Alert Code

Normal Run

Normal operation, no trip.

Solid Yellow

Code1

Long run time. Compressor is on running for more

than 18 hours. (Code1 is disabled in Heat Pump

Yellow Flash 1

mode.)

Code2

Compressor (pressure) trip. Compressor runs for

12 sec to 15 min followed by a compressor trip

Yellow Flash 2

condition lasting longer than 7 min.

Code3

Pressure switch cycling. Compressor runs for 12

sec to 15 min followed by a compressor trip lasting

Yellow Flash 3

between 35 sec to 7 min.

Code4

Locked rotor. Compressor trips within a compressor

run time of 12 sec and does not start within 35 sec.

Yellow Flash 4

Code5

Compressor (moderate run) trip. Compressor runs

for 15 min to 18 hrs followed by a compressor trip

Yellow Flash 5

lasting longer than 7 min.

Code9

The current to the PROT terminal is greater than 2A

Red Flash 9

Trip

Demand is present, but compressor is not running

Solid Red

© 2015 Emerson Climate Technologies

Table 1 — Quick Reference Table

Alert Condition

9

AE8-1379 R2

Lock

Lock Level

Indication

N/A

N/A

Red: Flash 2

4x consecutive

Yellow: Off

4x consecutive

Red: Flash 3

or 10x total

Yellow: Off

Red: Flash 4

10x consecutive

Yellow: Off

4x consecutive

Red: Flash 5

or 10x total

Yellow: Off

Red: Flash 9

Current >2A

for 40ms

Yellow: Off

N/A

N/A

N/A

N/A

1

© 2011 Emerson Climate Technologies

Printed in the U.S.A.

AE8-1385

Application Engineering

BULLETIN

Application Engineering

BULLETIN

Safety

Safety Instructions ………………………………………………………..2

Safety Icon Explanation ……………………………………………….. 2

Instructions Pertaining to Risk of Electrical Shock, Fire,

or Injury to Persons ………………………………………………………3

Safety Statements ………………………………………………………..3

Introduction

Overview …………………………………………………………………….4

Application Restrictions and Types ………………………………… 4

Product Speci cations …………………………………………………..4

Installation

Mounting …………………………………………………………………….4

Terminal Description ……………………………………………………..4

Operation

Compressor Protection …………………………………………………4

Module LED Description ………………………………………………. 5

Module Operation/Code Description ……………………………….5

Resetting Alert Codes ………………………………………………….. 6

Service

Module History Download …………………………………………….. 6

Warranty Information ……………………………………………………. 6

Support ………………………………………………………………………. 6

Figures and Tables

Wires Pulled Through Module ……………………………………….. 6

Module Dimensions in Millimeters ………………………………….. 7

Terminal Locations ……………………………………………………….7

Wiring Diagram …………………………………………………………… 8

Flash Code Description ………………………………………………… 9

LED Troubleshooting Information ……………………………….. 10-12

TABLE OF CONTENTS

AE8-1385

CoreSense Diagnostics

for Copeland Scroll® UltraTech® Air Conditioning Compressors

October 2011

2

© 2011 Emerson Climate Technologies

Printed in the U.S.A.

AE8-1385

Application Engineering

BULLETIN

Safety Instructions

Copeland Scroll® compressors with CoreSense Diagnostics technology are manufactured according to the latest

U.S. and European Safety Standards. Particular emphasis has been placed on the user’s safety. Safey icons are

explained below and safety instructions applicable to the products in this bulletin are grouped on Page 3. These

instructions should be retained throughout the lifetime of the compressor. You are strongly advised to follow

these safety instructions.

Safety Icon Explanation

DANGER indicates a hazardous situation which, if not avoided, will result

in death or serious injury.

WARNING indicates a hazardous situation which, if not avoided, could

result in death or serious injury.

CAUTION, used with the safety alert symbol, indicates a hazardous

situation which, if not avoided, could result in minor or moderate injury.

NOTICE is used to address practices not related to personal injury.

CAUTION, without the safety alert symbol, is used to address practices

not related to personal injury.

DANGER

WARNING

CAUTION

NOTICE

CAUTION

3

© 2011 Emerson Climate Technologies

Printed in the U.S.A.

AE8-1385

Application Engineering

BULLETIN

ELECTRICAL SHOCK HAZARD

• Disconnect and lock out power before servicing.

• Discharge all capacitors before servicing.

• Use compressor with grounded system only.

• Molded electrical plug must be used when required.

• Refer to original equipment wiring diagrams.

Failure to follow these warnings could result in serious personal injury.

PRESSURIZED SYSTEM HAZARD

• System contains refrigerant and oil under pressure.

• Remove refrigerant from both the high and low compressor side before

removing compressor.

• Never install a system and leave it unattended when it has no charge,

a holding charge, or with the service valves closed without electrically

locking out the system.

• Use only approved refrigerants and refrigeration oils.

• Personal safety equipment must be used.

• Failure to follow these warnings could result in serious personal injury.

BURN HAZARD

• Do not touch the compressor until it has cooled down.

• Ensure that materials and wiring do not touch high temperature areas of

the compressor.

• Use caution when brazing system commponents.

• Personal safety equipment must be used.

• Failure to follow these warnings could result in serious personal injury or

property damage.

COMPRESSOR HANDLING

• Use the appropriate lifting devices to move compressors.

• Personal safety equipment must be used.

• Failure to follow these warnings could result in personal injury or

property damage.

Safety Statements

• Refrigerant compressors must be employed only for their intended use.

install, commission and maintain this equipment.

• All valid standards and codes for installing, servicing, and maintaining electrical and

refrigeration equipment must be observed.

Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons

WARNING

WARNING

WARNING

CAUTION

4

© 2011 Emerson Climate Technologies

Printed in the U.S.A.

AE8-1385

Application Engineering

BULLETIN

INTRODUCTION

Overview

CoreSense Diagnostics is a breakthrough innovation

for troubleshooting residential air conditioning and heat

pump systems. The CoreSense Diagnostics module

is easily installed in the unit electrical panel near the

compressor contactor. By using the compressor as

a sensor, CoreSense Diagnostics helps the service

technician more accurately troubleshoot system and

compressor fault conditions.

CoreSense Diagnostics also provides compressor

and system protection through its proprietary lockout

feature. Depending on the severity and frequency of

the fault that caused the trip condition, the CoreSense

Diagnostics module can lockout the compressor

contactor to prevent damage to the compressor and

system components. Less severe fault conditions

resulting in an occasional trip will not result in a lockout

condition.

Flashing LEDs communicate ALERT and LOCK codes

to the service technician.

Application Restrictions and Types

The CoreSense Diagnostics (571-0072-00) module

is designed and quali ed for use with ZPS*K5 single-

phase Copeland Scroll® UltraTech compressors.

Product Speci cations

Operating Temp: — 40° to 150°F (- 40° to 65°C)

Storage Temp: — 40° to 175°F (- 40° to 80°C)

Supply Voltage: 18 to 28VAC , 48 to 62Hz

Module Current Sensing Range: 2 to 30A

Maximum Power Consumption: 2.5 VA (Excluding

solenoid load)

INSTALLATION

Mounting

Four #8 or #10 self tapping or sheet metal screws are

required for installation of the module. The maximum

mounting screw torque is 20 in.lbs. Locate the

module near the compressor contactor (wire routing

for compressor run, common, and start wires will be

easier in this position). The module can be mounted

in any orientation and LEDs should be visible for ease

of service.

The compressor’s run (R), common (C), and start (S)

wires are routed through the holes in the CoreSense

module marked “R”,”C”, and “S”. See Figure 1.

Terminal Description

The terminals for the CoreSense Diagnostics module

are ¼” spade terminals.

• COMMON (C)

The 24 volt common terminal for module power.

• DEMAND (Y)

The demand terminal requires a 24VAC signal

measured with respect to the COMMON (C)

terminal when there is a call for heating or

cooling. A signal above 6VAC indicates the

thermostat wants the compressor to be on, while

0-6VAC signal indicates the thermostat wants

the compressor to be off.

• SECOND STAGE DEMAND (Y2)

The demand (Y) and second stage demand

(Y2) terminals require a 24VAC signal measured

with respect to the COMMON (C) terminal when

there is a call for heating or cooling. A signal

above 10VAC indicates the thermostat wants the

Ultratech solenoid to be energized, while 0-10VAC

signal indicates the thermostat wants the Ultratech

solenoid to be deenergized.

• PROTECTION (PROT)

The protection terminal is internally connected

to the COMMON terminal through a solid state

switch.

• POWER (R)

The module requires a constant 24VAC supply

power to this terminal. The module must receive

an independent power supply in order to operate

properly. See Figure 4.

• Thermostat Communication (L)

Provides a 24V signal to an indoor thermostat

indicating the number of ALERT ashes displayed

on the module. (Reference thermostat manual for

available capability)

• Solenoid (DC SOL)

Provides a connection to the Copeland Scroll

UltraTech second stage compressor solenoid. This

solenoid is internal to the compressor, and has

a voltage range of 18 to 28VDC. Please refer to

bulletin AE-1311 for information on the Copeland

Scroll® UltraTech® compressor.

5

© 2011 Emerson Climate Technologies

Printed in the U.S.A.

AE8-1385

Application Engineering

BULLETIN

OPERATION

Compressor Protection

The CoreSense Diagnostics module utilizes proprietary

algorithms to protect the compressor and system from

repeated trips of system pressure controls and the

compressor internal overload. The protection terminal

of the module should be wired in series with the system

low pressure and high pressure cutouts, as well as

the compressor contactor. When the module detects

a series of trips as described below, it will activate a

lockout feature that opens the solid state switch in the

module, thereby cutting power to the contactor and de-

energizing the compressor.

Module LED Description

POWER LED (Green): indicates the module is

powered with 18 to 28 volts.

ALERT LED (Yellow): communicates an abnormal

system condition through a unique ash code. The

ALERT LED will ash a number of times consecutively,

pause and then repeat the process. The number of

consecutive ashes, de ned as the Flash Code,

correlates to a particular abnormal condition. Detailed

descriptions of speci c ALERT Flash Codes are

shown in Table 1.

TRIP/LOCK LED (Red): indicates either a TRIP or

LOCK condition.

TRIP: is indicated by a solid illumination of the

LED. This means the compressor is not running

and demand is present at the module.

LOCK: is indicated by a ashing LED correlating to

a LOCK condition in which the module will prevent

the compressor from starting.

Module Operation/Code Description

Code 1 – Long Run Time

The module will ash yellow one time when the

compressor operates for longer than 18 continuous

hours. This is an alert code only, and the module will

not lockout the compressor for this condition. This

code is inactive for heat-pumps.

Code 2 – Compressor (Pressure) Trips

The module will ash yellow two times when the

compressor operates from 12 seconds to 15 minutes

followed by a trip condition lasting longer than 7

minutes. When four consecutive or ten total Code

2 events are recorded, the module will lockout the

compressor and ash red two times.

Code 3 – Pressure Switch Cycling

The module will ash yellow three times when the

compressor operates from 12 seconds to 15 minutes

followed by a trip condition lasting between 35

seconds to 7 minutes. When four consecutive or ten

total Code 3 events are recorded, the module will

lockout the compressor and ash red three times.

Code 4 – Locked Rotor Trip

The module will ash yellow four times when the

compressor trips within 12 seconds of operation and

does not reset and start within 35 seconds. When ten

consecutive Code 4 events are recorded the module

will lockout the compressor and ash red four times.

Code 5 – Compressor (Moderate Run) Trip

The module will ash yellow ve times when the

compressor has operated between 15 minutes and

18 hours, followed by a compressor trip lasting longer

than 7 minutes. When four consecutive or ten total

Code 5 events are recorded, the module will lockout

the compressor and ash red ve times.

Code 6 – Open Start Circuit

The module will lockout the compressor and ash

red six times if the module detects a demand signal

in the “Y” terminal and current in the “R” winding of

the compressor, but no current is detected in the “S”

winding of the compressor for 2 seconds.

Code 7 – Open Run Circuit

The module will lockout the compressor and ash red

seven times if the module detects a demand signal

in the “Y” terminal and current in the “S” winding of

the compressor, but no current is detected in the “R”

winding of the compressor for 2 seconds.

Code 8 – Welded Contactor

The module will ash yellow eight times if it has

detected line currents in the “S” and “R” windings and

demand is absent for 15 seconds.

Code 9 – Low Voltage

The module will ash nine times if the module supply

voltage drops below 17VAC for 2 seconds. The

module will prevent the compressor from starting until

adequate voltage is established.

Code 10 – Over-Current Protection

When the current at the PROT terminal is greater than

2A for 40ms, the module will ash a Code 10. The red

LED will ash 10 times with the yellow LED remaining

6

© 2011 Emerson Climate Technologies

Printed in the U.S.A.

AE8-1385

Application Engineering

BULLETIN

off. This event will cause a lockout of the compressor

and indicates that the module is mis-wired or the

contactor coil is shorted to ground.

NOTICE

Code 10 is not speci ed on the module label.

Resetting Alert Codes

When the CoreSense Diagnostics module has detected

a series of adverse conditions that have caused it to

lockout the compressor, and after the issue has been

resolved, it is necessary to manually reset the module

in order to clear the present alert code.

The primary way of clearing the code and resetting

the ALERT or TRIP/LOCK is to cycle the power to the

module by disengaging the COMMON (C) Terminal.

This will not clear the seven day operating history

contained in the module memory. It will only clear the

present ALERT or TRIP/LOCK and allow for normal

operation.

SERVICE

WARNING

Always disconnect and lockout the power supply

before beginning electrical troubleshooting.

Module History Download

The CoreSense Diagnostics module is capable of

communicating with a personal computer, tablet, or

laptop, via Emerson Climate Technologies computer

Figure 1

Wires Pulled Through Module

software interface and USB connection, in order to

download and store fault history and module operation

time. This information can be used to help diagnose

and review data from troubled systems in the eld. For

more information, please contact your Emerson Climate

Application Engineer.

Warranty Information

Emerson Climate Technologies, Inc. warrants its

diagnostic module to be free from defects in materials

and workmanship under normal use for a period of one

year from the date of purchase or twenty months from

manufacture, whichever comes rst. During this period,

Emerson Climate Technologies, Inc. will replace any

defective diagnostic module without charge.

For more information on product warranty please visit

www.EmersonClimate.com

Support

For more information visit www.EmersonClimate.com,

or contact Emerson Climate Technologies, Inc. at 1-888-

EMR-9950.

7

© 2011 Emerson Climate Technologies

Printed in the U.S.A.

AE8-1385

Application Engineering

BULLETIN

ALERT

TRIP / LOCK

POWER

1 Long Run Time

2 Compressor (Pressure) Trip

3 Pressure Switch Cycling

4 Locked Rotor

5 Compressor (Mod Run) Trip

6 Open Start Circuit

7 Open Run Circuit

8 Welded Contactor

9 Low Voltage

DC SOL operating range: 18-28VDC

Compressor second stage is

energized when Y & Y2 are 24VAC

PROT breaks 24VAC common

leg of compressor contactor coil

Reset codes and PROT lockout

by removing 24VAC to module

Flash Event

Two Stage Control

Active Protection

C

S

R

47

37

62 112

67

Figure 2 – Module Dimensions in Millimeters

Y2

Y

Data Port

L

R

C

PROT

Solenoid

For Use With

Copeland Scroll

UltraTech

Compressors

P/N: 543-XXXX-XX

065312345

Patent: 6,615,594

Use With Class 2

Circuits Only

Supply 24VAC

50/60Hz

Power 1.5VA

Figure 3 – Terminal Locations

8

© 2011 Emerson Climate Technologies

Printed in the U.S.A.

AE8-1385

Application Engineering

BULLETIN

2-Stage

Thermostat

Indoor

Unit

Outdoor

Unit

C

R

Y1

Y2

C

R

L

Y

Y2

L

DC

Solenoid Solenoid

CoreSense

High/Low

Pressure Switch

CC

Compressor

Contactor

C

R

Y1

Y2

L

C

R

Y1

Y2

L

Prot

Figure 4

Wiring Diagram

9

© 2011 Emerson Climate Technologies

Printed in the U.S.A.

AE8-1385

Application Engineering

BULLETIN

Alert Code Alert Condition Lockout Level Lockout

Indication

Normal Run

Solid Green Normal operation, no trip. N/A N/A

Code1

Yellow Flash 1

Long run time. Compressor is running for more than

18 hours at full load. (Code1 is disabled in Heat Pump

mode.)

N/A N/A

Code2

Yellow Flash 2

Compressor Pressure trip. Compressor runs for 12sec

to 15min followed by a compressor trip condition lasting

longer than 7min.

4x consecutive,

10x total Red: Flash 2

Code 3

Yellow Flash 3

Pressure switch cycling. Compressor runs for 12sec to

15min followed by a compressor trip lasting between

35sec to 7min.

4x consecutive,

10 total Red: Flash 3

Code4

Yellow Flash 4

Locked rotor. Compressor trips within a compressor run

time of 12sec and does not start within 35sec. 10x consecutive Red: Flash 4

Code5

Yellow Flash 5

Compressor moderate run trip. Compressor runs for

15min to 18hrs followed by a compressor trip lasting

longer than 7min.

4x consecutive,

10x total Red: Flash 5

Code6

Red Flash 6

Open start circuit. Module has detected Y or Y1, and

current in the R winding of the compressor and no

current in the S winding of the compressor for 2 seconds.

1 occurrence Red: Flash 6

Code7

Red Flash 7

Open run circuit. Module has detected Y or Y1, and

current in the S winding of the compressor and no current

in the R winding of the compressor for 2 seconds.

1 occurrence Red: Flash 7

Code8

Yellow Flash 8

Welded Contactor. Module has detected line currents

in R and S windings, and Y or Y1 is at 0 VAC for 15

seconds.

N/A N/A

Code9

Yellow Flash 9

Low Voltage. Module has detected a 24 VAC supply

voltage below 17 VAC +/- 1 VAC for 2 seconds

N/A N/A

Code10

Red Flash 10

Over Current Protection. PROT terminal has above a 2A

input for more than 40 milliseconds. 1 occurrence Red: Flash 10

Table 1 – Flash Code Description

10

© 2011 Emerson Climate Technologies

Printed in the U.S.A.

AE8-1385

Application Engineering

BULLETIN

Status Description Troubleshooting Information

Solid Green “RUN” Module has power and

operating normally Supply voltage is present at module terminals

Solid Red “TRIP”

Thermostat demand signal Y is

present, but the compressor is

not running

1. Compressor protector is open

Check for high head pressure

Check compressor supply voltage

2. Outdoor unit power disconnect is open

3. Compressor circuit breaker or fuse(s) is open

4. Broken wire or connector is not making contact

5. High pressure switch open if present in system

6. Compressor contactor has failed open

“ALERT” Flash Codes

Yellow “ALERT”

Flash Code 1

Long Run Time

Low Refrigerant Charge

Compressor is running extremely

long run cycles

1. Low refrigerant charge

2. Evaporator blower is not running

Check blower relay coil and contacts

Check blower motor capacitor

Check blower motor for failure or blockage

Check evaporator blower wiring and connectors

Check indoor blower control board

Check thermostat wiring for open circuit

3. Evaporator coil is frozen

Check for low suction pressure

Check for excessively low thermostat setting

Check evaporator air ow (coil blockages or return air lter)

Check ductwork or registers for blockage

4. Faulty metering device

Check TXV bulb installation (size, location and contact)

• Check if TXV/ xed ori ce is stuck closed or defective

5. Liquid line restriction ( lter drier blocked if present in system)

6. Thermostat is malfunctioning

Check thermostat sub-base or wiring for short circuit

Check thermostat installation (location, level)

Yellow “ALERT”

Flash Code 2

Compressor (Pressure) Trip

High Refrigerant Charge

Discharge pressure out of limits

or compressor overloaded

1. Condenser fan is not running

Check fan capacitor

Check fan wiring and connectors

Check fan motor for failure or blockage

2. High head pressure

Check high pressure switch if present in system

Check if system is overcharged with refrigerant

Check for non-condensable in system

3. Condenser coil poor air circulation (dirty, blocked, damaged)

4. Return air duct has substantial leakage

Yellow “ALERT”

Flash Code 3

Pressure Switch Cycling

Compressor is running only

brie y due to pressure switch

cycling

1. Time delay relay or control board defective

2. If high pressure switch present go to Flash Code 2 information

Table 2 – CoreSense Diagnostics LED Troubleshooting Information

Flash Code number corresponds to the number of LED ashes, followed by a pause and then repeated.

TRIP and ALERT LEDs ashing at same time means control circuit voltage is too low for operation (brown-out conditions).

11

© 2011 Emerson Climate Technologies

Printed in the U.S.A.

AE8-1385

Application Engineering

BULLETIN

Yellow “ALERT”

Flash Code 4 Locked Rotor

1. Run capacitor has failed

2. Low line voltage (contact utility if voltage at disconnect is low)

Check wiring connections

3. Excessive liquid refrigerant in compressor

4. Compressor bearings are seized

Measure compressor oil level

Yellow “ALERT”

Flash Code 5

Compressor (Moderate Run)

Trip

1. Evaporator blower is not running

Check blower relay coil and contacts

Check blower motor capacitor

Check blower motor for failure or blockage

Check evaporator blower wiring and connectors

Check indoor blower control board

Check thermostat wiring for open circuit

2. Faulty metering device

Check TXV bulb installation (size, location and contact)

• Check if TXV/ xed ori ce is stuck closed or defective

3. Condenser coil poor air circulation (dirty, blocked, damaged)

4. Low refrigerant charge

Yellow “ALERT”

Flash Code 8

Welded Contactor

Compressor always runs

1. Compressor contactor has failed closed

2. Thermostat demand signal not connected to module

Yellow “ALERT”

Flash Code 9

Low Supply Voltage

Voltage below 18V

1. Control Circuit transformer is overloaded

2. Low line voltage (contact utility if voltage at disconnect is low)

“LOCKOUT” Flash Codes

Red “LOCKOUT”

Flash Code 2

Yellow Off

Compressor (Pressure) Trip

Compressor is locked out

after 4 consecutive or 10 total

compressor (pressure) trip events

1. Condenser fan is not running

Check fan capacitor

Check fan wiring and connectors

Check fan motor for failure or blockage

2. High head pressure

Check high pressure switch if present in system

Check if system is overcharged with refrigerant

Check for non-condensable in system

3. Condenser coil poor air circulation (dirty, blocked, damaged)

4. Return air duct has substantial leakage

Red “LOCKOUT”

Flash Code 3

Yellow Off

Pressure Switch Cycling

Compressor is locked out after 4

consecutive or 10 total pressure

cycling events

1. Time delay relay or control board defective

2. If high pressure switch present go to Flash Code 2 information

Red “LOCKOUT”

Flash Code 4

Yellow Off

Locked Rotor

Compressor is locked out after 10

consecutive locked rotor events

1. Run capacitor has failed

2. Low line voltage (contact utility if voltage at disconnect is low

Check wiring connections

3. Excessive liquid refrigerant in compressor

4. Compressor bearings are seized

Measure compressor oil level

Table 2 Continued

12

© 2011 Emerson Climate Technologies

Printed in the U.S.A.

AE8-1385

Application Engineering

BULLETIN

Red “LOCKOUT”

Flash Code 5

Yellow Off

Compressor (Moderate Run)

Trip

Compressor is locked out

after 4 consecutive or 10 total

compressor (moderate run) trip

events

1. Evaporator blower is not running

Check blower relay coil and contacts

Check blower motor capacitor

Check blower motor for failure or blockage

Check evaporator blower wiring and connectors

Check indoor blower control board

Check thermostat wiring for open circuit

2. Faulty metering device

Check TXV bulb installation (size, location and contact)

• Check if TXV/ xed ori ce is stuck closed or defective

3. Condenser coil poor air circulation (dirty, blocked, damaged)

4. Low refrigerant charge

Red “LOCKOUT”

Flash Code 6

Yellow Off

Open Start Circuit

Current only in run circuit

1. Run capacitor has failed

2. Open circuit in compressor start wiring or connections

Check wiring and connectors between supply and the

compressor “S” terminal

3. Compressor start winding is damaged

Check compressor motor winding resistance

Red “LOCKOUT”

Flash Code 7

Yellow Off

Open Run Circuit

Current only in start circuit

1. Open circuit in compressor run wiring or connections

Check wiring and connectors between supply and the

compressor “R” terminal. Con rm proper wire routing per

Figure 1.

2. Compressor run winding is damaged

Check compressor motor winding resistance

Red “LOCKOUT”

Flash Code 10

Over Current Protection

Current to PROT is greater than

2A mps

1. Check for contactor shorted to ground

2. Check for mis-wiring to the PROT terminal

Table 2 Continued

The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or

services described herein or their use or applicability. Emerson Climate Technologies, Inc. reserves the right to modify the designs or speci cations of such products at any time without

notice. Emerson Climate Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of

any Emerson Climate Technologies, Inc. product remains solely with the purchaser and end-user.

Specifications:

1755/1755944-coresense_diagnostics.pdf file (27 Dec 2022)

Accompanying Data:

Emerson Coresense Diagnostics Diagnostic Equipment PDF Bulletin (Updated: Tuesday 27th of December 2022 09:51:44 AM)

Rating: 4.6 (rated by 86 users)

Compatible devices: FilmArray Pneumonia Panel, Comfort Alert, FDS-5200, CRT511, CRP229, V007, 91648, MP720775.

Recommended Documentation:

Text of Bulletin

(Ocr-Read Version Summary of Contents, UPD: 27 December 2022)

  • 4, AE8-1379 R2 Introduction CoreSense ™ Diagnostics is a breakthrough innovation for troubleshooting residential air-conditioning and heat pump systems. The CoreSense Diagnostics module is easily installed in the unit electrical panel near the compressor contactor. By using the compressor as a sensor, CoreSense Diagnostics helps the…

  • 8, AE8-1379 R2 Current Sensor Opening Reset Bu on Yellow LED Red LED PROT Y (3 Wire Only) C Data Port (Not Present on 2 Wire) R (3 Wire Only) Y (2 Wire Only) Figure 4 Dimensions are in Millimeters © 2015 Emerson Climate Technologies 8

  • 5, AE8-1379 R2 Compressor Protection The CoreSense Diagnostics module utilizes proprietary algorithms to protect the compressor and system from repeated trips of system pressure controls and the compressor internal overload. The protection terminal of the module should be wired in series with the system low pressure and high pressure …

  • 1, Emerson Coresense Diagnostics AE8-1379 R2 February 2015 CoreSense ™ Diagnostics for Copeland Scroll ™ Air Conditioning Compressors TABLE OF CONTENTS Section Page Introduction ……………………………………………………………………………………. 4 CoreSense Diagnostics Part Numbers ……………………………………….…

  • 3, Emerson Coresense Diagnostics AE8-1379 R2 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons WARNING WARNING WARNING CAUTION ELECTRICAL SHOCK HAZARD • Disconnect and lock out power before servicing. • Discharge all capacitors before servicing. • Use compressor with grounded system only. •…

  • 10, AE8-1379 R2 Table 2 CoreSense Diagnostics LED Troubleshooting Information Flash Code number corresponds to the number of LED flashes, followed by a pause and then repeated. TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation. Status Description Troubleshooting Information Solid Yellow “RUN” Module has power and oper…

  • 11, AE8-1379 R2 Status Description Troubleshooting Information 1. Run capacitor has failed 2. Low line voltage (contact utility if voltage at disconnect is low) Yellow “ALERT” Flash Code 4 Locked Rotor • Check wiring connections 3. Excessive liquid refrigerant in compressor 4. Compressor bearings are seized • Measure compressor oil level 1.…

  • 6, Emerson Coresense Diagnostics AE8-1379 R2 lockout the compressor, and after the issue has been resolved, it is necessary to manually reset the module in order to clear the present alert code. The primary way of clearing the code and resetting the alert is to press the reset button located on the module. Note: Pressing the reset will require a pin or mini/electronics screwdr…

  • 9, AE8-1379 R2 Table 1 — Quick Reference Table Alert Code Alert Condition Lock Level Lock Indication Normal Run Solid Yellow Code1 Yellow Flash 1 Normal operation, no trip. Long run time. Compressor is on running for more than 18 hours. (Code1 is disabled in Heat Pump mode.) N/A N/A N/A N/A Code2 Compressor (pressure)…

Emerson Coresense Diagnostics Recommended Instructions:

F700, DVD6500, duet GEW9250PL0, VT-PTFMK, D-E770

  • MSW Motor Technics

    MSW-DENTPULLER.L01

    EXPONDO.DEDENT REPAIR LINE BOARD REFLECTORMSW-DENTPULLER.L01BEDIENUNGSANLEITUNGUser manual | Instrukcja obsługi | Návod k použití | Manuel d´utilisation | Istruzioni per l‘uso | Manual de instrucciones …

    MSW-DENTPULLER.L01 11

  • Whale

    PE-12-025

     1.00ENG This user manual includes detailed usage instructions for PortableUltrasound Diagnostic Scanner. Please read this manual …

    PE-12-025 298

  • Sealey

    VS2076

    Thank you for purchasing a Sealey product. Manufactured to a high standard, this product will, if used according to these instructions, and properly maintained, give you years of trouble free performance.IMPORTANT: PLEASE READ THESE INSTRUCTIONS CAREFULLY. NOTE THE SAFE OPERATIONAL REQUIREMENTS, WARNINGS & CAUTIONS. USE THE PRODUCT CORRECTLY AND WITH CARE FOR THE PURPOSE FO …

    VS2076 3

  • Launch

    X-431 PADII

    X-431 HD Module ( )Android-basedUser ManualLAUNCH了解 诊 断盒2 Download and Install X-431 HD Module App1. Visit the LAUNCH website and download the application corresponding to the X-431 HD module;Note: If downloading using the diagnostic tool, please be sure that Wi-Fi has good or strong signals. For details on Wi-Fi connection, refer to the user ’s manual of the diagnostic too …

    X-431 PADII 3

  • Toshiba

    e-STUDIO2010AC

    1 SYS Board Diagnosis Tool User’s Guide Version 01 10/2021 e-STUDIO2010AC/2510AC e-STUDIO2515AC/3015AC/3515AC/4515AC5015AC e-STUDIO2018A/2518A/3018A/3518A/4518A/5018A e-STUDIO5516AC/6516AC/7516AC e-STUDIO5518A/6518A/7518A/8518A …

    e-STUDIO2010AC 20

  • Matco Tools

    MaxLiteA

    IMDMAXLITEA WARNING 1. Always perform automotive testing in a safe environment.2. Do not connect or disconnect any test equipment while the ignition is on or the engine is running.3. DO NOT attempt to operate the tool while driving the vehicle. Have second personal operate the tool. Any distraction may cause an accident.4. Before starting the engine, put the gear lever in th …

    MaxLiteA 25

  • Eaton

    Crouse-hinds series

    Explosionsgeschützte LED-Rettungszeichenleuchte Serie: Ex-Lite, Ex-Lite V-CG-S, Ex-Lite 24 V, Ex-Lite LTExplosion protected LED exit luminaire Series: Ex-Lite, Ex-Lite V-CG-S, Ex-Lite 24 V, Ex-Lite LTPanneau de signalisation de sortie de secours lumineux antidéflagrant à diodes électroluminescentes Series: Ex-Lite, Ex-Lite V-CG-S, Ex-Lite 24 V, Ex-Lite LTCZ: &qu …

    Crouse-hinds series 8

  • Protec

    PRS 500 X

    PROTEC GmbH & Co. KG In den Dorfwiesen 14, 71720 Oberstenfeld, Germany Telephone: +49 (0) 7062/92 55-0 E-Mail: [email protected] Version: 2.0 Issued: 2019-07-31 Subject to alterations PRS 500 X Basic diagnostic X-ray system Model/ID: 7066-9-8050L User Manual Ident. Nr. 5066-0-8002 PRS 500 X i …

    PRS 500 X 38

  • Launch

    Creader Professional 909

    iLAUNCH Professional 909 User ManualCopyright InformationCopyright © 2019 by LAUNCH TECH CO., LTD. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, photocopying and recording or otherwise, without the prior written …

    Creader Professional 909 58

Additional Information:

Popular Right Now:
Operating Impressions, Questions and Answers:

Table of Contents for Emerson Coresense Diagnostics:

  • AE8-1379 R2 Safety Instructions Copeland Scroll ™ compressors with CoreSense ™ Diagnostics technology are manufactured according to the latest U.S. and European Safety Standards. Particular emphasis has been placed on the user’s safety. Safey icons are explained below and safety instructions applicable to the products in this bulletin are grouped on Page 3. These instructions should be retained throughout the lifetime of the compressor. You are strongly adv

  • AE8-1379 R2 lockout the compressor, and after the issue has been resolved, it is necessary to manually reset the module in order to clear the present alert code. The primary way of clearing the code and resetting the alert is to press the reset button located on the module. Note: Pressing the reset will require a pin or mini/electronics screwdriver. This button must be pressed and held for a minimum of one second for the module to be reset. Pressing the reset button clears the

  • AE8-1379 R2 Table 2 CoreSense Diagnostics LED Troubleshooting Information Flash Code number corresponds to the number of LED flashes, followed by a pause and then repeated. TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation. Status Description Troubleshooting Information Solid Yellow “RUN” Module has p

  • AE8-1379 R2 Compressor Protection The CoreSense Diagnostics module utilizes proprietary algorithms to protect the compressor and system from repeated trips of system pressure controls and the compressor internal overload. The protection terminal of the module should be wired in series with the system low pressure and high pressure cutouts, as well as the compressor contactor. When the module detects a series of trips as described below, it will activate a lockout feature that opens the normally closed p

  • AE8-1379 R2 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons WARNING WARNING WARNING CAUTION ELECTRICAL SHOCK HAZARD • Disconnect and lock out power before servicing. • Discharge all capacitors before servicing. • Use compressor with grounded system only. • Molded electrical plug must be used when required.

  • AE8-1379 R2 Current Sensor Opening Reset Bu on Yellow LED Red LED PROT Y (3 Wire Only) C Data Port (Not Present on 2 Wire) R (3 Wire Only) Y (2 Wire Only) Figure 4 Dimensions are in Millimeters © 2015 Emerson Climate Technologies 8

  • AE8-1379 R2 Status Description Troubleshooting Information 1. Run capacitor has failed 2. Low line voltage (contact utility if voltage at disconnect is low) Yellow “ALERT” Flash Code 4 Locked Rotor • Check wiring connections 3. Excessive liquid refrigerant in compressor 4. Compressor bearings are seized • Measure compressor oil level 1. Evaporator blower is not running • Check blower relay coil and contacts • Check blower motor capacitor

  • AE8-1379 R2 Contactor Coil HPCO LPCO P PROT Indoor C C Unit Y Y CoreSense Module Figure 1 571-0066-00 Two-Wire Diagram HPCO LPCO T1 Defrost Board Indoor C Unit Y R ASC T2 Y C R Contactor Coil P PROT C Y R CoreSense Module Figure 2 571-0067-00 Three-Wire Diagram Contactor Coil HPCO LPCO P PROT Indoor Unit C C Y Y R R CoreSense Module Figure 3 571-0067-00 Three-Wire Diagram © 2015 Emerson Climate Technologies 7

  • AE8-1379 R2 Introduction CoreSense ™ Diagnostics is a breakthrough innovation for troubleshooting residential air-conditioning and heat pump systems. The CoreSense Diagnostics module is easily installed in the unit electrical panel near the compressor contactor. By using the compressor as a sensor, CoreSense Diagnostics helps the service technician more accurately troubleshoot system and compressor fault conditions. CoreSense Diagnostics also provides compressor and system protection through its proprieta

  • AE8-1379 R2 Table 1 — Quick Reference Table Alert Code Alert Condition Lock Level Lock Indication Normal Run Solid Yellow Code1 Yellow Flash 1 Normal operation, no trip. Long run time. Compressor is on running for more than 18 hours. (Code1 is disabled in Heat Pump mode.) N/A N/A N/A N/A Code2 Compressor (pressure) trip. Compressor runs for Red: Flash 2 Yellow Flash 2 12 sec to 15 min followed by a compressor trip 4x consecu

  • AE8-1379 R2 February 2015 CoreSense ™ Diagnostics for Copeland Scroll ™ Air Conditioning Compressors TABLE OF CONTENTS Section Page Introduction ……………………………………………………………………………………. 4 CoreSense Diagnostics Part Numbers ……………………………………………….. 4 Application Restrictions and Types …………………………………………………….. 4 Product Specifications ………

Questions, Opinions and Exploitation Impressions:

You can ask a question, express your opinion or share our experience of Emerson Coresense Diagnostics device using right now.

EMERSON
CoreSense нового поколения
Компрессоры Copeland Stream
Руководство пользователя

1. Введение

CoreSense ™ — это торговая марка компонентов компрессорной электроники, связанной с компрессорами Copeland ™. Технология CoreSense использует компрессор в качестве датчика для получения информации из компрессора, обеспечивая дополнительные функции, такие как расширенная защита двигателя, диагностика, измерение энергопотребления и обмен данными.
Благодаря активной защите, усовершенствованным алгоритмам и функциям, таким как история отказов и светодиодные индикаторы, CoreSense нового поколения (или CoreSense следующего поколения) для компрессоров марки Copeland позволяет техническим специалистам диагностировать прошлое и недавнее состояние системы, обеспечивая более быструю и точную диагностику. и меньшее время простоя. CoreSense нового поколения доступен в стандартной комплектации с 4- и 6-цилиндровыми компрессорами Stream.

АдванtagОтличительные особенности модуля CoreSense нового поколения по сравнению с другими модулями защиты — это скорость отклика и общая схема защиты. Все функции защиты работают сразу после запуска компрессора, и модуль остановит компрессор менее чем за секунду при обнаружении опасной ситуации.

Введение

Рисунок 1: Модуль CoreSense нового поколения

2. Характеристики

Модуль CoreSense нового поколения расположен в клеммной коробке и предварительно смонтирован. Все необходимые параметры мигают при изготовлении компрессора.
Источник питания для модуля управления может быть 115 В переменного тока или 230 В переменного тока.

Технические характеристики CoreSense нового поколения

CoreSense нового поколения

Рисунок 2: CoreSense нового поколения внутри клеммной коробки

CoreSense

3. Функции CoreSense нового поколения

CoreSense нового поколения — это модульная система. Эта модульная конструкция дает клиентам возможность выбирать индивидуальные уровни защиты и / или управления. Можно расширить защиту компрессора от простых функций до высокоуровневой защиты, чтобы продлить срок службы компрессора.

Возможности CoreSense

Рисунок 3: Внутри view модуля CoreSense следующего поколения, с модульными платами

Модуль CoreSense

Таблица 2: Список основных функций

4. Предупреждения, отключения и блокировки.

CoreSense нового поколения обеспечивает 3 различных уровня защиты. Каждый из них имеет свой цвет светодиода.

  • Предупреждающие сигналы: компрессор продолжит работу.
  • Аварийные сигналы отключения: Компрессор выключается на определенное время с автоматическим сбросом.
    Компрессор был остановлен из-за неисправности. Компрессор перезапустится, когда неисправность будет устранена и истечет заданное время выключения.
  • Сигнализация блокировки: компрессор выключается, необходим ручной сброс.
    Компрессор был остановлен из-за неисправности. Компрессор перезапустится после устранения неисправности и выполнения ручного сброса с помощью кнопки сброса. Если установлен модуль расширения Modbus, сброс можно выполнить через Modbus.

5. Функции защиты

5.1 Защита от масла

5.1.1 Недостаточная защита от давления масла

Модуль CoreSense следующего поколения получает входные данные от датчика перепада давления масла (OPS3), расположенного в масляном насосе.

Модуль заменяет механический переключатель давления масла. Кроме того, он обеспечивает дополнительную ценность связи для предупреждения и блокировки недостаточного давления масла с помощью светодиодных мигающих кодов и / или контроллера блока управления. Общее время недостаточного давления масла для компрессора сохраняется и накапливается в памяти модуля.

Модуль выдаст предупреждение, когда перепад давления масла упадет ниже 0.95 бар в течение 4 секунд. Как только перепад давления масла упадет ниже 0.95 бар в течение 2 минут, модуль отключит компрессор и сообщит о «блокировке низкого давления масла». Перед использованием кнопки сброса необходимо выполнить устранение неполадок, чтобы понять причину сбоя. Компрессор снова включится после того, как сброс будет активирован вручную.

ПРИМЕЧАНИЕ: Эта функция не применима к компрессорам Stream CO2, которые не оснащены масляным насосом и смазываются разбрызгиванием.

Технические данные датчика реле давления масла OPS3:

  • Допустимая температура окружающей среды: от -30 ° C до 90 ° C
  • Класс защиты: IP45

OPS3 Давление масла

Рисунок 4: Датчик давления масла OPS3 и электронная часть (при поставке подключены)

5.1.2 Защита уровня масла (опция)

Защита масла достигается с помощью часового устройства OW4 / 5 TraxOil и устройства контроля уровня OM3 / 4/5 TraxOil.

TraxOil использует датчик Холла для измерения уровня масла. Магнитный поплавок (не подверженный вспениванию масла) меняет свое положение в зависимости от уровня масла. Датчик Холла преобразует изменения магнитного поля в эквивалентный сигнал, который используется встроенным электронным контроллером для отслеживания и отображения фактического уровня масла с помощью светодиодов.

ТраксОйл OW5

Рисунок 5: Устройство контроля масла TraxOil OW5 Oil

Смотровое стекло

Рисунок 6: Зоны контроля уровня в смотровом стекле

Легенда светодиодного кода

Таблица 3: Легенда кода светодиода

Устройство контроля уровня масла не входит в стандартный комплект поставки компрессора; его нужно будет подключить к модулю CoreSense следующего поколения через клеммы 15 и 16.

В приложении модуля CoreSense нового поколения можно выбрать два варианта подключения:

  • Закрыто, когда ОК:
    o Настройка по умолчанию после активации
    o Подключите синий (BU) и черный (BK) провода
  • Открыть, когда ОК:
    o Подключите коричневый (BN) и черный (BK) провода

Пользователь имеет возможность выбирать между предупреждением или аварийным состоянием, если уровень масла ниже 25%.

5.2 Защита двигателя от перегрева

Используя термисторы с положительным температурным коэффициентом (PTC) на моделях компрессоров 4M * и 6M * Stream, CoreSense нового поколения обеспечивает защиту двигателя от перегрева.
Две цепи из трех термисторов, каждая из которых соединена последовательно, встроены в обмотки двигателя таким образом, чтобы температура термисторов могла изменяться с небольшой инерцией.

5.2.1 Защита от статического перегрева

Модуль CoreSense следующего поколения отключит компрессор, если обмотки двигателя станут слишком горячими.

Стандартное состояние:

  • Общее сопротивление цепей термисторов при 25 ° C ≤ 1.8 кОм

Состояние тревоги:

  • Состояние срабатывания: сопротивление PTC> 4.5 кОм;
  •  Условие сброса: сопротивление PTC <2.75 кОм; Задержка 5 мин.

Отключение из-за неисправности датчика:

  • Короткое замыкание: сопротивление PTC <20 Ом;
  • Обрыв цепи: сопротивление PTC> 20 кОм.

5.2.2 Динамическая защита от перегрева

Если температура обмотки двигателя повысится за короткий период (> 240 Ом / 400 мс), модуль отключит компрессор. Компрессор перезапустится через 5 минут.

5.3 Защита от высокой температуры нагнетания

Защита по температуре нагнетания обеспечивается датчиком PT1000 в головке блока цилиндров компрессора.

Датчик предварительно установлен на заводе и подключен к модулю CoreSense нового поколения. Модуль защитит компрессор от условий высокой температуры нагнетания. Если датчик температуры определяет температуру нагнетания выше 154 ° C, модуль отключит компрессор до тех пор, пока температура не снизится до приемлемого уровня (на 20 K ниже заданного значения).
Конфигурируемый диапазон настроек отключения составляет от 108 ° C до 154 ° C, а значение сброса составляет от 83 ° C до 134 ° C.

  • Значение срабатывания ≥ 154 ° C на 0.5 сек.
  • Аварийный сигнал отключения: автоматический сброс через 2 минуты; температура нагнетания <130 ° C

Технические данные датчика PT1000:

  • Диапазон измерения: от -40 ° C до 155 ° C, 170 ° C в течение 30 минут макс.
  • Момент затяжки: 15 Нм
  • Класс защиты: IP65

Датчик температуры нагнетания

Рис.7: Датчик температуры нагнетания

5.4 Токовая защита

Датчик тока находится в клеммной коробке.
Один провод питания (2 от одной фазы в случае частичной обмотки) проходит через этот датчик — см. T1 в главе 16.2 Электрические схемы.
Следует уважать направление отведений.

Текущая защита

Рисунок 8: Датчик тока

5.4.1 Защита от заторможенного ротора

Если через 2.5 секунды после запуска компрессора ток составляет 150% от значения MOC, срабатывает аварийный сигнал и компрессор отключается. Аварийный сигнал сбрасывается через 5 минут.
После 10 отключений активируется блокировка, и модуль CoreSense нового поколения необходимо сбросить вручную с помощью кнопки сброса (без автоматического сброса).

5.4.2 Защита MOC

Значение MOC компрессора сохраняется в модуле CoreSense нового поколения. Компрессор отключается, если измеренный ток превышает значение MOC более 2 секунд.
Эта функция запускается через 4.5 секунды после запуска компрессора и автоматически сбрасывается через 5 минут после отключения.

5.4.3 Защита от превышения частоты коммутации

Количество запусков компрессора отслеживается в течение определенного периода времени. Если компрессор достигает максимального количества запусков за время короче заданного, срабатывает аварийный сигнал.

  • По умолчанию установлено 10 запусков за 1 час и создание поездки.
  • Время сброса рассчитывается как разница между заданным периодом времени (1 час) и фактическим временем, которое потребовалось для выполнения определенного максимального количества запусков (10).
  • Exampль:
    1. 10 запусков произошло за 35 минут.
    2. будильник срабатывает через 35 минут
    3. автоматический сброс будет выполнен через 25 минут.
    Можно выбрать предупреждение или отключение компрессора.

5.4.4 Обнаружение MOC при первом запуске

Большинство компрессоров имеют два набора номинального объемаtages и частоты:

  • Значение 50 Гц или 60 Гц для двигателей с частичной обмоткой (AW…)
  • другой объемtages для двигателей с Δ / Y-пуском (EW…)

При первом запуске и при каждом сбросе питания модуль CoreSense нового поколения автоматически определяет источник питания компрессора (объемtage и частота) и автоматически выберет соответствующие MOC и undervol.tagэ / овервольtage уставки защиты.

Если измеренный объемtage и / или частота отличается от указанной на паспортной табличке, модуль выдаст предупреждение.

Для бывшихampТо есть, если двигатель AWM / D (400 В / 50 Гц или 460 В / 60 Гц) подключен к линии питания 230 В, зеленый светодиод будет мигать.

5.5 Фаза / об.tagэлектронный мониторинг

Есть 6 томовtagЦепи датчиков для измерения трех фаз. Благодаря 3 датчикам можно также защитить двигатели с частичной обмоткой.

Состояние каждой фазы в прямом включении и частичной обмотке контролируется на пониженное напряжение.tagе, оверволtagе и фазовая асимметрия.

5.5.1 Защита от обрыва фазы / Защита от обрыва фазы

Сравнивается объемtagе каждой фазы и их среднее значение. Если после запуска компрессора отсутствует какая-либо из трех фаз питания, значит, существует однофазное состояние.
Любой объемtagДисбаланс выше 60% является условием отключения по обрыву фазы.
Аварийные условия: возникает в случае отсутствия фазы.

  • Время поездки: 5 минут с автоматическим сбросом.

Пропущенную фазу можно обнаружить при запуске и во время работы компрессора.

5.5.2 Пониженная громкостьtagэлектронная защита

Происходит, когда объем компрессораtage ниже номинального напряжения питанияtage.
Низкая громкостьtage условие предупреждения: объемtage <85% от номинальной линейной громкостиtage на 2 секунды.
Низкая громкостьtagе условия поездки: объемtage <75% от номинальной линейной громкостиtage 2 секунды.

  • Время в пути: 2 минут.

5.5.3 Оверволtagэлектронная защита

Происходит, когда объем компрессораtage выше номинального напряжения питанияtage.
Высокий объемtage условие предупреждения: объемtage> 115% от номинальной линейной громкостиtage на 2 секунды.
Высокий объемtagе условия поездки: объемtage> 125% от номинальной линейной громкостиtage на 2 секунды.

  • Время в пути: 2 минут.

5.5.4 томаtage защита от дисбаланса

Эта функция предназначена для защиты компрессора от перенапряжения.tagНесбалансированность, которая может привести к перегреву двигателя.

Настраиваемая настройка (по умолчанию = 5%) для об.tagДисбаланс используется для определения рабочего предела компрессора. ОбъемtagПараметр дисбаланса можно настроить в диапазоне от 2 до 8% с помощью приложения модуля CoreSense нового поколения.

Условия срабатывания сигнализации:

  • Предупреждение: когда объемtage дисбаланс> 3% (настраивается).
  • Поездка: когда томtage дисбаланс> 5% (настраивается).
  • Сброс: автоматический сброс через 5 мин; объемtagе дисбаланс <5%.

5.5.5 Защита сварного контактора

Эта защита проверяет 3 независимых сигнала работы:

  • обtagе доступно на всех терминалах;
  • ток обнаружен на 1 фазе;
  • сигнал запроса — сигнал от контроллера к контактору.

Если три сигнала запуска не идентичны, модуль CoreSense следующего поколения сгенерирует предупреждение.
По умолчанию защита отключена. Если модуль CoreSense следующего поколения подключен к главному контроллеру (клеммы 17 и 18) и обнаружен сигнал запроса, функция активируется.
Пользователь имеет возможность выбирать между предупреждением или аварийным состоянием. После отключения компрессор перезапустится через 2 минуты. По умолчанию установлено предупреждение.
После 10 отключений активируется блокировка, и модуль необходимо сбросить вручную с помощью кнопки сброса (без автоматического сброса).

5.5.6 Защита части обмотки

Два кабеля питания обмотки должны проходить через датчик тока в одном направлении.
При первом запуске или при перезагрузке модуля CoreSense нового поколенияtagе измеряется на обеих обмотках.

  • Если объемtages идентичны:
    1. компрессор включен по полной обмотке;
    2. защита отключена.
  • Если объемtages разные, объемtages сравниваются снова через 1 секунду:
    1. если объемtagе на второй обмотке такое же, как на первой обмотке:
    — компрессор включен по частям обмотки;
    — защита включена;
    2. если объемtage на второй обмотке не то же самое, что на первой обмотке, вторая обмотка подключена неправильно и компрессор отключается.

Пользователь имеет возможность выбирать между предупреждением или аварийным состоянием. После отключения компрессор перезапустится через 2 минуты. Настройка по умолчанию — отключение.

6. Режим частотно-регулируемого привода.

При работе с частотно-регулируемым приводом все электрические аварийные сигналы отключены.
Режим частотно-регулируемого привода (VFD) можно активировать с помощью следующей процедуры:

  • отключите модуль CoreSense нового поколения от источника питания;
  • отсоедините клеммы 9 и 10 датчика тока;
  • подключить перемычку между выводами датчика тока на модуле (короткое замыкание);
  • подать питание на модуль:
    1. появится предупреждение о коротком замыкании (мигающий оранжевый светодиод) датчика тока;
  • нажмите и удерживайте кнопку сброса более 10 секунд (может быть выполнено только в течение первых 5 минут после сброса питания):
    1. зеленый / красный код быстрого мигания светодиода;
    2. через 10 секунд мигание становится медленным;
  • после отпускания кнопки сброса активируется режим VFD.

Если датчик тока подключен снова, режим VFD можно активировать, нажав кнопку сброса более 10 секунд.

7. Аварийный режим.

Аварийный режим можно использовать в исключительных случаях для обхода расширенной защиты и работы только с базовой защитой (давление масла и температура двигателя).

Чтобы активировать аварийный режим:

  • отсоедините датчик температуры линии нагнетания от модуля CoreSense следующего поколения, клеммы 7 и 8;
  • подключить перемычку между выводами датчика температуры нагнетательной линии (короткое замыкание);
  • нажмите и удерживайте кнопку сброса более 10 секунд.

8. Светодиоды на крышке клеммной коробки.

Светодиодные индикаторы состояния трех цветов (зеленый, оранжевый и красный) видны в верхней части Т-образного блока.

крышка клеммной коробки

Рисунок 9: Клеммная коробка модуля CoreSense нового поколения

8.1 Коды состояния компрессора

  • Горит зеленым: индикация нормальной работы. В компрессоре нет неисправностей или проблем.
  • Мигающий зеленый: индикация состояния предупреждения. Компрессор продолжает работать.
  • Горит оранжевым: индикация того, что компрессор находится в аварийном режиме.
  • Мигающий оранжевый: индикация того, что компрессор отключился и автоматически перезапустится через определенное время (автоматический сброс).
  • Горит красным: означает, что CoreSense находится в режиме параметризации.
  • Мигающий красный: индикация того, что компрессор заблокирован. Для перезапуска необходим ручной сброс.

8.2 Сигналы неисправности, отображаемые светодиодами

Аварийные сигналы отображаются с помощью цветных светодиодов и мигающих последовательностей. Каждая последовательность вспышек прерывается 2-секундной паузой.

Стандартные настройки

Таблица 4: Пояснения к мигающим сигналам X = отключено в стандартной поставке

9. История аварийных сигналов.

20 последних аварийных сигналов хранятся в памяти модуля и могут быть загружены с помощью приложения модуля CoreSense нового поколения.

10. Кнопка сброса

После блокировки компрессора необходимо нажать кнопку сброса. Кроме того, его можно использовать для немедленного сброса аварийного отключения (нет времени ожидания компрессора для перезапуска).

  • Если условие отключения сброшено, все счетчики отключения сбрасываются на ноль, компрессор может перезапуститься.
  • Если условие отключения не устранено, сигнал сброса игнорируется.

11. Управление подогревателем картера.

Модуль CoreSense следующего поколения напрямую управляет нагревателем картера, поэтому только нагреватель картера с тем же источником питания, что и модуль CoreSense (115 В переменного тока или 230 В переменного тока), может быть применен и подключен к клеммам 3 и 4.

Управление подогревателем картера

Рисунок 10: Схема подключения — Подключения нагревателя картера

12. Измерение энергопотребления.

Мощность рассчитывается по измеренному объемуtagе, ток и коэффициент мощности.
Точность каждого измерения:

  •  обtagд ± 5%
  •  ток ± 5%
  •  коэффициент мощности ± 10%

Потребляемая мощность в кВтч указана в приложении модуля CoreSense нового поколения.

13. Порт данных для связи с приложением модуля CoreSense нового поколения.

Порт данных может использоваться для связи с приложением модуля CoreSense нового поколения для параметрирования или загрузки данных (история выполнения и аварийные сигналы).

Модуль CoreSense

Рисунок 11: Порт данных на модуле CoreSense нового поколения

13.1 Связь

Есть две возможности для связи через порт данных, USB или шлюз Bluetooth.
USB-шлюз можно использовать с любым компьютером USB типа A. Адаптеры USB типа A на USB micro-B и USB-C поставляются для подключения к устройствам Android. Подключение к устройствам iOS невозможно через шлюз USB.

Шлюз Bluetooth можно использовать с любым устройством с адаптером Bluetooth. Это также единственная возможность подключения для устройств iOS.

USB-шлюз

14. Модуль Modbus (опционально)

Модуль CoreSense нового поколения может быть оснащен модулем расширения Modbus для связи через RS485.

Данные диагностики могут быть считаны в системные контроллеры с использованием стандартного протокола Modbus RTU.

Модуль расширения Modbus

ПРИМЕЧАНИЕ: Более подробную информацию об интерфейсе Modbus можно найти в специальной технической информации TI_Stream_NGCS_02 «Next Generation CoreSense ™ — Описание интерфейса Modbus».

15. Приложение модуля CoreSense нового поколения.

Приложение можно загрузить из Google Play Store для Android, Microsoft Store для Windows или Apple Store для устройств iOS. Он обеспечивает доступ к памяти / счетчику ошибок, поэтому можно оценить текущее состояние системы и восстановить рабочие данные.viewредактор
Это приложение также позволяет анализировать измерения, выполняемые различными датчиками модуля CoreSense следующего поколения, и предоставлять информацию о работе компрессора, такую ​​как:

  • время работы в нормальных условиях / условиях предупреждения / отключения;
  • количество пусков и остановок;
  • потребляемая мощность;
  • время работы компрессора;
  • счетчик моточасов подогревателя картера.

Приложение модуля CoreSense нового поколения можно подключить к CoreSense следующего поколения с помощью шлюза DP-USB (не применяется для устройств Apple) или шлюза Bluetooth.

16. Электрические соединения

16.1 Основные подключения

Модуль CoreSense следующего поколения изначально поставляется с предварительно подключенными базовыми модулями.

Основные подключения

Рисунок 15: Базовые средства защиты CoreSense нового поколения

16.2 Схемы подключения

ВАЖНАЯ ИНФОРМАЦИЯ
Для моделей компрессоров Stream CO2 малых и средних размеров (от 4MTL-05 до 4MTL-30 и от 4MSL-03 до 4MSL-15) необходимо учитывать синие позиции 1U, 2V, 3W, 7Z, 8X, 9Y на схемах ниже. Расположение клемм на всех остальных моделях компрессоров Stream соответствует черным позициям. Заводская поставка правильная, НЕ меняйте местами соединения.

Легенда

Легенда

монтажная схема

Рисунок 16: Схема подключения двигателей с частичной обмоткой (AW…)

Моторы Delta

Рисунок 17: Схема подключения двигателей звезда / треугольник (EW…)

с частичной обмоткой и звездой

Рисунок 18: Схема подключения (2-я часть) для двигателей с частичной обмоткой и двигателями со звездой / треугольником (AW… и EW…)

Документы / Ресурсы

Рекомендации

  • ecteu-intranet.emrsn.org
    PENTAX K-3 Mark III User Manual — Руководства +

Понравилась статья? Поделить с друзьями:
  • Coreldrw exe ошибка приложения
  • Coreldraw при запуске выдает ошибку 126
  • Coreldraw попробуйте перезагрузить компьютер ошибка 1
  • Coreldraw ошибка шрифты не найдены
  • Coreldraw ошибка при импорте файла