Lme 22 коды ошибок

  • Page 1
    SCC Inc. Technical Instructions LME-1000 www.scccombustion.com June 11, 2019 LME7… Burner Controls Combustion Controls…
  • Page 2
    Intentionally Left Blank …
  • Page 3: Table Of Contents

    LME Series Technical Instructions Document No. LME-1000 Table of Contents Section 1: Overview Introduction ……………………… 1 LME7 System Builder ………………….2 Mounting ……………………..10 Important Safety Notes ………………….12 Approvals ……………………..13 Section 2: LME71 Wiring, Parameters, and Phase Diagrams LME71 Wiring Diagrams ………………….

  • Page 4
    Technical Instructions LME Series Document No. LME-1000 Section 6: PWM Blowers Introduction ……………………… 1 PWM Blower Fundamentals ………………..1 Centrifugal Blower Fundamentals ………………2 Blower Speed Monitoring …………………. 3 Commissioning the LME7 when Using a PWM Blower…………5 Adjusting P0, P1, and P2 via the LME7 Built-in Display …………7 Adjusting P0, P1, and P2 via the AZL23 Display Unit ……………
  • Page 5
    LME Series Technical Instructions Document No. LME-1000 Section 9: ACS410 ACS410 Software Introduction ………………..1 Software Installation ………………….2 Connecting to a PC ……………………. 3 Saving a Parameter Set to a PC ………………..4 Uploading a Parameter Set to an LME7 ……………… 5 Creating an LME7 Startup Report ……………….
  • Page 6
    Technical Instructions LME Series Document No. LME-1000 Intentionally Left Blank Table of Contents Page 4 SCC Inc.
  • Page 7
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 8
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 9: Introduction

    LME Series Technical Instructions Document No. LME-1000 Introduction The LME7 burner control is ideally suited for use in industrial thermal process applications. The LME7 is extremely flexible, and encompasses the following features: • Accepts standard UV, self-check UV, or self-check IR scanners and/or flame rods •…

  • Page 10: Lme7 System Builder

    Technical Instructions LME Series Document No. LME-1000 LME7 System Builder The LME7 burner control system is comprised of many components. Use the following pages to choose the components needed for your specific application. Control Panel Components Base Unit – Qty (1) Required Choose one of the following LME7 base unit options.

  • Page 11
    LME Series Technical Instructions Document No. LME-1000 Plug Set – Qty (1) Required The terminal plug set for the LME7 is sold separately. Each LME7 needs one plug set. Plug set containing all terminals for an LME7 system AGG3.710 LME7 Package — Optional For convenience, the LME7 base unit, PME7 program module, and AGG3.710 plug set can be ordered as a package that is shipped pre-assembled.
  • Page 12
    Technical Instructions LME Series Document No. LME-1000 Remote Display – Optional Each LME7 can be equipped with a remote display that provides additional status information not shown by the integral LED display on the LME7. Either the remote display or the ACS410 software are required to change parameter settings on the LME7.
  • Page 13
    LME Series Technical Instructions Document No. LME-1000 Actuators and Accessories Actuator – Qty (1) Optional with LME73 and LME75 Burner Controls SQM4… and SQM5… series actuators are available for use with the LME73 and LME75 burner controls. For more information on SQM4… actuators, refer to Document No. N7817. For more information on SQM5……
  • Page 14
    Technical Instructions LME Series Document No. LME-1000 Flame Scanners Flame Scanners – Qty (1) Required Unless Using a Flame Rod Four flame scanners are available for use with the LME7. For technical information about these flame scanners, refer to Document No. N7711 for the QRA4.U, Document No. N7719 for the QRI……
  • Page 15
    LME Series Technical Instructions Document No. LME-1000 QRA75.A17 Accessories — Optional Mounting accessories are available for the QRA75.A17 flame scanner. For more information, refer to Document No. N7712. Right angle adapter for mounting a QRA75 flame scanner. Comes with a 1” NPSM female thread AGG16.U connection Thermal barrier for use with the QRA75 flame…
  • Page 16
    Technical Instructions LME Series Document No. LME-1000 Additional Flame Scanner Accessories – Optional Additional accessories are available for flame scanners to prevent heat from getting to the scanner. For more information, refer to Document No. N7711 and Document No. N7712. Thermal barrier for use with the QRA4.U flame scanner, and QRI2B2.B180B flame scanner when THERMAL-…
  • Page 17
    LME Series Technical Instructions Document No. LME-1000 Enclosures Enclosures — Optional A small NEMA 1 enclosure is available for use with any LME7… base unit. Three ½” conduit knockouts are available on both the top and the bottom of the enclosure. NEMA 1 enclosure for any LME7……
  • Page 18: Mounting

    Technical Instructions LME Series Document No. LME-1000 Mounting LME7 Controller The LME7 must be mounted inside an enclosure that will protect it from dirt and moisture. The unit should be mounted with three #8 screws (not provided). The panel, which the unit sits on, should be drilled and tapped to accommodate these screws.

  • Page 19
    LME Series Technical Instructions Document No. LME-1000 AZL23 Display The AZL23 is designed to be mounted in a rectangular cutout through the face / door of an electrical enclosure. It has one screw on the top and another on the bottom that engage small plastic tabs which will swing out when the screw is tightened clockwise;…
  • Page 20: Important Safety Notes

    Technical Instructions LME Series Document No. LME-1000 Important Safety Notes • The LME7 is a safety device. Under no circumstances should the unit be modified or opened. SCC Inc. will not assume responsibility for damage resulting from unauthorized modification of the unit. •…

  • Page 21: Approvals

    LME Series Technical Instructions Document No. LME-1000 Approvals The LME7 has the following standards and approvals: SCC Inc. Page 13 Section 1…

  • Page 22
    Technical Instructions LME Series Document No. LME-1000 Intentionally Left Blank Section 1 Page 14 SCC Inc.
  • Page 23
    Section 1 Overview LME71 Wiring, Section 2 Parameters, and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 24
    Section 1 Overview Section 2 LME71 Wiring, Parameters, and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 25: Lme71 Wiring Diagrams

    LME Series Technical Instructions LME-1000 LME71 Wiring Diagrams PME71.111A1 – Pilot or direct spark; with purge; no actuator control; no valve proving SCC Inc. Page 1 Section 2…

  • Page 26
    Technical Instructions LME Series Document No. LME-1000 PME71.112A1 – Pilot or direct spark; no purge; no actuator control; no valve proving Section 2 Page 2 SCC Inc.
  • Page 27
    LME Series Technical Instructions LME-1000 PME71.901A1 – PWM blower control; direct spark only; valve proving; no actuator control SCC Inc. Page 3 Section 2…
  • Page 28: Lme71 Parameter List

    Technical Instructions LME Series LME71 Parameter List LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME71. PME71. PME71. Shaded Parameters = Frequently Used Parameter Name Number 111A1…

  • Page 29
    Technical Instructions LME Series LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME71. PME71. PME71. Shaded Parameters = Frequently Used Parameter Name Number 111A1…
  • Page 30
    Technical Instructions LME Series LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME71. PME71. PME71. Shaded Parameters = Frequently Used Parameter Name Number 111A1…
  • Page 31
    Technical Instructions LME Series LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME71. PME71. PME71. Shaded Parameters = Frequently Used Parameter Name Number 111A1…
  • Page 32
    Defines the device being controlled by the LME7 that is used to influence the amount of air to the burner. This value is set by Siemens and cannot be modified. On PME71.901A1, this value should always be set to Read only •…
  • Page 33
    Max Ramp Down For Siemens use only. Sets the maximum allowable value for the ramp down time (parameter 523). For Siemens use only. Sets the amount of time the blower speed can lie outside of tolerance band 1 • Tolerance Band 1 Time before a lockout occurs.
  • Page 34
    Technical Instructions LME Series LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME71. PME71. PME71. Shaded Parameters = Frequently Used Parameter Name Number 111A1…
  • Page 35: Lme71 Phase Diagrams

    Technical Instructions LME-1000 LME71 Phase Diagrams The Siemens LME7 burner controls can perform a number of different burner sequences based upon which PME7 program module is used, how certain parameters are set, and how the LME7 is wired. Each program module has an associated phase diagram. The phase diagrams illustrate when input and output terminals are expected to be energized or de-energized.

  • Page 36
    LME Series Technical Instructions LME-1000 PME71.111A1 Phase Diagram Phase Param. OPER- STARTUP SHUTDOWN ATION SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch X5-01.2 Gas Pressure Switch(es) X10-05.2 Flame Signal X10-06.1/2 POC (P237 = 1) X2-02.4…
  • Page 37
    LME Series Technical Instructions LME-1000 PME71.112A1 Phase Diagram Phase Param. OPER- STARTUP SHUTDOWN ATION SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X5-01.2 Gas Pressure Switch(es) X10-05.2 Flame Signal X10-06.1/2 POC (P237 = 1) X2-02.4 POC (P237 = 2) X2-02.3…
  • Page 38
    Technical Instructions LME Series LME-1000 PME71.901A1 Phase Diagram Phase Param. OPER- STARTUP SHUTDOWN VALVE PROVING ATION SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch X5-01.2 Gas Pressure Switch(es) X9-04.2 Valve Proving Pressure Switch X10-05.2 Flame Signal…
  • Page 39
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams Section 3 LME73 Wiring, Parameters, and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 40
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams Section 3 LME73 Wiring, Parameters, and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 41: Lme73 Wiring Diagrams

    LME Series Technical Instructions LME-1000 LME73 Wiring Diagrams PME73.811A1 – Modulating actuator control with valve proving; ignition position = low fire SCC Inc. Page 1 Section 3…

  • Page 42
    Technical Instructions LME Series Document No. LME-1000 PME73.812A1 – Modulating actuator control with independent ignition position; no valve proving Section 3 Page 2 SCC Inc.
  • Page 43
    LME Series Technical Instructions LME-1000 PME73.840A1 – Floating/bumping (position proportional) actuator control with valve proving; actuator can be disabled; ignition position = low fire SCC Inc. Page 3 Section 3…
  • Page 44: Lme73 Parameter List

    Technical Instructions LME Series LME73 Parameter List LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME73. PME73. PME73. Shaded Parameters = Frequently Used Parameter Name Number 811A1…

  • Page 45
    Technical Instructions LME Series LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME73. PME73. PME73. Shaded Parameters = Frequently Used Parameter Name Number 811A1…
  • Page 46
    Technical Instructions LME Series LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME73. PME73. PME73. Shaded Parameters = Frequently Used Parameter Name Number 811A1…
  • Page 47
    Technical Instructions LME Series LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME73. PME73. PME73. Shaded Parameters = Frequently Used Parameter Name Number 811A1…
  • Page 48
    Technical Instructions LME Series LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME73. PME73. PME73. Shaded Parameters = Frequently Used Parameter Name Number 811A1…
  • Page 49: Lme73 Phase Diagrams

    Technical Instructions LME-1000 LME73 Phase Diagrams The Siemens LME7 burner controls can perform a number of different burner sequences based upon which PME7 program module is used, how certain parameters are set, and how the LME7 is wired. Each program module has an associated phase diagram. The phase diagrams illustrate when input and output terminals are expected to be energized or de-energized.

  • Page 50
    Technical Instructions LME Series Document No. LME-1000 PME73.811A1 Phase Diagram Phase Param. STARTUP OPERATION SHUTDOWN VALVE PROVING SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch X5-01.2 Gas Pressure Switch(es) X9-04.2 Valve Proving Pressure Switch X10-05.2…
  • Page 51
    LME Series Technical Instructions Document No. LME-1000 PME73.812A1 Phase Diagram Phase Param. STARTUP OPERATION SHUTDOWN SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch X5-01.2 Gas Pressure Switch(es) X10-05.2 Flame Signal X10-06.1/2 POC (P237 = 1) X2-02.4…
  • Page 52
    Technical Instructions LME Series Document No. LME-1000 PME73.840A1 Phase Diagram Phase Param. OPER- STARTUP SHUTDOWN VALVE PROVING ATION SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch X5-01.2 Gas Pressure Switch(es) X9-04.2 Valve Proving Pressure Switch X10-05.2…
  • Page 53
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams Section 4 LME75 Wiring, Parameters, and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 54
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams Section 4 LME75 Wiring, Parameters, and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 55: Lme75 Wiring Diagrams

    LME Series Technical Instructions LME-1000 LME75 Wiring Diagrams PME75.811A1 – Modulating actuator control with valve proving; self-check scanner or flame rod; ignition position = low fire SCC Inc. Page 1 Section 4…

  • Page 56
    Technical Instructions LME Series Document No. LME-1000 PME75.812A1 — Modulating actuator control with independent ignition position; no valve proving; self-check scanner or flame rod Section 4 Page 2 SCC Inc.
  • Page 57: Lme75 Parameter List

    Technical Instructions LME Series LME75 Parameter List LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME75. PME75. Shaded Parameters = Frequently Used Parameter Name 811A1 812A1…

  • Page 58
    Technical Instructions LME Series LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME75. PME75. Shaded Parameters = Frequently Used Parameter Name 811A1 812A1 Number…
  • Page 59
    Technical Instructions LME Series LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME75. PME75. Shaded Parameters = Frequently Used Parameter Name 811A1 812A1 Number…
  • Page 60
    Technical Instructions LME Series LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME75. PME75. Shaded Parameters = Frequently Used Parameter Name 811A1 812A1 Number…
  • Page 61
    Technical Instructions LME Series LME-1000 LEGEND — Password Level: S = Service; O = OEM; S/O = View — Service, Write — OEM; Info = Info Menu; Ser = Service Menu Parameter PME75. PME75. Shaded Parameters = Frequently Used Parameter Name 811A1 812A1 Number…
  • Page 62: Lme75 Phase Diagrams

    LME Series LME-1000 LME75 Phase Diagrams The Siemens LME7 burner controls can perform a number of different burner sequences based upon which PME7 program module is used, how certain parameters are set, and how the LME7 is wired. Each program module has an associated phase diagram. The phase diagrams illustrate when input and output terminals are expected to be energized or de-energized.

  • Page 63
    Technical Instructions LME Series Document No. LME-1000 PME75.811A1 Phase Diagram Phase Param. STARTUP OPERATION SHUTDOWN VALVE PROVING SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On Air Pressure Switch Note 3 X3-02.1 Gas Pressure Switch(es) Note 4 X5-01.2 X9-04.2…
  • Page 64
    LME Series Technical Instructions Document No. LME-1000 PME75.812A1 Phase Diagram Phase Param. STARTUP OPERATION SHUTDOWN SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch Note 3 X5-01.2 Gas Pressure Switch(es) Note 4 X10-05.1 Flame Signal…
  • Page 65: Section 5: Commissioning

    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…

  • Page 66
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 67: Commissioning A New Lme7 Burner Control

    LME Series Technical Instructions Document No. LME-1000 Commissioning a New LME7 Burner Control 1. Ensure all devices are properly connected to the LME7. See Section 2 (LME71…), Section 3 (LME73…), or Section 4 (LME75…) of this manual for more information on wiring devices to the LME7 burner control.

  • Page 68: Parameter Backups / Restores

    Technical Instructions LME Series Document No. LME-1000 Parameter Backups / Restores Both the LME7 burner control and PME7 program module contain one parameter set. The parameter set in the LME7 burner control is always the one that is used for burner operation. The parameter set in the PME7 program module is simply a backup parameter set.

  • Page 69: Displaying The Flame Signal From The Lme7 Burner Control

    LME Series Technical Instructions Document No. LME-1000 Parameter Restore (PME7 -> LME7) Using the AZL23 Display Unit Use to overwrite the parameters in the LME7 with those previously saved in the PME7. 1. Press and hold the F and A buttons on the AZL23 until “CodE” is displayed, then release. 2.

  • Page 70: Displaying The Actuator Position / Pwm Blower Speed From The Lme7 Burner Control

    Technical Instructions LME Series Document No. LME-1000 Displaying the Actuator Position / PWM Blower Speed from the LME7 Burner Control The current position of the actuator (LME73…/LME75…) or speed of the PWM blower (LME71… with PME71.901A1) can be viewed from the LME7 burner control using the following procedure. 1.

  • Page 71
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 72
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 73: Introduction

    LME Series Technical Instructions Document No. LME-1000 Introduction The LME71 flame safeguard, when used with the PME71.901A1 program module, features an integrated, closed-loop PWM (pulse width modulation) blower control. This integrated control is used to modulate the speed of a PWM blower with firing rate. The LME71 transmits a PWM control signal to the blower, and then reads back the speed of the blower.

  • Page 74: Centrifugal Blower Fundamentals

    Technical Instructions LME Series Document No. LME-1000 Centrifugal Blower Fundamentals Since a centrifugal blower is the piece of machinery being controlled by the LME7, a brief mention of its basic characteristics is warranted. Specifically, there are three fundamental «fan laws» that a person working with such equipment should be aware of.

  • Page 75: Blower Speed Monitoring

    LME Series Technical Instructions Document No. LME-1000 Blower Speed Monitoring To help ensure that the burner is either operated at a safe fuel-to-air ratio or is shut down, the blower speed is constantly monitored while a flame is present. The speed is monitored in a way that nuisance shutdowns are eliminated, but fast shutdowns will occur if the speed deviation is large.

  • Page 76
    Technical Instructions LME Series Document No. LME-1000 Tolerance Band 1 Tolerance Band 2 Name of Tolerance Band High Limit of Tolerance Band +1.0% to 5.0% +1.0% to 10.0% Low Limit of Speed Band -1.0% to 5.0% -1.0% to 10.0% Parameter to Adjust Width of Band 650.00 650.01 Maximum Blower Speed (P519)
  • Page 77: Commissioning The Lme7 When Using A Pwm Blower

    LME Series Technical Instructions Document No. LME-1000 Commissioning the LME7 when Using a PWM Blower After verifying that all PWM blower-related components are installed and wired correctly, the LME7 burner control can be programmed for the PWM blower application. Prerequisites Ensure that the PWM blower is a closed loop type, meaning that it is utilizing an onboard speed •…

  • Page 78
    Technical Instructions LME Series Document No. LME-1000 8. Set the ignition (P0), low fire (P1), and high fire (P2) blower speeds with the burner off. These values are found in the 400 set of parameters. To set these parameters, use the following procedure: a.
  • Page 79: Adjusting P0, P1, And P2 Via The Lme7 Built-In Display

    LME Series Technical Instructions Document No. LME-1000 Adjusting P0, P1, and P2 via the LME7 Built-in Display 1. While in standby (OFF), press and hold the A button and either the + or — button for more than five seconds until “OFF” starts blinking. 2.

  • Page 80: Adjusting P0, P1, And P2 Via The Azl23 Display Unit

    Technical Instructions LME Series Document No. LME-1000 Adjusting P0, P1, and P2 via the AZL23 Display Unit 1. Log in at the Service or OEM access level. The display will say “400: Set”. Press the info button. 2. The display will say “run”. Give the LME7 a call for heat. The LME7 will proceed to start the burner. After prepurge is complete, the LME7 will slow the blower down to the preset ignition speed (P0).

  • Page 81: Additional Tips For Burners With Pwm Blowers

    LME Series Technical Instructions Document No. LME-1000 Additional Tips for Burners with PWM Blowers Most of the time, speed faults that are seen on the LME7 are caused by the PWM blower not being • able to decelerate quickly enough when the blower is being ramped down. If fast ramp times are not critical for the application, ramp times (parameters 522 and 523) can be increased and this should correct the issue.

  • Page 82
    Technical Instructions LME Series Document No. LME-1000 Intentionally Left Blank Section 6 Page 10 SCC Inc.
  • Page 83
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 84
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 85: Troubleshooting Introduction

    LME Series Technical Instructions Document No. LME-1000 Troubleshooting Introduction The LME7 has an extensive list of fault codes to help clarify the nature of any fault. Section 7-2 describes every fault code in detail and gives guidance on how to correct it. When a fault occurs, the LME7 will alternate between displaying “Loc”…

  • Page 86
    Technical Instructions LME Series Document No. LME-1000 Navigating the Fault History To navigate the fault history, use the following key strokes on the AZL23. • When the parameter number is flashing, press the “+” or “-” button to cycle through the list of faults (parameters 701-711).
  • Page 87: Complete Fault Code List

    Complete Fault Code List Fault Description of the Fault Corrective Action Code A flame failure occurred during lightoff. 1. Check the wiring of the ignition transformer, pilot valve, and main valve(s). 2. Ensure manual shutoff valves on the pilot gas line and main gas line are open. No flame at start-up 3.

  • Page 88
    Fault Description of the Fault Corrective Action Code A flame failure occurred during normal operation. 1. Check the fuel / air ratio. Loss of flame 2. Check the flame detector signal in the presence of a known flame source. Replace the flame detector if it does not produce the anticipated signal.
  • Page 89
    Fault Description of the Fault Corrective Action Code Check all of the switches wired into the safety loop on terminal X3-04.1. One of the switches opened, Safety loop open causing the fault. Fix the condition that caused the switch to open and reset the fault. The 4-20 mA input connected to terminal X65 is out of range.
  • Page 90
    Fault Description of the Fault Corrective Action Code One or more PWM blower settings are not compatible. Make sure the following three conditions on the minimum and maximum speed settings are met. PWM blower parameterization error 1. 516.00 ≤ P0 ≤ 516.01 2.
  • Page 91: Other Common Faults

    LME Series Technical Instructions Document No. LME-1000 Other Common Faults Known Causes of Loc 10 Loc 10 is a catchall fault that can be caused by a variety of issues. All known causes of Loc 10 are listed below in Table 7-1. Table 7-1: All Known Causes of Loc 10 Cause # LME71/73/75…

  • Page 92
    Technical Instructions LME Series Document No. LME-1000 LME7 LED is Flashing Red When the LED on the front of the LME7 is flashing red very quickly, this indicates that the LME7 has been placed into Diagnostic Mode. While being in Diagnostic Mode does not prevent successful operation of the burner, it does remove the status that is typically displayed by the LED, as well as causes operators to incorrectly conclude that the LME7 is damaged.
  • Page 93
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 94
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 95: Introduction

    LME Series Technical Instructions Document No. LME-1000 Modbus RTU and BACnet MS/TP Communication Introduction The physical connection from the LME7 burner control to the Modbus RTU or BACnet MS/TP system is made via an external OCI417.10 interface module. The OCI417.10 is compatible with all LME7……

  • Page 96: Status Led

    Technical Instructions LME Series Document No. LME-1000 Connection to the BMS The connection from the BMS to the OCI417.10 is via terminal block. The physical medium is RS-485. Multiple RS-485 nodes may be connected in a daisy-chain. For long runs (typically greater than 1,000 feet) or noisy environments, termination may be required on the end node.

  • Page 97: Modbus Rtu Connection Details

    LME Series Technical Instructions Document No. LME-1000 Modbus RTU Connection Details Modbus RTU protocol selection and addressing is done using the PC tool OCI417 Configuration Utility (see next section). Supported addresses: 1-247 Supported baud rates: 2400, 4800, 9600, 19200, 38400, 57600 and 115200 Supported data bits: 8 Supported parity and stop bits: none (1 or 2 stop bits), odd (1 stop bit), and even (1 stop bit) Supported function codes: 3 (read holding registers), 4 (read input registers)

  • Page 98: Bacnet Ms/Tp Connection Details

    Technical Instructions LME Series Document No. LME-1000 BACnet MS/TP Connection Details BACnet MS/TP protocol selection and addressing is done using the PC tool OCI417 Configuration Utility (see next section). Supported addresses: 0-127 Supported baud rates: 9600, 19200, 38400, 57600, 76800 and 115200 Supported data bits: 8 Supported parity and stop bits: none (1 stop bit) Supported device instances: 0-4194302…

  • Page 99: Using The Oci417 Configuration Utility

    LME Series Technical Instructions Document No. LME-1000 Using the OCI417 Configuration Utility 1. To download the OCI417 configuration utility, go to the following website and click the “OCI417.10 Configuration Utility” link to download and install the software. http://www.scccombustion.com/flame.htm. 2. Once installed, double-click the icon to open the configuration utility. 3.

  • Page 100
    Technical Instructions LME Series Document No. LME-1000 4. Use a mini-USB cable to connect the OCI417.10 to the computer, such as SCC part number AGA5-05M. A driver may self-install the first time a connection is made. The connected device will then be indicated on the screen. 5.
  • Page 101: Updating The Oci417.10 Firmware

    LME Series Technical Instructions Document No. LME-1000 Updating the OCI417.10 Firmware 1. From the OCI417.10 Configuration Utility, click File -> Update Device… 2. Locate the supplied update file with a .duf extension and click Open. 3. The device will automatically reboot and reconnect with the OCI417.10 Configuration Utility once the firmware update is complete.

  • Page 102: Modbus Mapping

    Technical Instructions LME Series Document No. LME-1000 Modbus Mapping ADDRESS ACCESS DESCRIPTION FORMAT NOTES PHASE Unsigned Int 16 FLAME INTENSITY Unsigned Int 16 MAINS VOLTAGE Unsigned Int 16 STARTUPS RESETTABLE Unsigned Int 32 STARTUPS TOTAL Unsigned Int 32 RELAY K12 CYCLES Unsigned Int 32 RELAY K11 CYCLES Unsigned Int 32…

  • Page 103
    LME Series Technical Instructions Document No. LME-1000 Modbus Mapping ADDRESS ACCESS DESCRIPTION FORMAT NOTES 27 bit 2 INCREASE MODULATION (LR-OPEN) Boolean TERMINAL X5.03.3 27 bit 3 DECREASE MODULATION (LR-CLOSED) Boolean TERMINAL X5.03.2 27 bit 4 COMBUSTION AIR SWITCH (LP) Boolean TERMINAL X3.02.1 27 bit 5 LOW GAS PRESSURE SWITCH (Pmin)
  • Page 104
    Technical Instructions LME Series Document No. LME-1000 Modbus Mapping ADDRESS ACCESS DESCRIPTION FORMAT NOTES HISTORY 7 ERROR LOAD Unsigned Int 16 255 IS NO LOAD RECORDED HISTORY 8 ERROR CODE Unsigned Int 16 HISTORY 8 ERROR STARTUPS Unsigned Int 32 HISTORY 8 ERROR PHASE Unsigned Int 32 PHASE IS 0 WHEN NO ERROR…
  • Page 105: Bacnet Mapping

    LME Series Technical Instructions Document No. LME-1000 BACnet Mapping ADDRESS DESCRIPTION UNITS ACTIVE TEXT INACTIVE TEXT PHASE NO UNITS FLAME INTENSITY PERCENT MAINS VOLTAGE VOLTS STARTUPS RESETTABLE NO UNITS STARTUPS TOTAL NO UNITS RELAY K12 CYCLES NO UNITS RELAY K11 CYCLES NO UNITS RELAY K2 CYCLES NO UNITS…

  • Page 106
    Technical Instructions LME Series Document No. LME-1000 BACnet Mapping ADDRESS DESCRIPTION UNITS ACTIVE TEXT INACTIVE TEXT AV46 HISTORY 6 ERROR LOAD PERCENT AV47 HISTORY 7 ERROR CODE NO UNITS AV48 HISTORY 7 ERROR STARTUPS NO UNITS AV49 HISTORY 7 ERROR PHASE NO UNITS AV50 HISTORY 7 ERROR LOAD…
  • Page 107: Unused Inputs

    LME Series Technical Instructions Document No. LME-1000 BACnet Mapping ADDRESS DESCRIPTION UNITS ACTIVE TEXT INACTIVE TEXT BV27 FAN (M) CMD ON CMD OFF BV28 VALVE 1 (V1) CMD ON CMD OFF BV29 VALVE 2 (V2) CMD ON CMD OFF Unused Inputs Any inputs unused by the selected PME……

  • Page 108
    Technical Instructions LME Series Document No. LME-1000 Intentionally Left Blank Section 8 Page 14 SCC Inc.
  • Page 109
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 110
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 111: Acs410 Software Introduction

    LME Series Technical Instructions Document No. LME-1000 ACS410 Software Introduction The LME7 burner control can be completely programmed using either the AZL23 or a PC with the ACS410 software. Most people find that using the AZL23 is more convenient than the ACS410 for a “manual”…

  • Page 112: Software Installation

    Accept the license agreement and click “Next”. d. Select the folder where the ACS410 software will be installed. The default folder is C:Program Files (x86)SiemensACS410. Click “Next”. e. Select the folder where the ACS410 software shortcuts will be installed in the Start Menu.

  • Page 113: Connecting To A Pc

    LME Series Technical Instructions Document No. LME-1000 Connecting to a PC The following steps summarize the procedure for establishing communication between the LME7 and a PC. 1. An OCI410 interface module is required to connect the LME7 to a PC. Three different interface modules are available: Table 9-1: Available Interface Modules to Connect the LME7 to a PC Interface Module…

  • Page 114: Saving A Parameter Set To A Pc

    The default location for storing parameter sets is C:Program Files (x86)SiemensACS410bkp. Notice that two files are created in this folder: one with a .bkp file extension and one with a .unl file extension. Both files are necessary in order to view the parameter set or restore it to an LME7.

  • Page 115: Uploading A Parameter Set To An Lme7

    LME Series Technical Instructions Document No. LME-1000 Uploading a Parameter Set to an LME7 The following steps outline the procedure for uploading parameter sets from a PC to an LME7. 1. Ensure that the ACS410 software is open, and the PC is connected to the LME7 at the service or OEM level.

  • Page 116: Creating An Lme7 Startup Report

    Technical Instructions LME Series Document No. LME-1000 Creating an LME7 Startup Report The following steps outline the procedure for saving, viewing, and printing a startup report to a 1. Open the ACS410 software. Instead of logging in, click the “Offline” button. Then click the “Backup”…

  • Page 117: Synchronizing The Lme7 And Pme Parameters

    LME Series Technical Instructions Document No. LME-1000 Synchronizing the LME7 and PME Parameters The ACS410 software can be used to synchronize the parameter set used by the LME7 and the backup copy stored on the PME chip. 1. Ensure that the ACS410 software is open, and the PC is connected to the LME7 at the service or OEM level.

  • Page 118: Saving And Viewing Trends

    Technical Instructions LME Series Document No. LME-1000 Saving and Viewing Trends The ACS410 software can be used to view and save trends. Trending enables a technician to easily view and quantify system behavior over time. The following steps outline the procedure for viewing and saving trends with the ACS410 software.

  • Page 119
    5. Trending data is stored in the following location: C:Program Files (x86)SiemensACS410tn. Each set of trending data creates two files: one with a .unl format and one with a .dtd format. Both files are necessary if the trend is to be viewed at a later time through the ACS410 software.
  • Page 120: Viewing The Status Screen

    Technical Instructions LME Series Document No. LME-1000 Viewing the Status Screen When connected to the LME7, the ACS410 can provide a status screen. This provides a useful summary of the LME7 inputs and outputs, as well as the operating state of the LME7. The following steps outline the procedure for viewing the ACS410 status screen.

  • Page 121
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 122
    Section 1 Overview LME71 Wiring, Parameters, Section 2 and Phase Diagrams LME73 Wiring, Parameters, Section 3 and Phase Diagrams LME75 Wiring, Parameters, Section 4 and Phase Diagrams Section 5 Commissioning Section 6 PWM Blowers Section 7 Troubleshooting Section 8 Modbus Section 9 ACS410 Appendix A…
  • Page 123
    LME Series Technical Instructions Document No. LME-1000 Appendix A: LME7 Application Guide Description The LME7 Application Guide includes programming, wiring, and operation examples of the control system for the most common applications. SCC Inc. Page 1 Appendix A…
  • Page 124: Honeywell Modutrol Iv Motor With The Lme75

    Technical Instructions LME Series Document No. LME-1000 Table of Contents Honeywell Modutrol IV Motor with the LME75 Introduction ……………………… 3 Setup Procedure without Valve Proving …………….. 3 Sequence of Operation without Valve Proving …………… 5 Setup Procedure with Valve Proving ………………7 Sequence of Operation with Valve Proving …………….

  • Page 125
    Honeywell Modutrol IV with the LME75 Introduction The Siemens LME75 burner control is designed specifically for use with a Siemens SQM4… or SQM5… series actuator. However, with some simple programming changes and the addition of only a few relays, the LME75 can be set up to safely and effectively control a Honeywell Modutrol IV motor.
  • Page 126
    Technical Instructions LME Series Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) Figure A-1: Wiring a Honeywell Mod IV Motor to the LME75 (no Valve Proving) Appendix A Page 4 SCC Inc.
  • Page 127
    LME Series Technical Instructions Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) Sequence of Operation without Valve Proving 1. The LME75 is in standby. All valves are closed and all relays are de-energized. All relay contacts are as shown in the electrical schematic. The Honeywell Modutrol IV motor (hereafter referred to as mod motor) is at the low fire position.
  • Page 128
    Technical Instructions LME Series Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) 7. Main valve output X7-04.4 is energized in phase 50 (for piloted burners) or phase 40 (for non-piloted burners). Input X5-03.3 is energized, which has no effect. Output X2-09.3 is de-energized, so normally open contact CR-1B remains open, and relay CR-2 remains de- energized.
  • Page 129
    LME Series Technical Instructions Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) Setup Procedure with Valve Proving 1. The following procedure should be used when valve proving is being utilized. 2. Set the following parameters in the LME75 as described below: Parameter 241 = 1 Parameter 259 = Greater than or equal to the running time of the Honeywell Modutrol IV motor being used…
  • Page 130
    Technical Instructions LME Series Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) Figure A-2: Wiring a Honeywell Mod IV Motor to the LME75 (with Valve Proving) Appendix A Page 8 SCC Inc.
  • Page 131
    LME Series Technical Instructions Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) Sequence of Operation with Valve Proving 1. The LME75 is in standby. All valves are closed and all relays are de-energized. All relay contacts are as shown in the electrical schematic. The Honeywell Modutrol IV motor (hereafter referred to as mod motor) is at the low fire position.
  • Page 132
    Technical Instructions LME Series Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) 5. Output X2-09.3 de-energizes and output X2-09.2 energizes in phase 36. These actions de-energize relay CR-1 and energize relay CR-3. Normally open contact CR-1A opens, removing the connection that was keeping the mod motor to high fire. Since normally open contact CR-2 remains open, the mod motor drives to the low fire position.
  • Page 133
    LME Series Technical Instructions Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) 11. Output X2-09.1 is energized in phase 10 to drive the mod motor to low fire. Since the mod motor is already at the low fire position, the low fire proving switch is closed, and actuator feedback input X2-09.4 is energized.
  • Page 134
    Technical Instructions LME Series LME-1000 PME75.811A1 Phase Diagram with Relays Phase Param. STARTUP OPERATION SHUTDOWN VALVE PROVING SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch Note 3 X5-01.2 Gas Pressure Switch(es) Note 4 X9-04.2 Valve Proving Pressure Switch…
  • Page 135: Two Flame Detectors

    LME Series Technical Instructions Document No. LME-1000 Two Flame Detectors Introduction When using a piloted line burner with a flame propagating in excess of three feet, two flame detectors are required by both NFPA 86 and CSA B149.3. These flame detectors are: 1.

  • Page 136
    Technical Instructions LME Series Document No. LME-1000 Two Flame Detectors (continued) Wiring Diagrams Two Flame Rods (Any LME7) Two Flame Scanners (LME71/73) Appendix A Page 14 SCC Inc.
  • Page 137
    LME Series Technical Instructions Document No. LME-1000 Two Flame Detectors (continued) Two Flame Scanners (LME75) One Flame Rod and One Flame Scanner (LME71/73) SCC Inc. Page 15 Appendix A…
  • Page 138
    Technical Instructions LME Series Document No. LME-1000 Two Flame Detectors (continued) One Flame Rod and One Flame Scanner (LME75) Appendix A Page 16 SCC Inc.
  • Page 139
    Intentionally Left Blank …
  • Page 140
    Technical Instructions LME-1000 June 11, 2019…

Здравствуйте!
Добрался до котла.
Повесил вместо датчика пламени резистор на 1.3Ком начал вываливаться сразу в аварию LME горит красным.
Между выводами уф датчика бесконечное сопротивление, попробовал колхозный метод по проверки датчика, зажигаешь зажигалку рядом с лампой и должно появится свечение. Свечения нет. Не знаю даже, рабочий способ или нет.
Еще способ, визуальный, если на электродах имеется фиолетовый налет, значит датчик вышел из строя. Налет действительно есть.
По паспорту для проверки нужен микроамперметр, подойдет ли для этого цифровой мультиметр китайский?
Электролиты есть, а какое-то напряжение нужно подавать на уф-датчик? Или просто замкнуть цепь микроамперметром и параллельно к амперметру подключить конденсатор? И что использовать для засветки датчика?

Допустим датчик не годный, можно ли какой-то более дешевый аналог подобрать, цена на эту стекляшку 32К.
По паспорту наработка датчика 10 000 часов, котлу уже 10 лет))).

7

101

Use, features

Use

Features

Gas Burner Controls LME…

Gas burner controls for the supervision of 1- or 2-stage gas burners of small to medium capacity (typically up to 350 kW), in intermittent operation.

The LME… and this Data Sheet are intended for use by OEMs which integrate the burner controls in their products.

LME… burner controls are used for the startup and supervision of 1- or 2-stage gas burners in intermittent operation. The flame is supervised by an ionization probe or flame detector QRA… with ancillary unit AGQ3… or blue–burning flames with blueflame detectors QRC…

In terms of housing dimensions, the LME… are identical with the LGB… and LMG… burner controls (refer to «Type summary»).

Burner controls conforming to EN 298

For gas burners with fans conforming to EN 676

Undervoltage detection

Air pressure supervision with functional check of the air pressure switch during startup and operation

Electrical remote reset facility

Multicolor indication of fault status and operational status messages

Limitation of the number of repetitions

Accurate control sequence thanks to digital signal handling

Controlled intermittent operation after 24 hours of continuous operation

CC1N7101en

29.06.2006

Building Technologies

HVAC Products

Warning notes

Engineering notes

Mounting notes

To avoid injury to persons, damage to property or the environment, the following warning notes should be observed!

Do not to open, interfere with or modify the unit!

• All activities (mounting, installation and service work, etc.) must be performed by qualified staff

• Before making any wiring changes in the connection area of the LME…, completely isolate the burner control from the mains supply (all-polar disconnection)

• Ensure protection against electric shock hazard by providing adequate protection for the burner control’s connection terminals

• Check the connecting lines of the air pressure switch for short-circuits (connection terminals 3, 6 and 11)

• Press the lockout reset button / operation button only manually (applying a force of no more than 10 N) without using any tools or pointed objects

• Fall or shock can adversely affect the safety functions. Such units must not be put into operation, even if they do not exhibit any damage

• Each time work has been carried out (mounting, installation, service work, etc.), check to ensure that wiring is in an orderly state and make the safety checks as described in «Commissioning notes»

• When used in connection with actuators, there is no position feedback signal from the actuator to the burner control

• When used in connection with actuators, the requirements of EN 676 must be observed

• The running times of the actuators must match the burner control’s program. An additional safety check of the burner control together with the actuators is required

• When substituting burner controls type LGB… or LMG… by LME…, the AGQ1… or

AGQ2… ancillary unit must be replaced by the AGQ3…

• Ensure that the relevant national safety regulations are complied with

2/23

Building Technologies

HVAC Products

CC1N7101en

29.06.2006

Installation notes

• Always run the ignition cables separate from the unit and other cables while observing the greatest possible distance

• Do not mix up live and neutral conductors

• Install switches, fuses, earthing, etc., in compliance with local regulations

• The connection diagrams show the burner controls with earthed neutral conductor.

In networks with nonearthed neutral conductor and ionization current supervision, terminal 2 must be connected to the earth conductor via an RC unit (type reference

ARC 4 668 9066 0). It must be made certain that local regulations are complied with (e.g. protection against electric shock hazard) since AC 230 V / 50 Hz mains voltage produces peak leakage currents of 2.7 mA

• Make certain that the maximum permissible current rating of the connection terminals will not be exceeded

• Do not feed external mains voltage to the control outputs of the unit. When testing the devices controlled by the burner control (fuel valves, etc.), the LME… must not be connected

• In the case of burners with no fan motor, an AGK25 must be connected to terminal

3 of the unit, or else the burner cannot reliably be started up

• For safety reasons, feed the neutral conductor to terminal 2. Connect the burner components (fan, ignition transformer and gas valves) to the neutral distributor as shown below in figure 7101a05. The connection between neutral conductor and terminal 2 is prewired in the base

Example

2 3 7 4 5

Legend

M

Z

BV2

BV1

N

7101a05/0804

Wiring of neutral conductors!

Electrical connection of flame detectors

It is important to achieve practically disturbance- and loss-free signal transmission:

• Never run detector cables together with other cables

– Line capacitance reduces the magnitude of the flame signal

– Use a separate cable

• Observe the permissible length of the detector cables (refer to «Technical data»)

• The ionization probe is not protected against electric shock hazard

• Locate the high-voltage ignition electrode and the ionization probe such that the ignition spark cannot arc over to the ionization probe (risk of electrical overloads) and that it cannot adversely affect the supervision of ionization

– Must be a minimum of 50 M

Ω between ionization probe and ground

– Soiled detector holders reduce the insulation resistance, thus supporting cree-

page currents

• Earth the burner in compliance with the relevant regulations; earthing the boiler alone does not suffice

Building Technologies

HVAC Products

3/23

CC1N7101en

29.06.2006

Commissioning notes

• When commissioning the plant for the first time or when doing maintenance work, make the following safety checks:

Safety check to be carried out

a) Burner startup with previously interrupted line to the flame detector

Anticipated response

LME11…:

Max. 3 repetitions

LME2…:

Lockout at the end of «TSA» b) Burner operation with simulated loss of flame. For that purpose, cut off the gas supply

LME11…:

Establishment of flame at the end of «TSA»

→ Max. 3 repetitions

No establishment of flame at the end of «TSA»

→ Lockout

LME2…:

Lockout

Immediate lockout c) Burner operation with simulated air pressure failure (not with atmospheric burners)

Standards and certificates

Conformity to EEC directives

— Electromagnetic compatibility EMC (immunity)

— Directive for gas-fired appliances

ISO 9001: 2000

Cert. 00739

ISO 14001: 2004

Cert. 38233

Identification code to EN 298

LME11…

F M C L X N

LME21… / LME22… / LME23…

F T L L X N

LME44…

A M L L X N

Service notes

• Use the KF8872 service adapter for short periods of time only

Disposal notes

89 / 336 / EEC

90 / 396 / EEC

The unit contains electrical and electronic components and must not be disposed of together with domestic waste.

Local and currently valid legislation must be observed.

4/23

Building Technologies

HVAC Products

CC1N7101en

29.06.2006

Mechanical design

LME…

Indication and diagnostics

Versions

• Units of plug-in design like their predecessor types LGB… and LMG… (refer to

«Dimensions»)

• The housing is made of impact-proof, heat-resistant and flame-retarding plastic. It is of plug-in design and engages audibly in the base

• The housing accommodates the

— microcontroller for the control sequence and the control relays for load control

— electronic flame signal amplifier (ionization)

— lockout reset button with its integrated 3-color signal lamp (LED) for operational

status and fault status messages and the socket for connecting the OCI400 inter-

face adapter

• Multicolor indication for operational status and fault status messages

• Transmission of operational status and fault status messages and detailed service information via additional OCI400 interface adapter and ACS400 / ACS410 PC

Windows software

• Burner capacity unlimited (thermal output on startup ≤ 120 kW)

• 3 repetitions in the event of loss of flame during operation (LME11…)

Building Technologies

HVAC Products

5/23

CC1N7101en

29.06.2006

Type summary (other types of burner controls on request)

The type references given below apply to the LME… burner control without plug-in base and without flame detector. For ordering information on plug-in bases and other accessories, refer to «Ordering».

Flame detector

Type reference

Main voltage tw approx. t1 min.

TSA max.

t3n approx.

s s s s

Burner controls for 1-stage burners without communication (up to 120 kW output)

Ionization probe

(ION)

LME11.330A2

AC230V t3 approx.

s t4 approx.

s t22 approx.

s

2) t10 min. s

3) t11 min. s

1) t12 min.

s

1)

For replacing of

2.5 30 3 2 2 — — 5 — —

Burner controls for 2-stage burners without communication, without actuator control

LME21.130A1

AC 120 V

LGB21.130A27

2.5 7 3 2 2 8 — 5 —

LME21.130A2

AC 230 V

LGB21.130A27

2.5 7 3 2 2 8 — 5 —

LMG21.130A27

Ionization probe

(ION) or flame detector QRA… with AGQ3…

LME21.230A2

LME21.330A1

LME21.330A2

LME21.350A1

AC 230 V

AC 120 V

AC 230 V

AC 120 V

LGB21.230A27

2.5 20 3 2 2 8 — 5 — —

LMG21.230A27

2.5 30 3 2 2 8 — 5 — —

LGB21.330A27

2.5 30 3 2 2 8 — 5 — —

LMG21.330A27

LGB21.350A17

2.5 30 5 4 2 10 — 5 — —

LME21.350A2

LME21.550A2

AC 230 V

AC 230 V

LGB21.350A27

2.5 30 5 4 2 10 — 5 — —

LMG21.350A27

LGB21.550A27

2.5 50 5 4 2 10 — 5 — —

LMG22.550B27

Burner controls for 2-stage burners without communication, with actuator control

LME22.131A2

LME22.232A2

AC 230 V

AC 230 V

LGB22.130A27

2.5 7 3 2 3 8 — 3 12

LMG22.130A27

2.5 20 3 2 3 8 — 3

LGB22.230A27

16.5

LMG22.230A27

Ionization probe

(ION) or flame detector

QRA…

4)

with

AGQ3…

LME22.233A2

LME22.331A1

LME22.331A2

AC 230 V

AC 120 V

AC 230 V

2.5 20 3 2

2.5 30 3 2

3

3

8

8

— 3 30 30

— 3 12 12

LGB22.330A27

2.5 30 3 2 3 8 — 3 12 12

Burner controls for 2-stage burners

Blue flame detector QRC…

LME23.331A2

AC 230 V

LME23.351A2 AC 230 V

2.5 30 3 2 3 8 — 3 12 12

LGB32.350A27

2.5 30 5 4 1 10 — 3 12 12

Legend tw Waiting time

TSA Safety time t1 t3

Prepurge time

Preignition time t3n Postignition time t4 Interval between ignition «Off» and «BV2» t10 Specified time for air pressure signal t11 Programmed opening time for actuator «SA» t12 Programmed closing time for actuator «SA» t22 2nd safety time

4)

1)

2)

3)

Max. running time available for actuator «SA»

The actuator running time must be shorter t22 + response time of flame relay

Max. 65 s

Only used for AC 230 V

6/23

Building Technologies

HVAC Products

CC1N7101en

29.06.2006

Type summary (other types of burner controls on request) [cont´d]

Flame detector

Type reference

Main voltage tw min. s t1´ min.

s

TSA max.

s t3n approx.

s

Burner controls for atmospheric burners t3 approx.

s t4 approx.

s t22 approx. s t10 min. s

2) t11 min. s

1) t12 min.

s

1)

For replacing of

Ionization probe

(ION) or flame detector QRA…

4) with AGQ3…

LME44.056A2

AC 230 V

LME44.057A1

AC 120 V

16 9 5 4 2 10 5 — — —

16 9 5 4 2 10 8 — — —

LME44.057A2

AC 230 V

16 9 5 4 2 10 8 — — —

Legend tw Waiting time

TSA Safety time t1´ t3

Purge time

Preignition time t3n Postignition time t4 Interval between ignition «Off» and «BV2» t10 Specified time for air pressure signal t11 Programmed opening time for actuator «SA» t12 Programmed closing time for actuator «SA» t22 2nd safety time

4)

1)

2)

3)

Max. running time available for actuator «SA»

The actuator running time must be shorter t22 + response time of flame relay

Max. 65 s

Only used for AC 230 V

Building Technologies

HVAC Products

7/23

CC1N7101en

29.06.2006

Ordering

Gas burner control, without plug-in base

Connection accessories for small burner controls

Plug-in base AGK11…

Cable holders AGK65…, AGK66, AGK67…

Cable strain relief elements for AGK67…

Connection accessories for small burner controls

Plug-in base AGK13…

Plug-in housing AGK56…

Accessories AGK68…

Flame detectors

— Ionization probe

— Flame detector QRA2… or QRA10…

— Blue-flame detector QRC1…

Diagnostics tool refer to «Type summary» refer to Data Sheet N7201 refer to Data Sheet N7203 supplied by thirds refer to Data Sheet N7712 refer to Data Sheet N7716 refer to Data Sheet N7614

Interface adapter OCI400

PC Windows software ACS400

Actuators SQN3…

Actuators SQN7…

Actuators SQN9…

refer to Data Sheet N7808 refer to Data Sheet N7804 refer to Data Sheet N7806

RC unit

ARC 4 668 9066 0

For the supervision of ionization currents in networks with nonearthed neutral conductor

PTC resistor (AC 230 V)

AGK25

For producing a burden on terminal 3 (on burners with no fan motor, e.g. atmospheric gas burners)

Ancillary unit for UV supervision

— Cable length 500 mm

AGQ3.1A27

AGQ3.2A27

— Cable length 300 mm

Can be fitted under the plug-in base (for size, refer to «Dimensions»)

Service adapter

KF8872

— For checking the functioning of the burner controls on the burner plant

— Functional test with signal lamps

Note: With no load on the output terminals, the relevant signal lamp may light up.

— Detector resistance measurement with a jack of 4 mm diameter

8/23

Building Technologies

HVAC Products

CC1N7101en

29.06.2006

Technical data

General unit data

Environmental conditions

Mains voltage

Mains frequency

Power consumption

External primary fuse (Si)

Mounting position

Input current at terminal 12

AC 120 V +10 % / -15 %

AC 230 V +10 % / -15 %

50…60 Hz ±6 %

12 VA max. 10 A (slow) optional max. 5 A

Safety class

Degree of protection

Perm. cable length terminal 1

I

IP 40 (to be ensured through mounting) max. 1 m at a line capacitance of 100 pF/m

(max. 3 m at 15 pF / m) max. 20 m at 100 pF / m Perm. cable length from QRA… to

AGQ3…A27 (lay separate cable)

Remote reset laid separately

Perm. cable length terminals 8 and 10 max. 20 m at 100 pF / m max. 20 m at 100 pF / m

Perm. cable lengths other terminals

Current rating max. 3 m at 100 pF / m

At cos ϕ ≥ 0.6

At cos ϕ = 1

— Terminal 3

— Terminals 4, 5, 7 and 9 (11) Max. 1.7 A

— Terminal 10

Max. 2.7 A

(15 A for max. 0.5 s

→ only LME2…)

Max. 1 A

Max. 3 A

Max. 2 A

Max. 1 A

Storage

Climatic conditions

Mechanical conditions

Temperature range

Humidity

DIN EN 60721-3-1 class 1K3 class 1M2

-20…+60 °C

< 95 % r.h.

Transport

Climatic conditions

Mechanical conditions

Temperature range

Humidity

Operation

DIN EN 60 721-3-2 class 2K2 class 2M2

-20…+60 °C

< 95 % r.h.

Climatic conditions

Mechanical conditions

Temperature range

Humidity

DIN EN 60 721-3-3 class 3K3 class 3M3

-20…+60 °C

< 95 % r.h.

Condensation, formation of ice and ingress of water are not permitted!

Building Technologies

HVAC Products

9/23

CC1N7101en

29.06.2006

Technical data (cont´d)

Flame supervision with ionization probe

Note

Measuring circuit

At mains voltage

UN = AC 230 V ¹)

Detector voltage between ionization probe and ground

(AC voltmeter Ri

≥ 10 MΩ)

Switching threshold (limit values):

Switching on (flame on) (DC ammeter Ri

≤ 5 kΩ)

Switching off (flame off) (DC ammeter Ri

≤ 5 kΩ)

Detector current required for reliable operation

Switching threshold in the event of poor flame during operation

(LED flashes green)

Short-circuit current between ionization probe and ground

(AC ammeter Ri

≤ 5 kΩ)

AC 115…240 V

≥ DC 1.5 µA

≤ DC 0.5 µA

≥ DC 3 µA

Approx. DC 5 µA

Max. AC 100…300 µA

¹) For applications outside the European Community, operation at mains voltage AC 230 V ±10 % is

ensured

With the same quality of flame, the detector current with the LME… may be another than that with the LMG… / LGB…

Flame supervision with ionization is accomplished by making use of the conductivity and rectifying effect of the flame. The flame signal amplifier only responds to the DC current component of the flame signal. A short-circuit between ionization probe and ground causes the burner to initiate lockout.

LME…

7101v01/0804

1

M

+

+

C

ION

Legend

C Electrolytic capacitor 100…470 µF; DC 10…25 V

ION Ionization probe

M Microammeter, Ri max. 5000

For detector currents, refer to « Technical data ».

10/23

Building Technologies

HVAC Products

CC1N7101en

29.06.2006

Technical data (cont´d)

Flame supervision with AGQ3… and UV detector QRA…

Ancillary unit AGQ3…

Legend

Mains voltage

Mains frequency

AC 230 V +10 % / -15 %

50…60 Hz

±6 %

Perm. cable length from QRA… to AGQ3… max. 20 m

(lay separate cable)

Perm. cable length from AGQ3… to LME… max. 2 m

Weight of AGQ3… approx. 140 g

Mounting position

Degree of protection optional

IP 40, to be ensured through mounting

Power consumption 4.5 VA

At mains voltage U

N

AC 220 V AC 240 V

Detector voltage at QRA… (with no load)

Terminal 3 off (refer to control sequence)

Terminal 3 on (refer to control sequence)

Detector voltage

Load by DC measuring instrument Ri > 10 M

Terminal 3 off (refer to control sequence)

Terminal 3 on (refer to control sequence)

DC current detector signals with UV detector

QRA…

Measurement at the UV detector QRA…

DC 400 V

DC 300 V

DC 380 V

DC 280 V

DC 380 V

DC 280 V

Min. required Max. possible

200 µA

DC 400 V

DC 300 V

500 µA

In connection with LME… burner controls, use of UV ancillary unit AGQ3… is mandatory.

(A) Correct functioning of aged UV cells can be checked as UV test with a higher supply voltage across the UV cell after controlled shutdown until terminal 3 on.

Connection diagram Measuring circuit for measuring the UV detector current

LME…

AGQ3…

12

2

3

1 br bl rt sw sw bl

L

GP/SB

R/W

L

N

(A) br bl rt sw sw bl

AGQ3…

+

QRA…

Measurement made at the UV detector

QRA…

C Electrolytic capacitor 100…470 µF; DC 10…25 V bl Blue

M Microammeter Brown

SB

R

W

Safety limit thermostat

Control thermostat or pressurestat

Limit thermostat or pressure switch gr Grey rt Red sw Black

Building Technologies

HVAC Products

11/23

CC1N7101en

29.06.2006

Technical data (cont´d)

Flame supervision with QRC…

(only LME23…)

Green LED for operational status indication

Measuring circuit for detector current

Detector current required

(with flame)

Min. 70 µA

Perm. detector current

(without flame)

Max. 5.5 µA

Possible detector current with flame (typically)

Max. 100 µA QRC…

The values given in the table above only apply under the following conditions:

— Mains voltage AC 230 V

— Ambient temperature 23 °C

Detector current in operation:

— Flame signal instable

— Green LED flashing

< 45 µA

Detector current in operation:

— Flame signal stable

— Green LED steady on

> 45 µA QRC…

The values given in the table above only apply under the following conditions:

— Mains voltage AC 230 V

— Ambient temperature 23 °C

2 1 12 LME…

bl sw

+ br 7101v02/1005

µA DC

Legend

µA DC DC microammeter with an internal resistance of

Ri = max. 5 k

Ω bl Blue sw Black br Brown

QRC1…

As an alternative to detector current measurement, the OCI400 / ACS400 diagnostics tool can be used. In that case, the DC microammeter is not required.

12/23

Building Technologies

HVAC Products

CC1N7101en

29.06.2006

Functions

Preconditions for burner startup

Undervoltage

Controlled intermittent operation

Reversed polarity protection with ionization

Control sequence in the event of fault

Resetting the burner control

Limitation of repetitions

(only LME11…)

• Burner control must be reset

• All contacts in the line are closed, request for heat

• Air pressure switch «LP» must be in its no-load position or CPI or wire link 2

• Fan motor or AGK25 is closed

• Flame detector is darkened and there is no extraneous light

• Safety shutdown from the operating position takes place should mains voltage drop below about AC 175 V (at U

N

= AC 230 V)

• Restart is initiated when mains voltage exceeds about AC 185 V (at U

N

= AC 230 V)

After no more than 24 hours of continuous operation, the burner control will initiate automatic controlled shutdown followed by a restart.

If the connections of live conductor (terminal 12) and neutral conductor (terminal 2) are mixed up, the burner control will initiate lockout at the end of «TSA».

If lockout occurs, the outputs for the fuel valves, the burner motor and the ignition equipment will immediately be deactivated (< 1 second).

Cause

Mains failure

Voltage below undervoltage threshold

Voltage above undervoltage threshold

Extraneous light during «t1»

Response

Restart

Safety shutdown

Restart

Lockout

Extraneous light during «tw»

No flame at the end of «TSA»

Loss of flame during operation

«LP» is welded in working position

Prevention of startup, lockout after 30 seconds at the latest

LME11…:

Max. 3 repetitions, followed by lockout at the end of «TSA»

LME2…:

Lockout at the end of «TSA»

LME11…:

Establishment of flame at the end of

«TSA»

→ Max. 3 repetitions

No establishment of flame at the end of

«TSA»

→ Lockout

LME2…:

Lockout

Prevention of startup, lockout after 65 seconds at the latest

«LP» is welded in normal position Lockout on completion of «t10»

No air pressure signal after completion «t10» Lockout

«CPI» contact is open during «tw» Prevention of startup, lockout after 60 seconds at the latest

In the event of lockout, the LME… remains locked and the red signal lamp (LED) will light up. The burner control can immediately be reset. This state is also maintained in the case of mains failure.

When lockout occurs, the burner control can immediately be reset. To do this, press the lockout reset button for about 1 second (< 3 seconds). The LME… can only be reset when all contacts in the line are closed and when there is no undervoltage.

If no flame is established at the end of «TSA», or if the flame is lost during operation, a maximum of 3 repetitions per controlled startup can be performed via «R», or else lockout will be initiated. Counting of repetitions is restarted each time a controlled startup via «R» takes place.

Building Technologies

HVAC Products

13/23

CC1N7101en

29.06.2006

Operation, indication, diagnostics

Operation

EK

Lockout reset button «EK…» is the key operating element for resetting the burner control and for activating / deactivating the diagnostics functions.

Red

Yellow

Green

The multicolor signal lamp (LED) in the lockout reset button is the key indicating element for visual diagnostics and interface diagnostics.

LED

Both «EK…» and LED are located under the transparent cover of the lockout reset button.

There are 2 diagnostics choices:

1. Visual diagnostics: Operational status indication or diagnostics of the cause of fault

2. Interface diagnostics: With the help of the OCI400 interface adapter and the

ACS400 PC software or flue gas analyzers of different makes (refer to Data Sheet

N7614)

Visual diagnostics:

In normal operation, the different operating states are indicated in the form of color codes according to the color code table given below. Interface diagnostics is activated by pressing the lockout reset button for at least 3 seconds (refer to Data Sheet N7614).

If, by accident, interface diagnostics has been activated, in which case the slightly red light of the signal lamp flickers, it can be deactivated by pressing again the lockout reset button for at least 3 seconds. The instant of switching over is indicated by a yellow light pulse.

Operating position

Operating position

Visual diagnostics

> 3 s

Interface diagnostics

PC / analyzer

Operational status indication

Legend

Color code table xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx

EK

During startup, status indication takes place according to the following table:

Color code table for multicolor signal lamp (LED)

Waiting time «tw», other waiting states

…………………………………..

Ignition phase, ignition controlled

Operation, flame o.k.

Off z  z  z  z  z  z

Flashing yellow

†……………………………………

Green

Operation, flame not o.k.

Extraneous light on burner startup

†  †  †  †  † 

Flashing green

† S † S † S † S † S

Green-red

Undervoltage

Fault, alarm

Error code output (refer to «Error code z S z S z S z S z S

S…………………………………..

S S S S

Yellow-red

Red

Flashing red table»)

Interface diagnostics

S S S S S S S S

Red flicker light

…… Steady on



Off

S z

†

Red

Yellow

Green

14/23

Building Technologies

HVAC Products

CC1N7101en

29.06.2006

Operation, indication, diagnostics (cont´d)

Diagnostics of the cause of fault

After lockout, the red fault signal lamp will remain steady on. In that condition, visual diagnostics of the cause of fault according to the error code table can be activated by pressing the lockout reset button for more than 3 seconds. Pressing the reset button again for at least 3 seconds, interface diagnostics will be activated (for more detailed information, refer to Data Sheet N7614).

The following sequence activates the diagnostics of the cause of fault:

Building Technologies

HVAC Products

Lockout position

Lockout position

Visual diagnostics

Flashing

Lockout position

Interface diagnostics

PC / analyzer

On

Reset

EK

EK

EK

> 3 s

Error code table xxxx xxxx xxxx xxxx xxxx xxxx xxxx xxxx xxxx xxxx xxxx xxxx

> 3 s

< 3 s

Red blink code of

signal lamp (LED)

«AL» at term. 10

Error code table

Possible cause

2 blinks hh

On No establishment of flame at the end of «TSA»

Faulty or soiled fuel valves

Faulty or soiled flame detector

Poor adjustment of burner, no fuel

Faulty ignition equipment

3 x blinks hhh — Loss of air pressure signal after «t10»

— «LP» is welded in normal position

4 blinks hhhh

5 blinks hhhhh

6 blinks

On Extraneous light when burner startup

— «LP» is welded in working position

On Free hhhhhh

7 blinks hhhhhhh

On Too many losses of flame during operation

(limitation of repetitions)

Faulty or soiled fuel valves

Faulty or soiled flame detector

Poor adjustment of burner

On Free 8 x blinks hhhhhhhh

9 blinks hhhhhhhhh

10 blinks hhhhhhhhhh

14 blinks

On Free

Off

On

Wiring error or internal error, output contacts, other faults

CPI contact not closed hhhhhhhhhh hhhh

During the time the cause of fault is diagnosed, the control outputs are deactivated

Burner remains shut down

External fault indication remains deactivated

Fault status signal «AL» at terminal 10, according to the error code table

The diagnostics of the cause of fault is quit and the burner switched on again by resetting the burner control. Press the lockout reset button for about 1 second (< 3 seconds).

15/23

CC1N7101en

29.06.2006

Connection diagram and control sequence LME11…

NT

µC control

EK

RESET

R / W

12

T

2

K1

K2/1

10

GP

AL

3

K2/2

7

K3

4

5

M Z

BV1

FSV

9

6

LP pa

11

8

ION

1

EK

STB

H

Si

L

N

SB / R

W / GP

AL

A

M

Z

BV1

LP

FS

EK2 tw t10 t1

B

t3 t3n

TSA

t4

C

D

12

10

3

1

8

7

4

6 11

7101a24e/0606

16/23

Building Technologies

HVAC Products

CC1N7101en

29.06.2006

Connection diagram and control sequence LME21…

NT

µC control

EK

RESET

R / W

12 2

T

K1

K2/1

10

GP

AL

3

K2/2

7

K3

4

K4

5

9

6

LP pa

FSV

11

8

ION

1

M Z

BV1

BV2

EK

STB

H

Si

L

N

7101a22e/0606

SB / R

W / GP

AL

A

M

Z

BV1

(LR) BV2

LP

FS tw t10 t1 t3

B

t3n

TSA

t4

C

D

12

10

3

7101d05/0206

7

4

5

6 11

1

Application examples only LME11… / LME21… / LME22…

The suitable wiring schemes are merely examples which must be verified in the individual case depending on application!

Burner without fan and without «LP» Only for burner with fan control via auxiliary contactor «HS» with

«LP»

2 3 11 6

12 2 3 11 6

*

AGK25

GP/SB

R/W

HS AGK25

LP

7101a17/0804

M

L

N

7101a18/0804

* Note: Different from LGB…

Building Technologies

HVAC Products

17/23

CC1N7101en

29.06.2006

Application examples

The suitable wiring schemes are merely examples which must be verified in the individual case depending on application!

Control of actuators of 2-stage or 2-stage modulating burners. Controlled prepurging «t1» with low-fire air volume. Same low-fire actuator position during startup and operation.

For information about actuators «SA»:

SQN3…: Refer to Data Sheet N7808

SQN7…: Refer to Data Sheet N7804

SQN9…: Refer to Data Sheet N7806

L

5

LR

12

SA

SB/R/W

4

7101a09/0705

BV1

RV

BV2

LME21…

12 2 10 8 3

AL

EK2

M

6 11 9 7

LP

GP/SB

R/W

Z

4

(*)

5

BV1

LR

HS

0 I

N L

Si

N 1 b1

2 b2 a

III

b a3

II

a b

MS

I

a b a2

B

6

7

5 a

IV b

A

4

(*) a b

V

BV2

3

*

1

ION

RV

LK

LKP

NL

KL

IV

III

Zu

II t1

I

IV

IV

III

LME21…

12 2 10 8 3 6 11 9 7 4 5

AL

EK2

LP

M Z

BV1

GP/

SB

R/W

LR

HS

0 I

N L

Si

N N 1 t

2

+

IV

a b

C3 a b

II

MS

I a b

D

+

SA

K2

5 3 6 a b

III

K1

C31

R32 R1 a b

V

BV2

4

1

ION

LK

SQN91.140… / 2-stage control SQN3…121… / 2-stage control

* Note

With 2-stage modulating burners (with gas regulation damper «RV»), «BV2» and the dotted connection between terminals (*) are not required.

LME21…

12

2 10 8 3 6 11 7 4 5 1

LP

ION

Z

AL

EK2

M

GP/

SB

R/W

BV1

LR

BV2

HS

0 I

N L

Si

N

8 4 a1

1 c1

5

3

2 b2

7

B

A b1 a2

I

M

II III

C

IV

6

LKP

NL

I

KL zu

II

III t1

TSA t4

I

IV IV

III t

SQN7…244 / 2-stage control

18/23

Building Technologies

HVAC Products

CC1N7101en

29.06.2006

Connection diagram and control sequence LME22… / LME23…

NT

µC control EK

RESET

R / W

12

T

2

GP

K1

K2/1

10

AL

FSV

3

K2/2

7

K3

4

K4

5

M

Z

BV1

BV2

9

6

LP pa

11

8

ION

1

SA

EK

Nur LME23…

12

2 br bl

1 sw

QRC

STB

H

Si

L

N

SB / R

W / GP

AL

A

I

SA

BV1

(LR) BV2

LP

FS

EK2

LK

M

Z tw t11 t10 t1 t12

B

t3 t3n

TSA

B´ C

t4

D

12

10

7101d02/0606

3

7

9

4

1

8

5

6 11

7101a02e/0606

Building Technologies

HVAC Products

19/23

CC1N7101en

29.06.2006

Application examples

The suitable wiring schemes are merely examples which must be verified in the individual case depending on application!

Control of actuators of 2-stage or 2-stage modulating burners. Controlled prepurging «t1» with nominal load air volume.

For information about actuators «SA»:

SQN3…: Refer to Data Sheet N7808

SQN7…: Refer to Data Sheet N7804

SQN9…: Refer to Data Sheet N7806

L

12 5

SB/R/W

LR

9

SA

4

7101a13/0804

BV1

RV

BV2

GP

R/W

LME22…

12 2 10

AL

EK2

8

M

3 6 11

9 5

7

LP

S1)

LR

Z

SB

HS

0

I

N

L

Si

N

1 8

2

R3

B

A a1 b1

7

I

M

II

5

6

III b2 a2

4

BV1

3

*

BV2

4 9

*

2)

LK

V

5

1)

RV

1

ION

LKP

NL

KL

Zu

II

III

I

t1

III

TSA t4

SQN3…151… or SQN3…251…

* Note

With 2-stage modulating burners (with gas regulation damper «RV»), «BV2» and the dotted connection between terminals (*) are not required.

LME22…

12 2 10 8 3

6

11 9 5 7 4 1

ION

EK2

LP

R/W

GP/SB

AL

LR Z

BV1

M t

HS

0 I

Si

N L

6 8 10

2

R3

1

R1

K2

C2

+

D

R2

+

K1

C1

I

MS

3

C3

III

II

7 9

RV

LK

SA

SQN90.220… / 2-stage modulating control

LME22…

R/W

12 2 10 8 3 6 11 5 9

LP

EK2

LR

GP/SB

AL

M

7

Z

4 1

ION

R/W

LME22…

12

2 10 8

3 6

11

9

5

7

LP

Z

EK2

GP/SB

AL M

1

LR

2

4

1

ION

BV1

BV1

BV2

BV2

HS

0 I

N L

Si

N

5

4 a1

1 3 2 8 6 7 c1 b2

C A b1 a2

I

M

II III

B

IV

SQN7…454 / 2-stage control

1 wire control

LKP

NL

I

KL zu

II t1

III

TSA t4

I

IV IV

III

HS

0 I

N L

Si t

N

4

5 1 a1

A

3 b2

2 8 6 7 b1 a2

I

M

II III

B

IV

SQN7…424 / 2-stage control

2 wire control

20/23

Building Technologies

HVAC Products

CC1N7101en

29.06.2006

Connection diagram and control sequence LME44…

NT

µA control EK

RESET

R / W

12

T

2

GP

K1

K2/1

10

AL

3

K2/2

7

K3

4

K4

5

M

Z

BV1

BV2

STB

L

N

H

Si

SB / R

W / GP

AL

A

M

Z

BV1

BV2

ZV1

CPI

FS tw t1´

B B´ C D

12

10

3

7 t3 t3n

TSA t4 t22

7101d06/0206

1

6

4

5

11

6

K5

11

ZV1

EK

FSV

8

ION

1

7101a20e/0606

Building Technologies

HVAC Products

21/23

CC1N7101en

29.06.2006

Legend

AL

CPI

EK…

EK2

FSV

GP

HS

Error message (alarm)

Closed Position Indicator

Remote lockout reset button (internal)

Remote lockout reset button

Flame signal amplifier

Gas pressure switch

Auxiliary contactor, relay

KL Low-fire

LKP

LP

Air damper position

Air pressure switch

22/23

Building Technologies

HVAC Products

I

ZV

A

B-B´

C

C-D

D

R

RV

SB

STB bl blue br brown sw black

Control thermostat / pressurestat

Gas regulation damper

Safety limit thermostat

Safety limit thermostat t Time

W Limit thermostat / pressure switch

Pilot gas valve

Start command (switching on by «R»)

Interval for establishment of flame

Operating position of burner reached

Burner operation (generation of heat)

Controlled shutdown by «R»

• Burner will immediately be shut down

• Burner control will immediately be ready for new startup

Cam I actuator t10 Specified time for air pressure signal t11 Programmed opening time for actuator «SA» t12 Programmed closing time for actuator «SA» t22 2 nd

safety time

TSA Ignition safety time

CC1N7101en

29.06.2006

Dimensions

LME…

Dimensions in mm

22

88

91

41,6

Ancillary unit AGQ3…

90,5

60

220 69 6

13

5,4

7101m01/0804

5,4

A B 6

Type reference

Dimensions

Building Technologies

HVAC Products

© 2006 Siemens Building Technologies HVAC Products GmbH

Subject to change!

23/23

CC1N7101en

29.06.2006

БЛОК УПРАВЛЕНИЯ И КОНТРОЛЯ LME 22… ДЛЯ ГАЗОВЫХ ГОРЕЛОК

Указание

При пуске, указание на состояние происходит на основании следующей таблицы:

рабочее состояние

Состояние

Время ожидания «tw», другие режимы ожидания

Фаза розжига, контролируемый розжиг

Функционирование, пламя в порядке

Функционирование, пламя не в порядке

Странный свет при пуске горелки

Недостаточное напряжение

Неисправность, аварийный сигнал

Появление кода ошибки

(см. «таблица кодов ошибок»)

Диагностирование интерфейса

Обозначения

…. Включ. фиксирован.

¡ Выключ.

Функционирование, индикация, диагностирование

(следует за предыдущей страницей)

Диагностирование причины неисправности

После блокировки, индикатор неисправности остаётся

гореть фиксированным цветом. В этих условиях можно

запустить процесс зрительного диагностирования

причины неисправности на основании таблицы кодов

ошибок. Для этогот нажмите в течение чуть больше 3

секунд кнопку восстановления. Повторно нажав кнопку

восстановления работы в течение, как минимум, 3

секунд, подключиться диагностирование интерфейса.

Красный мигающий код индикатора

(СВЕТОДИОДА)

2 мигания

l l

3 мигания

l l l

4 мигания

l l l l

5 миганий

l l l l l

6 миганий

l l l l l l

7 миганий

l l l l l l l

8 миганий

l l l l l l l l

9 миганий

l l l l l l l l l

10 миганий

l l l l l l l l l l

Во время выполнения диагностирования причины неисправности контрольные выходы отключены

— Горелка остаётся в отключенном положении

— Индикация внешней неисправности остаётся дезактивированной

— Сигнал состояния неисправности «AL» на терминале 10, на основании таблицы кодов ошибок

Для выхода из режима диагностирования причины неисправности и включения горелки сбросьте команду горелки.

Нажмите кнопку восстановления работы в течение около 1 секунды (< 3 секунд).

Таблица цветовых кодов для яркого многоцветного индикатора (СВЕТОДИОДА)

Цветовой код

¡………………………………………..

l

¡

l

¡

¡………………………………………..

n

¡

n

¡

n рn рn рn рn

p

p

l

l

l

р………………………………………..

p

p

p

¡

¡

¡

p p p p p p p p

p

Красный

Жёлтый

l

Зелёный

n

Положение

блокировки

Таблица кодов ошибок

«AL» на терминале

Возможная причина

10

Нет пламени по истечение «TSA» (безопасное время при розжиге)

— Топливные клапаны неисправны или грязные — Детектор пламени неисправен

или загрязнён

Включ.

— Неправильно выполнена регулировка горелки, нет топлива

— Устройство розжига неисправно

«LP» (воздушный прессостат) неисправен

— Сигнал давления воздуха отсутствует или неправилен по завершении «t10»

Включ.

— «LP» приварен в нормальном положении

Странный свет при пуске горелки

Включ.

Включ.

Тайм-аут «LP» — «LP» приварен в рабочем положении

Включ.

Не используется

Слишком большие потери пламени во время функционирования (ограничение

повторений)

Включ.

— Топливные клапаны неисправны или грязные

— Датчик пламени неисправен или загрязнён

— Неправильная регулировка горелки

Включ.

Не используется

Включ.

Не используется

Ошибка в электрических соединениях или внутренняя ошибка, контакты выхода,

Выключ.

другие неисправности

11 / 18

0006081362_200906

l

¡

l

¡

l

¡

n

¡

n

¡

n

¡

p

p

l

l

p

¡

Положение

блокировки

Зрительное диагностирование

Ошибка коды таблицы

Цвет

Выключ.

Жёлтый мигающий

Зелёный

Зелёный мигающий

Зеленый-красный

Жёлтый-красный

Красный

Красный мигающий

Мерцающий красный свет

Положение

блокировки

ПК/анализатор

Диагностирование

интерфейса

Сброс

Р

У

С

С

К

И

Й

Понравилась статья? Поделить с друзьями:
  • Logik 16s ошибки
  • Logging started ошибка
  • Logano g234 ошибка def
  • Logan ошибка p0141
  • Logamatic 2107 ошибка отопление def