующего поколения изначально поставляется с предварительно подключенными базовыми модулями.
Рисунок 15: Базовые средства защиты CoreSense нового поколения
16.2 Схемы подключения
ВАЖНАЯ ИНФОРМАЦИЯ
Для моделей компрессоров Stream CO2 малых и средних размеров (от 4MTL-05 до 4MTL-30 и от 4MSL-03 до 4MSL-15) необходимо учитывать синие позиции 1U, 2V, 3W, 7Z, 8X, 9Y на схемах ниже. Расположение клемм на всех остальных моделях компрессоров Stream соответствует черным позициям. Заводская поставка правильная, НЕ меняйте местами соединения.
Легенда
Рисунок 16: Схема подключения двигателей с частичной обмоткой (AW…)
Рисунок 17: Схема подключения двигателей звезда / треугольник (EW…)
Рисунок 18: Схема подключения (2-я часть) для двигателей с частичной обмоткой и двигателями со звездой / треугольником (AW… и EW…)
Документы / Ресурсы
Рекомендации
PENTAX K-3 Mark III User Manual — Руководства +