Mitsubishi ошибка 7101

[7-9 Error Code Definitions and Solutions: Codes [7000 — 7999] ]

7-9-2

1. Error code definition

Capacity code setting error

2. Error definition and error detection method

Connection of incompatible (wrong capacity code) indoor unit or outdoor unit

3. Error source, cause, check method and remedy

Error source

Outdoor unit

(1) The model name (capacity code) set by the

Indoor unit

switch (SW2) is wrong.

*The capacity of the indoor unit can be con-

firmed by the self-diagnosis function (SW1

operation) of the outdoor unit.

Outdoor unit

(2) The model selection switches (SW5-3 — 5-8)

on the outdoor unit are set incorrectly.

HWE14040

Cause

SW5

Model

3

4

5

6

P200 model

OFF ON OFF OFF

P250 model

ON

ON OFF OFF

P300 model

OFF OFF ON OFF

P350 model

OFF ON

ON OFF

P400 model

ON

ON

ON OFF

P450 model

OFF OFF OFF ON

P500 model

ON OFF OFF ON

Check method and remedy

1) Check the model name (capacity code) of the in-

door unit which has the error source address set

by the switch (SW2 on indoor unit board).

When the model name set by the switch is differ-

ent from that of the unit connected, turn off the

power source of the outdoor and the indoor units,

and change the setting of the capacity code.

Check the setting for the model selection switch

on the outdoor unit (Dipswitches SW5-3 — 5-8 on

the outdoor unit control board).

7

8

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON OFF

— 227 —

GB

background image

— 34 —

6754

“Отклонение от нормы линии K – Отклонение от нормы датчика дренажа, срабатывание поплавкового реле уровня”

6755

“Отклонение от нормы линии K – Отклонение дренажного насоса от нормы”

6756

“Отклонение от нормы линии K – Образование льда на змеевике / срабатывание защиты от перегрева”

6757

“Отклонение от нормы линии K – Ошибка системы”

6758

“Отклонение от нормы линии K – Неисправность наружного блока, ошибка обмена данными между внутренним и наружным блоком”

6761

“Отклонение от нормы линии K – Отклонение термистора комнатной температуры от нормы”

6762

“Отклонение от нормы линии K – Отклонение от нормы термистора внутреннего змеевика, отклонение от нормы датчика температуры конденсации”

6763

“Отклонение от нормы линии K – Ошибка передачи/приема”

6764

“Отклонение от нормы линии K – Отклонение датчика дренажа от нормы”

6765

“Отклонение от нормы линии K – Отклонение дренажного насоса от нормы”

6766

“Отклонение от нормы линии K – Образование льда на змеевике / срабатывание защиты от перегрева”

6767

“Отклонение от нормы линии K – Неисправность наружного блока, ошибка обмена данными между внутренним и наружным блоком”

6771

“Отклонение от нормы линии K – Отклонение высокого давления от нормы, отклонение низкого давления от нормы”

6772

“Отклонение от нормы линии K – Функция термостата внутреннего блока, отклонение температуры на выходе от нормы,
срабатывание термостата корпуса, срабатывание максимальной токовой защиты”

6773

“Отклонение от нормы линии K – Срабатывание термостата пластины радиатора”

6774

“Отклонение от нормы линии K – Отклонение термистора наружного блока от нормы”

6775

“Отклонение от нормы линии K – Отклонение датчика давления от нормы, Ошибка обмена данными между внутренним и наружным блоком”

6776

“Отклонение от нормы линии K – Отключение по максимальному току”

6777

“Отклонение от нормы линии K – Ошибка системы”

6778

“Отклонение от нормы линии K – Норма”

6779

“Отклонение от нормы линии K – Избыток хладагента, отклонение напряжения от нормы, отклонение датчика CT от нормы”

6800

“Ошибка связи – Другие ошибки связи”

6801

“Ошибка связи – Ошибка связи V-контроль”

6810

“Ошибка связи – Ошибка связи пульта дистанционного управления блока”

6811

“Ошибка связи – Невозможно восстановить синхронизацию пульта дистанционного управления блока”

6812

“Ошибка связи – Сбой аппаратного обеспечения пульта дистанционного управления блока”

6813

“Ошибка связи – Ошибка определения значения разряда состояния связи пульта дистанционного управления блока”

6820

“Другие ошибки связи”

6821

“Другие ошибки связи – Линия передачи данных занята”

6822

“Другие ошибки связи – Отсутствует подтверждение связи”

6823

“Другие ошибки связи – Отсутствует отклик”

6824

“Другие ошибки связи – Ошибка приема данных”

6830

“Ошибка связи – Ошибка пульта дистанционного управления MA, ошибочное повторное задание адреса”

6831

“Ошибка связи – Отсутствует прием сигналов пульта дистанционного управления MA”

6832

“Ошибка связи – Невозможно восстановить синхронизацию пульта дистанционного управления MA”

6833

“Ошибка связи – Нарушение работы аппаратного обеспечения передачи/приема данных пульта дистанционного управления MA”

6834

“Ошибка связи – Ошибка определения стартового бита при обмене данными с пультом дистанционного управления MA”

6840

“Ошибка связи – Ошибка A-контроль, отсутствует обмен данными управления между внутренним и наружным блоком / ошибка приема данных”

6841

“Ошибка связи – Ошибка восстановления синхронизации обмена данными A-контроль между внутренним и наружным блоком”

6844

“Ошибка обмена данными A-контроль между внутренним и наружным блоком, неправильное подключение проводки
между внутренним и наружным блоком, чрезмерное количество внутренних блоков (более пяти)”

6845

“Ошибка связи – Ошибка обмена данными A-контроль между внутренним и наружным блоком, неправильное
подключение проводки между внутренним и наружным блоком (дистанционная связь, разъединение)”

6846

“Ошибка связи – Превышения максимального времени установления связи A-контроль между внутренним и наружным блоком”

7000

“Отклонение системы от нормы”

7100

“Отклонение системы от нормы – Ошибка общей производительности”

7101

“Отклонение системы от нормы – Код ошибки производительности”

7102

“Отклонение системы от нормы – Превышение максимального допустимого количества подключенных блоков”

7103

“Отклонение системы от нормы – Ошибка задания длины трубопроводов”

7104

“Отклонение системы от нормы – Ошибка задания высоты потолков”

7105

“Отклонение системы от нормы – Задан адрес выше 254”

7106

“Отклонение системы от нормы – Ошибка задания атрибута”

7107

“Отклонение системы от нормы – Ошибка настройки распределителя”

7108

“Отклонение системы от нормы – Ошибка настройки системы охлаждения”

7109

“Отклонение системы от нормы – Ошибка настройки соединения”

7110

“Отклонение системы от нормы – Неустановившийся режим соединения системы охлаждения / неустановившиеся данные соединения”

7111

“Отклонение системы от нормы – Входное/выходное оборудование не подключено / отклонение датчика пульта дистанционного управления от нормы”

7112

“Отклонение системы от нормы – Ошибка задания типа входов/выходов”

7113

“Отклонение системы от нормы – Оборудование не установлено”

Mitsubishi Electric Corporation was established in 1921 and worked its way to becoming a leading multinational electrical equipment and electronics manufacturer. With its headquarters in Tokyo, there was a time the company only focused on elevators, escalators, and high-end appliances such as air conditioners. While the company has grown, these three remain to be their top candidates.

When it comes to air conditioning the company offers ac systems such as room air conditioners, package air conditions, VRF systems, Ventilators, air curtains, and so on. Along with endless home and commercial appliances that start with toasters and ends with elevators and moving walks. With its main focus on air conditioners, Mitsubishi is one of the leading designers, manufacturers, and providers in the world. Yet, there are times when customers find themselves baffled by a random code on their appliance.

To help you out we have listed down some of the most common error codes for Mitsubishi Air conditioners. Start by noting down the error code, and match it using the list below. Once you have the error code you can understand the main issue with your Mitsubishi air conditioner, and draw out a solution that works to your advantage.

Mr Slim P Series (A)

Mr. Slim P-Series ductless heat pumps and air conditioners are compact yet powerful, offering unrivaled energy efficiency and design flexibility. Their advanced technology has been designed and tested to withstand the extremes of the Canadian climate in order to deliver a reliable and proven climate control system that you can trust all year round. With a variety of models to choose from, there’s a P-Series solution for any commercial application.

Mitsubishi Mr. Slim Air Conditioner Error Codes

Mitsubishi Mr. Slim Air Conditioner Error Codes – Meaning and Solution
Fault Codes Problem
A0 Duplicate address — Lossnay units attached with the same address — change addresses and reset the units power
A2 Hardware error of transmission processor (Lossnay) — check comms wiring, and for possible Lossnay board fault
A3 Line busy no data could be transmitted for 8 minutes — check A- M-Net connections (TB7 and TB3)
A6 Communication error with communication processor — Lossnay address not transmitted — check M-Net voltage
A7 No ACK signal — check A- M-Net wiring, range of transmission wiring exceeded or if faulty A- M-Net converter
A8 M-Net no response — check A- M-Net wiring, range of transmission wiring exceeded, faulty A- M-Net converter or if incorrect wire used for M-Net connection
EA Mis-wiring/loose inter-connecting cables. Noise interference
EB Mis-wiring/loose interconnecting cables. Noise interference. Wrong cable size/spec
EC Start-up time over. The unit has failed to initialise after power up. Noise interference. Wrong cable size/spec
ED Serial communication error. Comms error between boards on outdoor unit caused by M-Net interface board incorrectly fitted
EF Non-defined error code. Noise interference — power down outdoor unit for 30 seconds then switch back on
E0 Remote controller communication error — check wiring, connections and comms voltage. Also check Master/Slave settings if multiple systems are connected
E1 Remote controller issue — if grouped, check addressing. If twinned, check wired to master indoor only
E2 Remote controller issue — if grouped, check addressing. If twinned, check wired to master indoor only
E3 Remote controller issue — not transmitting — if grouped, check addressing. If twinned check wired to master indoor only
E4 Remote controller issue — not receiving — if grouped, check addressing. If twinned, check wired to master indoor only
E5 Remote controller issue — not receiving — if grouped, check addressing. If twinned, check wired to master indoor only
E6 Indoor/outdoor communication error, mainly caused by outdoor unit being powered up before indoor unit. Drain pump being wired into S1 and S2 causes interference
E7 Comms fault between I/C and O/C — check for condensate pump at I/C, reset power to O/C, check 12/24Vdc on S2 and S3 possible I/C board failure
E8 Comms failure indoor to outdoor (S2/S3) — check pumps wired in, check indoor isolator and re-power in the correct sequence i.e. indoor then outdoor
E9 Comms failure indoor to outdoor (S2/S3) — check pumps wired in, check indoor isolator and re-power in correct sequence i.e. indoor then outdoor
FA 51CM connector open — check thermal relay for disconnection or contact failure. Possible defective board
F1 Reverse phase detection — check power supply, try swapping 2 phases round. Possible defective board
F2 L3 phase open — check power supply, also check for open circuit protection devices
F3 63L open — check low pressure switch for disconnection or contact failure. Possible defective board
F4 49C open — compressor inner thermostat for open circuit or contact failure
F5 63H open — check high pressure switch for disconnection or contact failure. Possible defective board
F7 Phase detection circuit fault — faulty outdoor board
F8 No input detected at outdoor unit — outdoor board defective
F9 Two or more protection devices are open — check protection devices for disconnection or contact failure
P1 Return air thermistor fault (TH1) — check if TH1 disconnected or open or close circuit
P2 Liquid pipe thermistor fault (TH2) check if TH2 disconnected or open or close circuit
P4 Drain sensor fault — DS open or close circuit
P5 High condensate level — drain pump failure or blockage in the drain
P6 Freezing/Overheating of indoor unit heat exchanger — mainly caused by reduced air flow through indoor coil. Dirty filters. Fan motor problem. Blockage
P8 Abnormal pipe temperature — mainly caused by refrigerant leakage. Possibility that the thermistor mounted incorrectly
P9 TH5 condenser/evaporator thermistor open/close circuit. Disconnected from the board
U1 High pressure trip — outdoor fan failure, blocked coil, blockage in the system, blocked filters on indoor in heating etc
U2 High discharge temperature — compressor over heating due to lack of refrigerant, faulty thermistor, high ambient running conditions. Can also be caused by 49C (comp inner thermostat or external Klixon ) tripping
U3 Discharge thermistor fault
U4 Outdoor thermistor fault
U5 Inverter heat sink temperature too high (TH8) — check for lack of air flow around heat sink, no silicone paste, faulty thermistor (temperature can be read from service tool (or PAR21 on power inverter model))
U6 Compressor over current — carry out inverter output test and electrical checks to the compressor
U7 Low discharge superheat — check TH4 reading is correct. Check LEV operations
ho -For about 2 minustes following power-on, operation of the remote controller is not possible deu to system start-up. — Connector for the outdoor unit’s protection device is not connected. -Reserve or open phase wiring for the outdoor unit’s power terminal block (L1,L2,L3). -Incorrect wiring between indoor and outdoor units (incorrect polarity of S1,S2,S3). -Remote controller wire short.
FFFF No unit. Buzzer sound: Triple beep. Operation Led: No lit.
U0-UP Outdoor unit error.
F1-FA Outdoor unit error.
E0-E5 Signal error between remote controller and indoor units.
E6-EF Communication error between indoor and outdoor units.
No alarm history.

Mr Slim P Series (K)

Mitsubishi Electric Fault Codes

Mitsubishi Electric Fault Codes – Solutions

Mr. Slim P-Series is the ductless solution for demanding environments that require an efficient and reliable heating or cooling system. P-Series ductless systems are stylish, compact, and more attractive than traditional systems. Advanced technology also means your Mr. Slim ductless system will run more efficiently than a conventional unit, saving you from rising energy costs.

Fault Codes Problem
EO System transmission error — check for possible comms fault between I/C and R/C, could also be incorrect group or master/slave settings (check CN40, SW2 and SW6)
P1 TH1 fault — check return air thermistor (6.4K_ @ 20°C)
P2 TH2 fault — check coil/pipe thermistor (6.4K_ @20°C)
P3 System transmission error — check for possible comms fault between I/C and R/C, could also be incorrect group or master/slave settings (check CN40, SW2 and SW6)
P4 Drain sensor fault — check drain sensor resistance, connection and continuity
P5 Drain fault — unit has detected high condensate — check for blockage in drain or tray, pump failure or sensor fault
P6 Frost protection in cooling/Overheat protection in heating — detected by indoor coil sensor — general causes are lack of air flow or refrigerant charge problem
P7 System error — address setting fault — check CN40 SW2 and SW6. Potential board issue
P8 Abnormal pipe/coil temperature — no temperature change at indoor unit after 9 minutes of operation. General causes are outdoor unit tripped, problem with refrigerant charge or lack of air flow at the indoor unit. TH2 faulty or not mounted correctly
LD1 Reverse phase on mains supply — change phases around, check for potential board problem
LD2 Component open circuit — check CH, 52C, 21S4, SV, 63H and 26C for open circuit or disconnected
LD3 Outdoor coil thermister is open or short circuit may be disconnected or outdoor board fault
LD4 63H high pressure switch open — investigate high pressure causes, 63H switch disconnected
LD5 51CM overcurrent relay open — compressor locked or pulling too much current — check power supply
LD6 26C thermal switch open — check if refrigerant level low or if 26C is disconnected
LD7 Overheat protection — coil temp has exceeded 67°C — reduced airflow through condenser — check for fan motor problem or thermistor problem
LD8 Input circuit of outdoor board — replace the outdoor board

Multi City VRF

The CITY MULTI S series (for small applications) and Y series (for large applications) make use of a two-pipe refrigerant system, which allows for system changeover from cooling to heating, ensuring that a constant indoor climate is maintained in all zones.

Mitsubishi Multi City VRF AC Error Codes

Mitsubishi Multi City VRF AC Error Codes – How to Fix It?
Error Codes Problem
403 Comms fault between boards — check inverter error detail for which 2 boards, check transformer, bus voltage and inter-connecting cables
900 Lossnay unit in test run
1102 High compressor discharge temperature. Discharge temperature has exceeded 110°C or more. Short of refrigerant. Discharge thermistor
1111 Low pressure/temperature fault — check thermistors (TH2, TH3, TH4), gas charge, indoor fan, heat exchanger and filter
1112 Low pressure/temperature fault — check thermistors (TH2, TH3, TH4), gas charge, indoor fan, heat exchanger and filter
1113 Low pressure/temperature fault — check thermistors (TH2, TH3, TH4), gas charge, indoor fan, heat exchanger and filter
1202 Preliminary fault to 1102
1204 Preliminary heat exchanger gas temperature sensor fault — check thermistors 10a and 10b
1205 Preliminary thermistor fault (TH5)
1211 Preliminary thermistor fault (TH2)
1214 Preliminary thermistor fault (THHS)
1216 Preliminary thermistor fault (TH7)
1217 Preliminary thermistor fault (TH8)
1219 Preliminary thermistor fault (TH9)
1221 Preliminary thermistor fault (TH6)
1243 Preliminary thermistor fault (TH10)
1301 Low pressure fault (63L operation) low pressure sensor sensing less than 1 bar immediately before starting
1302 High pressure fault — check pressure in system for more than 29 bar (R407c) 38 bar (R410A). Check high pressure sensor against gauge pressure
1368 Pressure sensor fault (PS1) at BC — compare pressure reading on SW1 on O/C
1370 Pressure sensor fault (PS3) at BC — compare pressure reading on SW1 at O/C
1402 Preliminary fault to 1302
1500 System overcharge. Abnormal low compressor superheat — discharge thermistor TH4
1501 High compressor shell temp — check for shortage of gas, insufficient indoor index running (comms room units)
1505 Suction pressure abnormal — generated by low pressure sensor detecting a vacuum — check for blockage, closed valve or sensor fault
2500 Detecting lack of water flow on a water circuit
2502 I/C has water level in drip tray, when the unit was running in cooling (temperature sensors — check for open or closed circuit and operation of pump)
2503 I/C has water level in drip tray when the unit was running in cooling (float sensor — check for closed circuit on float switch and operation of pump)
2600 Water leak from humidifier
4100 Compressor over current protection on Mr Slim with M-net interface — check inverter or compressor
4101 Compressor over current protection on Mr Slim with M-net interface — check inverter or compressor
4102 Open phase fault — check power supply and noise filter for loss of phase, check wiring and fuses
4103 Reverse phase fault — check phase rotation, loss of phase through the noise filter, fuse blown and high pressure switch open at power on
4106 Transmission power supply fault — check wiring, high current, incorrect voltage on transmission line and/or M-Net board
4108 Over current protection on DOL compressor — check power supply, contactor and compressor
4115 Power supply abnormal — check power, fuses, connections and PCB
4116 Fan motor abnormal — check fan motor and board (relates to indoor unit or Lossnay unit)
4124 Thermal switch (49C) open circuit on Mr Slim on M-Net — reset and check pressures and air flow
4210 Compressor over current problem — check inverter balance. Compressor and inverter
4220 Low inverter board BUS voltage. Less than 289VdcDC is detected. — check mains supply
4225 Low DC voltage on Vdc on fan inverter — check CNVdc for 300Vdc on diode stack and check mains power supply to outdoor unit
4230 High temperature on heat sink on inverter — check for blockages in air duct, failure of INV fan or failure of thermistor
4235 Fan inverter heat sink overheat protection. Reduced airflow through heat sink. Fan motor problem. THHS thermistor problem
4240 Over current protection. If high current is detected for more than 10 minutes — check inverter balance. Reduced airflow through heat sink
4245 Over current protection. Possible ACCT current sensor fault. Should read 280 ohms between pins 1 & 2 and across pins 3 & 4
4250 Over current protection. Inverter IPM problem. Compressor lock — check inverter balance
4255 Inverter cooling fan problem — if high static fan is used then check that SW3-9 is on
4260 Preliminary inverter heat sink overheat protection. Reduced airflow through heat sink. Fan motor problem. THHS thermistor problem
5101 Thermistor fault at indoor/outdoor unit — check fault code address
5102 Thermistor fault at indoor/outdoor unit — check fault code address
5103 Thermistor fault at indoor/outdoor unit — check fault code address
5104 Thermistor fault at indoor/outdoor unit — check fault code address (indoor fault — check SW7-3 is off)
5105 TH5 open/short circuit — check if the TH is disconnected from the board
5106 TH6 open/short circuit — check if the TH is disconnected from the board
5107 TH7 open/short circuit — check if the TH is disconnected from the board
5108 TH8 open/short circuit — check if the TH is disconnected from the board
5109 TH9 open/short circuit — check if the TH is disconnected from the board
5110 TH10 open/short circuit — check if the TH is disconnected from the board
5111 BC box thermistor error — TH11 open/short circuit, disconnected from board/pipe
5112 BC box thermistor error — TH10 open/short circuit, disconnected from board/pipe
5113 BC box thermistor error — TH open/short circuit, disconnected from board/pipe
5114 BC box thermistor error — TH open/short circuit, disconnected from board/pipe
5115 BC box thermistor error — TH15 open/short circuit, disconnected from board/pipe
5116 BC box thermistor error — TH16 open/short circuit, disconnected from board/pipe
5201 Pressure sensor fault outdoor unit/BC box — check fault code address/SW1 pressure sensor readings
5202 Pressure sensor fault (PS2) in the BC box
5203 Pressure sensor fault (PS3) in the BC box
5300 A-Control UH fault — see Mr Slim fault code list
5301 Current sensor fault, ACCT or DCCT — check inv. error details
5401 Temperature sensor fault — check CN30 for humidity sensor
5701 Loose float switch connector — check switch, check CN4F on indoor unit
6201 TB7 transmission line communication error — check for voltage abnormality/short
6202 Transmission processor hardware error — check for noise/short on M-Net cable
6600 Repeat address fault — two or more units are assigned the same address — correct the repeated address
6601 Polarity setting error — no voltage or short circuit on the m-net transmission line
6602 Hardware error of transmission processor. Noise interference. Polarity problem on TB7
6603 Bus circuit busy — check if indoor unit, Lossnay unit or anything else has been wired into TB7, instead of TB3
6607 Communication issue — no response back from unit whilst system is operational
6608 Communication error — loss of voltage or noise entering the transmission line
6700 K control communication error — R22 type unit connected onto M-Net circuit comms error
6701 K control communication error — R22 type unit connected onto M-Net circuit comms error
6702 K control duplicate address error — two or more R22 type units connected onto M-Net circuit with the same address
6750 K control communication error — R22 type unit connected onto M-Net circuit comms error
6751 R22 R/A thermistor fault (P1)
6752 R22 frost protection at I/C (P6)
6753 Comms fault between O/C and I/C
6754 R22 drain fault (P5)
6755 R22 drain fault (P5)
6756 R22 frost protection at I/C (P6)
6757 System error
6758 Comms fault between I/C and O/C
6761 R22 R/A thermistor fault (P1)
6762 R22 TH2 fault check resistance (P2)
6763 R22 Comms fault between I/C and O/C
6764 R22 drain fault (P4)
6765 R22 drain fault (P5)
6766 R22 frost protection at I/C (P6)
6767 R22 comms fault between I/C and O/C
6771 K abnormality — high pressure abnormality or low pressure abnormality
6772 K abnormality — inner thermostat function, discharge temperature abnormality, shell thermostat function, over current protection
6773 K abnormality — radiator plate thermostat function
6774 K abnormality — outdoor thermistor abnormality
6775 K abnormality — pressure sensor abnormality, indoor/outdoor communication error
6776 K abnormality — over current shut-off
6777 K abnormality — system error
6778 K abnormality — normal
6779 K abnormality — refrigerant overcharge, abnormal voltage, abnormal CT sensor
6830 Comms fault between I/C and R/C check connections to MA R/C and check for 12Vdc check R/C not set sub controller
6831 MA R/C communication fault — check connections on TB15 or that the controller was removed while the I/C was powered
6832 MA controller comms fault — check cable length no bigger than 500m, check connection and type of cable used, check R/C not set sub on field settings
6833 MA controller comms fault check cable length no bigger than 500m, check connection and type of cable used, check R/C not set sub on field settings
6834 MA Controller comms fault — check cable length no bigger than 500m, check connection and type of cable used, check R/C not set sub on field settings
6840 A-Control E6/E8 fault — see Mr Slim fault code list
6841 A-Control E7/E9 fault — see Mr Slim fault code list
6844 A-Control EA fault — see Mr Slim fault code list
6845 A-Control Eb fault — see Mr Slim fault code list
6846 A-Control EC fault — see Mr Slim fault code list
7100 Over capacity — (R2 150% index exceeded) (Y 130% index exceeded)
7101 Capacity setting error — SW2 set wrong on indoors, SW5 on YHMA outdoor, (SW3-10 on older kit)
7102 Error in number of connected units — loss of M-Net voltage (short or break), no power to BC, wrong SW5 setting on box, wrong box type
7105 Address setting error — OC or BC addressed wrong
7106 Attribute setting error — SW3-1 setting on a GUF
7107 Port setting error — check if too much capacity on a single port, wiring SW2 setting, wrong SW14 setting or wrong units on a box when using multiple boxes
7110 Check SW5-7 is correctly set
7111 Remote control sensor fault — SW1 — 1 on and no controllers fitted or faulty remote controller
7113 Function setting error — wrong SW5 setting or wrong resistors fitted on YHM-A
7117 Model setting error — SW5 set wrong or wrong resistors in
7130 Incompatible equipment on M-Net — check split with MAC 399 wired onto the TB5 line TB5 line, not the TB7

Cassette AC

Mitsubishi inverter Cassette AC Error Codes

Mitsubishi inverter Cassette AC Error Codes – How To Troubleshoot and Fix?
Alarm Codes Solutions
P1 Intake sensor error
P2 Pipe (TH2) sensor error
P9 Pipe (TH5) sensor error
E6,E7 Indoor/outdoor unit communication error
P4 Drain sensor error/Float switch connector (CN4F) open
P5 Drain pump error
PA Forced compressor stop (due to water leakage abnormality)
P6 Freezing/Overheating protection operation
EE Communication error between indoor and outdoor units
P8 Pipe temperature error
E4,E5 Remote controller signal receiving error
Fb Indoor unit control system error (memory error, etc.)
PL Refrigerant circuit abnormal
E0,E3 Remote controller transmission error
E1,E2 Remote controller control board error
E9 Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
UP Compressor overcurrent interruption
U3,U4 Open/short of outdoor unit thermistors
UF Compressor overcurrent interruption (When compressor locked)
U2 Abnormal high discharging temperature/49C operated/ insufficient refrigerant
U1,Ud Abnormal high pressure (63H operated)/Overheating protection operation
U5 Abnormal temperature of heat sink
U8 Outdoor unit fan protection stop
U6 Compressor overcurrent interruption/Abnormal of power module
U7 Abnormality of super heat due to low discharge temperature
U9,UH Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error

Ecodan

Ecodan air source heat pumps use 1kW of electrical energy input and take 2.2kW of low temperature renewable heat energy from the air, producing a high efficient 3.2kW heat energy output. This heats refrigerant in the system which in turn heats water for domestic hot water and space heating.

Mitsubishi Ecodan Error Codes

Mitsubishi Ecodan Error Codes – Details and Solution
Fault Codes Problem
F3 Low pressure switch failure — check connection on the board and continuity of switch
F5 High pressure switch failure — check connection onto board and continuity of switch
F9 Both pressure switch contacts are open at the same time — check connection onto board and continuity of switch and for a potential board failure
EA Mis-wiring fault between FTC and Ecodan — check S1,S2,S3 also check voltages and comms
EB Mis-wiring fault between FTC and Ecodan — Check S1,S2,S3 also check voltages and comms
EC Unit cannot finish start up process — generally caused by a comms fault
U1 Ecodan high pressure fault — mainly caused by incorrect water flow rates — check with flow setter
U2 Ecodan high compressor discharge temperature — mainly caused by refrigerant shortage or dirty condenser
U3 Ecodan discharge thermistor problem — mainly caused by TH4 discharge thermistor — open/close circuit
U4 Open or close circuit Ecodan thermistors (TH3, TH32, TH33, TH6, TH7, TH8) — open or close circuit or disconnected from main board
U5 Inverter heat sink overheat protection (W50 and W85 models 77°C, HW140 model 95°C — reduced air flow through Ecodan — faulty fan motor
U6 Inverter/Compressor over current — system indicates possible IPM error
U8 Ecodan fan motor problem — mainly caused by DC fan motor being disconnected, connected or obstructed with the power on or possible main board fault
U9 Over voltage or under voltage — mainly caused by either CN2 or CN5 loose or disconnected or decrease of mains power supply
UD Overheat protection TH3 ≥ 70°C or 63HS ≥ 70°C saturation temperature
UF Compressor over current/Compressor lock — occurs within 30 seconds of compressor start
UH Abnormal running current — < 1A or > 40A detected during operation — check CN5 connections
UL Open circuit (63L )
UP Over current detected after 30 seconds of operation — do an inverter test to determine outputs balanced
E0 Transmitting Error PAR W21 — check refrigerant address on SW1 of Ecodan
E1 Faulty controller
E3 Transmitting Error (PAR W21) — check refrigerant address on SW1 of Ecodan
E4 Receiving Error (PAR W21) — check refrigerant address of SW1 on Ecodan
E5 Receiving Error (PAR W21) — check refrigerant address of SW1 on Ecodan
E6 Indoor/Outdoor communication error — mainly due to Ecodan being powered up before FTC(2)
E8 Indoor/Outdoor communication error — mainly due to Ecodan being powered up before FTC(2)
E9 Indoor/Outdoor communication error — mainly due to Ecodan being powered up before FTC(2)
EF Non-defined error code — noise interference — power down Ecodan for 30 seconds then switch back on
ED Serial communication fault between Ecodan main board and Ecodan inverter board — mainly due to loose CN2 or CN5 cable
P1 Flow temp sensor fault — TH1 not connected, short or open circuit
P6 Over heating at heat exchanger — lack of water flow, air in the system, flow rate incorrectly set, blockage or pump problem
P8 No temp change at plate heat exchanger — problem with flow rate (too high) — incorrect sizing of system
P9 TH5 Fault — TH5 not connected, short or open circuit, FTC not configured for heating only
PE Inlet water temp fault — TH32 is below 10°C whilst compressor is in operation — possible thermistor out of range, short of gas, incorrect sizing of radiator or problem in the water circuit (blockage, pump failure etc)

Hot Water Heat Pumps PWFY Series

Mitsubishi Hot Water Heat Pumps PWFY Series Error Codes

Mitsubishi Hot Water Heat Pumps PWFY Series Error Codes

12.5kW Hot Water Module. Flexibility to create very large systems. Can be installed in conjunction with City Multi VRF air conditioning. Available in one size: PWFY-P100VM-E-BU (12.5kW heating) which is modular to allow creation of larger solutions. Sanitary water heating has suitable applications in: hotels and motels, apartments, commercial kitchens and laundries, office buildings, food processing industry, heat recovery from air conditioning systems into sanitary water storage, and direct sanitary water heating is also possible.

Fault Codes Problem
403 Comms fault between boards — check between control board an inverter board
403 Comms fault between boards — check between control board an fan board
1102 High compressor discharge temperature — discharge temp has exceeded 115°C or more — check if short of refrigerant or discharge thermistor
1301 Low pressure fault — low pressure sensor sensing less than 1 bar immediately before starting
1302 High pressure fault — check system pressure exceded 32.3 bar, check high pressure sensor (63HS) against gauge pressure
2000 Pump interlock error — pump interlock open whilst system in operation
2134 Abnormal water temperature (TH6) has exceded 85°C
2135 Water source heat exchanger frozen (TH6) or (TH8) reading 2°C
4102 Open phase fault — check power supply and noise filter for loss of phase, check wiring and fuses
4115 Power supply abnormal — check power, fuses, connections and PCB
4220 Low inverter board BUS voltage — less than 200Vdc is detected during in inverter operation — check mains supply
4220 Bus voltage error PAM damage — replace the inverter board
4220 High bus voltage Vdc>380v — check power supply and possible faulty inverter board
4220 Replace inverter board
4230 High temperature (85°C) on heat sink on inverter — check for blockages in air duct, failure of INV fan failure of INV fan or failure of thermistor (THHS)
4250 Over current protection — inverter IPM problem or compressor lock — check inverter balance
4250 ACCT sensor over current detection 34.5A peak or 16A rms is detected — check the compressor for failure, or possible inverter board failure
5102 Thermistor TH22 failure
5103 Thermistor TH13 or TH23 failure
5104 Thermistor TH11 failure
5106 Thermistor TH6 failure
5108 Thermistor TH8 failure
5110 Thermistor THHS failure
5201 High pressure sensor fault — check the system pressure is >1 bar, check the operation of 63HS high pressure transducer
5202 Pressure sensor fault
5301 Current sensor fault, ACCT or DCCT — check inv. error details
5301 Low output current <1.5A rms whilst the inverter is in operation

Packaged Hot Water Heat Pump CAHV

Mitsubishi Packaged Hot Water Heat Pump CAHV Error Codes

Mitsubishi Packaged Hot Water Heat Pump CAHV Error Codes

45kW Packaged Hot Water Heat Pump. Can be combined to max. 70kW. “Flash-injection Circuit”, which is designed for our ZUBADAN CITY MULTI (air conditioning system for cold regions), is mounted in our new Hot Water Heat Pump. By utilizing our advanced “Flash-injection Circuit” and the latest high-efficiency compressor, Hot Water Heat Pump provides hot water upto 70°C, and produces less capacity drop at low outdoor temperature.

Error Codes Problem
AFSA Water supply cut-off (flow switch has been triggered) — check flow switch and wiring
AHP1 High pressure fault — check water flow, possible high pressure sensor fault LEV fault
AdSH Compressor crank case temperature of 10°C or less for 40 minutes while compressor in operation — check for possible failure of fan motor, low pressure sensor, compressor shell thermistor, high pressure sensor, discharge thermistor (TH1 TH5), LEV or SV2
1303 Low pressure protection low pressure below 6 bar within 30 sec of start up — possible failure of LP sensor, air inlet thermistor fault (TH4 TH8), suction temperature (TH2 TH6), LEV bypass check valve
1103 Compressor shell bottom temperature exceeded 80°C detected whilst compressor running
5109 Compressor shell thermistor faulty (TH3 TH6), LEV failure
5110 Outside temperature thermistor fault — check TH9
5112 Water inlet temperature — check TH10 main circuit
5111 Water inlet temperature — check TH12 sub circuit
5113 Outlet water temperature — check TH11 main circuit
5103 Outlet water temperature — check TH12 sub circuit
5107 Compressor shell temperature — check TH3 main circuit
5101 Compressor shell temperature — check TH7 sub circuit
5105 Discharge temperature — check TH1 main circuit
5102 Discharge temperature — check TH5 sub circuit
5106 Inlet temperature — check TH2 main circuit
5104 Inlet temperature — check TH6 sub circuit
5108 Air to refrigerant heat exchanger inlet temperature — check TH4 main circuit
5114 Air to refrigerant heat exchanger inlet temperature — check TH8 sub circuit
5115 Common return water when using multiple outdoors — check TH14
5117 Common return water when using multiple outdoors — check TH15
5118 High pressure sensor or high pressure fault — check 63HS sensor or 63H (hp switch)
7113 Low pressure sensor low or low pressure fault — check 63LS
7117 Model setting error 1 — mis-set switch
4115 Model setting error 2 — faulty Z21 resistor
A471 Power supply frequency fault — power supply frequency is not 50Hz or 60Hz
1104 Discharge temperature fault — 120°C detected during compressor operation — check water flow, pump, high pressure sensor fault or LEV fault
AC61 Power supply fault — check transmission power supply or if PCB faulty

MR Slim Operation Light Blinking

Mitsubishi Air Conditioner Operation Light Flashing

Mitsubishi Air Conditioner Operation Light Flashing – Fix it

Flashing of POWER lamp indicates abnormalities. Before taking measures, make sure that the symptom reappears for accurate troubleshooting. Self check table

When the indoor unit has started operation and the above detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.

Indicator lamp Solution
POWER lamp flashes. 0.5-second ON Mis-Wiring or serial signal. Outdoor unit does not operate. When the serial signal form the outdoor unit is not received for a maximum of 6 minutes.
POWER lamp lights up Out door control system. Outdoor unit does not operate. When it cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board. Check the blinking pattern of the LED on the inverter P.C. board or the outdoor lectronic control P.C. board.
POWER lamp flashes. 2-time flash Indoor coil thermistor. Room temperature thermistor. Indoor unit and outdoor unit do not operate. When the indoor coil or the room temperature thermistor is short or open circuit.
POWER lamp flashes. 3-time flash Indoor fan motor. Indoor unit and outdoor unit do not operate. When the rotational frequency feedback signal is not emit during the indoor fan operation. 
POWER lamp flashes. 5-time flash Out door power system. Indoor unit and outdoor unit do not operate. When it consecutively occurs 3 times that the compressor stops for overcurrent protection or start-up failure protection witth in 1 minute after start-up. 
POWER lamp flashes. 6-time flash Outdoor thermistors. Indoor unit and outdoor unit do not operate. When the outdoor thermistors short or open circuit during the compressor operation.
POWER lamp flashes. 7-time flash Out door control system. Indoor unit and outdoor unit do not operate. When it cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
POWER lamp flashes. 14-time flash Other abnonmality. Indoor unit and outdoor unit do not operate. An abnormality other than above mentioned is deteced. Confirm the abnormarity in detail using the failure mode recall function.

Split AC Timer Light Blinking

Trouble Contents
3 blinking-1 blinking Abnormality of comp. surface thermistor (TH32) and discharging temperature (TH4)
3 blinking-2 blinking Abnormal high pressure (High pressure switch 63H operated.)
3 blinking-3 blinking Abnormality of outdoor fan motor rotational speed. Protection from overheat operation(TH3).
3 blinking-4 blinking Compressor overcurrent breaking (Start-up locked). Compressor overcurrent breaking. Abnormality of current sensor (P.B.). Abnormality of power module.
3 blinking-5 blinking Open/short of discharge thermistor (TH4) and comp. surface thermistor (TH32). Open/short of outdoor thermistors (TH3, TH6, TH7 and TH8).
3 blinking-6 blinking Abnormality of heatsink temperature
3 blinking-7 blinking Abnormality of voltage
4 blinking-1 blinking Abnormality of room temperature thermistor (TH1). Abnormality of pipe temperature thermistor /Liquid (TH2). Abnormality of pipe temperature thermistor/Condenser-Evaporator.
4 blinking-2 blinking Abnormality of drain sensor (DS) Float switch(FS) connector open. Indoor drain overflow protection.
4 blinking-3 blinking Freezing (cooling)/overheating (heating) protection
4 blinking-4 blinking Abnormality of pipe temperature

Mitsubishi Split Air Conditioner Timer Light Blinking

Mitsubishi Split Air Conditioner Timer Light Blinking

Aircon RedLINK Codes

Error Codes Meaning
E0 27 Verify device temperature is within operating range. If within range for at least 30 minutes and problem persists, replace Remote Controller.
E0 91 Communication was established between wireless receiver and the indoor unit, but communication has been lost for 10 minutes. Check cable connection. Try replacing the cable.
E1 29 Attempting to connect incompatible wireless devices.
E1 34 Low signal strength. Move wireless device to a different location and try again.
E1 38 Make sure Connect light on wireless receiver is flashing and you are 2+ feet away from wireless receiver.
E1 54 Indoor unit does not support wireless receiver.

Troubleshooting

Mitsubishi Air Conditioning Troubleshooting

Mitsubishi Air Conditioning Troubleshooting

Even if these items are checked, when the unit does not recover from the trouble, stop using the air conditioner and consult your dealer.

Symptom: The unit cannot be operated.

Explanation & Check points:

  • Is the breaker turned on?
  • Is the power supply plug connected?
  • Is the ON timer set?

Symptom: The horizontal vane does not move.

Explanation & Check points:

  • Are the horizontal vane and the vertical vane installed correctly?
  • Is the fan guard deformed?
  • When the breaker is turned on, the horizontal vanes’ position will be reset in about a minute. After the reset has completed, the normal horizontal vanes’ operation resumes. The same is true in the emergency cooling operation.

Symptom: The airfl ow direction changes during operation. The direction of the horizontal vane cannot be adjusted with the remote controller.

Explanation & Check points:

  • When the unit is operated in COOL or DRY mode, if the operation continues with air blowing down for 0.5 to 1 hour, the direction of the airfl ow is automatically set to horizontal position to prevent water from condensing and dripping.
  • In the heating operation, if the airfl ow temperature is too low or when defrosting is being done, the horizontal vane is automatically set to horizontal position.

Symptom: Water leaks from the outdoor unit.

Explanation & Check points:

  • During COOL and DRY operations, pipe or pipe connecting sections are cooled and this causes water to condense.
  • In the heating operation, water condensed on the heat exchanger drips down.
  • In the heating operation, the defrosting operation makes ice forming on the outdoor unit melt and drip down.

Symptom: The display on the remote controller does not appear or it is dim. The indoor unit does not respond to the remote control signal.

Explanation & Check points:

  • Are the batteries exhausted?
  • Is the polarity (+, -) of the batteries correct?
  • Are any buttons on the remote controller of other electric appliances being pressed?

Symptom: The room cannot be cooled or heated sufficiently.

Explanation & Check points:

  • Is the temperature setting appropriate?
  • Is the fan setting appropriate? Please change fan speed to High or Super High.
  • Are the fi lters clean?
  • Is the fan or heat exchanger of the indoor unit clean?
  • Are there any obstacles blocking the air inlet or outlet of the indoor or outdoor unit?
  • Is a window or door open?
  • It may take a certain time to reach the setting temperature or may not reach that dependingon the size of the room, the ambient temperature, and the like.

Symptom: The air from the indoor unit smells strange.

Explanation & Check points:

  • Are the fi lters clean?
  • Is the fan or heat exchanger of the indoor unit clean?
  • The unit may suck in an odor adhering to the wall, carpet, furniture, cloth, etc. and blow it out with the air.

Symptom: Weekly timer does not operate according to settings.

Explanation & Check points:

  • Is the ON/OFF timer set?
  • Transmit the setting information of the weekly timer to the indoor unit again. When the information is successfully received, a long beep will sound from the indoor unit. If information fails to be received, 3 short beeps will be heard. Ensure information is successfully received.
  • When a power failure occurs and the main power turns off, the indoor unit built-in clock will be incorrect. As a result, the weekly timer may not work normally.
Electrical Wiring Diagram

Mitsubishi Electric Mr.Slim ac electrical wiring diagram

Mitsubishi Electric Mr.Slim ac electrical wiring diagram
Refrigerator Diagram

mitsubishi electric mr slim ac refrigerator diagram

mitsubishi electric mr slim ac refrigerator diagram
Manuals PDF

Mitsubishi Air Conditioning Service Handbook PDF

Mitsubishi Air Conditioning Service Manual PDF

Mitsubishi Electric MRCH1 Remote ControllerOperating Manual PDF

Mitsubishi Electric Split AC Manual MSZ-AP22VGD PDF 

Mhk1 Wireless Remote Receiver Kit Manual PDF

MIFH1, MRCH1, MCCH1, MOS1 Controller Kit Installation Manual PDF

Mitsubishi Air Conditioning Error Codes PDF – R410A Systems

  • Author
  • Recent Posts

Danny Reese

Regarding error and fault codes, we believe sharing knowledge is the best way to help everyone. That is why we established ACErrorCode.com, to give you every bit of info you need as a customer. HVAC Expert Contact: dannyreese@acerrorcode.com

Danny Reese

*If you can’t find the code you’re looking for on our site, please let us know, and we’ll update our database as soon as possible.

Error Расшифровка Русский перевод
P1 Intake sensor error Ошибка датчика на входе
P2 Pipe (TH5) sensor error Ошибка датчика теплообменника ТН5 (по схеме)
P4 Drain sensor error/Float switch connector (CN4F) open Переполнение дренажного поддона, или обрыв поплавкового датчика CN4F
P5 Drain pump error Ошибка дренажной помпы
P6 Freezing/Overheating protection operation Ошибка по обмерзанию или перегреву
P8 Pipe temperature error
P9 Pipe (TH2) sensor error Ошибка по датчику теплообменника ТН2
PA Forced compressor stop(due to water leakage abnormality) Принудительная остановка компрессора (из-за переполнения дренажной системы)
E0, E3 Remote controller transmission error Нет связи с пультом управления
E1, E2 Remote controller control board error Неисправна плата пульта управления
E4, E5 Remote controller signal receiving error
E9 Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) Нет связи между внутренним и внешним блоком (Ошибка на внешнем блоке)
EE Communication error between indoor and outdoor units Отсутствует межблочная связь между внутренним и внешним блоками
U1,Ud Abnormal high pressure (63H worked)/Overheating protection operationс Высокое давление по датчику 63Н, или защита от перегрева
U2 Abnormal high discharging temperature/49C worked/insufficient refrigerant Сработал датчик 49С, очень низкое давление нагнетания, недостаток хладагента
U3, U4 Open/short of outdoor unit thermistors Обрыв, короткое замыкание термодатчика внешнего блока
U5 Abnormal temperature of heat sink Температура конденсатора не соответствует норме
U6 Compressor overcurrent interruption/Abnormal of power module Компрессор принудительно остановлен по токовой перегрузке, неисправен силвой модуль
U7 Abnormality of super heat due to low discharge temperatureAbnormal high discharging temperature/49C worked/insufficient refrigerant Сработал датчик 49С / очень низкое давление нагнетания / недостаток хладагента
U8 Outdoor unit fan protection stop Двигатель вентилятора внешнего блока остановлен
U9, UH Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error Повышенное / пониженное напряжение питания, неисправность токового датчика
UF Compressor overcurrent interruption (When compressor locked) Компрессор остановлен из-за токовой перегрузки, компрессор заклинило
UP Compressor overcurrent interruption Остановка компрессора из-за перегрузки по току
Fb Indoor unit control system error (memory error, etc.) Ошибка платы управления внутреннего блока (EEPROM и т.д.)

Определить ошибку в бытовых сплит системах можно по миганию индикаторов на панели внутреннего блока.

Получить расшифровку всех возможных кодов холодильного оборудования Mitsubishi Electric можно на сайте:

Язык оригинальной документации — английский.

Компания Mitsubishi Electric разработала программу для телефонов с помощью которой можно получить расшифровку кода ошибок.

 bork


Error

Расшифровка

Русский перевод

P1

Intake sensor error

Ошибка датчика на входе

P2

Pipe (TH5) sensor error

Ошибка датчика теплообменника ТН5 (по схеме)

P4

Drain sensor error/Float switch connector (CN4F) open

Переполнение дренажного поддона, или обрыв поплавкового датчика CN4F

P5

Drain pump error

 Ошибка дренажной помпы

P6

Freezing/Overheating protection operation

Ошибка по обмерзанию или перегреву

P8

Pipe temperature error

P9

Pipe (TH2) sensor error

Ошибка по датчику теплообменника ТН2

PA

Forced compressor stop(due to water leakage abnormality)

Принудительная остановка компрессора (из-за переполнения дренажной системы)

E0, E3

Remote controller transmission error

Нет связи с пультом управления

E1, E2

Remote controller control board error

Неисправна плата пульта управления

E4, E5

Remote controller signal receiving error

E9

Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)

Нет связи между внутренним и внешним блоком (Ошибка на внешнем блоке)

EE

Communication error between indoor and outdoor units

Отсутствует межблочная связь между внутренним и внешним блоками

U1,Ud

Abnormal high pressure (63H worked)/Overheating protection operationс

Высокое давление по датчику 63Н, или защита от перегрева

U2

Abnormal high discharging temperature/49C worked/insufficient refrigerant

Сработал датчик 49С, очень низкое давление нагнетания, недостаток хладагента

U3, U4

Open/short of outdoor unit thermistors

Обрыв, короткое замыкание термодатчика внешнего блока

U5

Abnormal temperature of heat sink

Температура конденсатора не соответствует норме

U6

Compressor overcurrent interruption/Abnormal of power module

Компрессор принудительно остановлен по токовой перегрузке, неисправен силвой модуль

U7

Abnormality of super heat due to low discharge temperatureAbnormal high discharging temperature/49C worked/insufficient refrigerant

Сработал датчик 49С / очень низкое давление нагнетания / недостаток хладагента

U8

Outdoor unit fan protection stop

Двигатель вентилятора внешнего блока остановлен

U9, UH

 Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error

Повышенное / пониженное напряжение питания, неисправность токового датчика

UF

Compressor overcurrent interruption (When compressor locked)

Компрессор остановлен из-за токовой перегрузки, компрессор заклинило

UP

Compressor overcurrent interruption

Остановка компрессора из-за перегрузки по току

Fb

Indoor unit control system error (memory error, etc.)

Ошибка платы управления внутреннего блока (EEPROM и т.д.)

Код EA
Неправильный монтаж внутреннего / наружного блока. Проверить межблочное соединение, электрическая цепь. Обрыв цепи.
Код Eb
Неправильный монтаж, отключения, сработала защита.
Код ЕС
Ошибка запуск по времени, в течение 5 мин. Выключить питание, обесточить сплит систему Mitsubishi Electric, вынуть батарейки из дистанционного пульта управления. Далее проделать операцию через 5 мин. в обратном порядки.
Все настройки сплит системы вернутся к заводским по- умолчанию.
Неправильный монтаж внутреннего / наружного блоков как правило ведёт к поломкам сплит системы..
Mitsubishi Electric инверторного типа, таблица неисправностей.
Обрыв связи.
Код E6
Ошибка соединений внутреннего / наружного блока, датчик приёма сигнала (нет приема сигнала).
Сигнала нет, замыкание.
Код E7
Ошибка внутреннего / наружного ошибка блока передачи (ошибка передачи).
Сигнала нет, замыкание.
Код E8
Ошибка, не работает датчик приёма, проверить приходит ли питание к датчику.
Обрыв цепи.
Код E9
Ошибка внутреннего / наружного ошибка межблочного соединения.
Обрыв цепи. Сигнала нет.
Код E0 Нет сигнала от пульта управления (прием сигнала)
Поменяйте батарейки пульта ду.
Код E3
Не правильный сигнал. ПУ кондиционера не правильно формирует сигнал.
Исправить, — См. Код ЕС
Код Е4
Проверить межблочное соединение, целостность датчиков температуры и давления.
Код E5
Проверить напряжение в сети. Возможны сбои в работе оборудования.
Код EF
Ошибка M-NET, — нет сигнала
Проверить межблочное соединение, обрыв соединений или плохой контакт.
Код Эд
Последовательность формирования сигнала нарушена. Сбой шагового- искателя.
Исправление, — см. Код ЕС Mitsubishi Electric, — вернуться к заводским настройкам кондиционера по умолчанию.
Код P1
Не работает датчик температуры Mitsubishi Electric (TH1).
Проверить датчик на целостность. Нарушена герметичность датчика, датчик и соединительный кабель настолько грязные и мокрые, что замыкают. При необходимости заменить датчик
Код P2
Датчик обморожения внутреннего блока, сработал датчик.
Грязный внутренний блок, плохое прохождение воздуха, вследствии обморожения. Проверить контур сплит системы Mitsubishi Electric на утечку газа.
Обморожение как правило начинается из-за недостатка газа или кондиционер требует к себе внимания, — профилактики.
Код P4
Проверить дренаж, слив, — сработал датчик переполнения ванны. Забит слив.
Код P5
Не работает сток, двигатель дренажа работает в холостую.
Ремонтируем сплит системы, кондиционеры Mitsubishi Electric до 2006 года выпуска
Коды ошибок. Mitsubishi Electric до 2006 года выпуска
Код P6
Ошибка, —
Замораживание / сработала защита от перегрева. Проверить контур сплит системы на утечку газа.
Обморожение как правило начинается из-за недостатка газа.
Код P8
Температурный режим вышел за заданные параметры, проверить датчик температуры на целостность. Сопротивление датчика должно быть в пределах 16 Ом.
Код P9
Датчик температуры замкнут.
Проверить датчик на целостность. Нарушена герметичность датчика, датчик и соединительный кабель настолько грязные и мокрые, что замыкают(TH5)
Замыкание.
Код F1
Проверить фазировку на двигателе компрессора наружнего блока кондиционера   Mitsubishi Electric.
Код F2
Ошибка L3 обрыв фазы.
Код F3
Ошибка 63L нет сигнала с платы управления.
проверить качество формирования сигнала, проверить датчики на целостность, возможная причина, 0 — подгорели контакты реле включения, залипания контактов, неисправность пружины реле…
Код F4
Ошибка 49C разъем разомкнут.
Код F9
Ошибка, — разъем 2 или более нет сигнала.
Код FA
Ошибка L2- обрыв фазы или 51см разъем разомкнут.
Код F7
Ошибка последовательности фаз шлейфа, проверить состояние кабеля.
Код F8
Сбои в питании, проверить напряжение в сети.
Код U2
Высокие температурные параметры работы компрессора, сработала защита от перегрузки.
Код U2
Ошибка
Внутренний термостат (49C) проверить причины сработки, проверить рабочие и пусковые токи компрессора кондиционера, напряжение питания, количество и давление газа фреона в холодильном контуре сплит системы.
Код U1
Датчик давления (высокое давление swicth 63H сработал)
Код U1
Фатальная ошибка.
Код УП
Ошибка
Высокое давление в системе, шаровой кран закрыт, залом меж.блочной трассы, не работает перепускной клапан, задир, залип…Постучать тук-тук-тук.
Код UL
Низкое давление в системе, сработал датчик.
Код Ud
Сработала тепловая защита компрессора кондиционера. Смотреть исправление и причины, — код U2
Код U6
Перегрузка компрессора. Смотреть исправление ошибки и причины, — код U2
Код UA
Ошибка компрессора. Проверить пусковое реле.
Код UF
Нет сигнала блокировка пуска. Фатальная ошибка, неисправно всё, начинай проверку сначала.
Например смотреть неисправности тык
а) неисправности электрической части, системы эл. питания и управления кондиционером. рис. 1.
б) неисправности холодильного контура, рис. 2.
Блокировка пуска компрессора, неверные входящие и разрешающие пуск параметры.
Код UH
Текущая ошибка датчика.
Код U3
Проверить конденсатор, недостаточное сглаживание по току, варистор неисправен.
Код U4
Не работает датчик температуры наружнего блока кондиционера.
Коды P1-P8 | Mitsubishi Electric .Slim K-контроль

Дисплей на пульте дистанционного управления Mitsubishi Electric.
Горит лампочка светодиода E0
Диагностика неисправности приема / передачи сигнала ошибки.
Сигнала нет, замыкание датчика.
Горит лампочка светодиода P1
Диагностика неисправности датчиков всасываемого воздуха, ошибка.
Сигнала нет, замыкание.
Горит лампочка светодиода P2
Диагностика неисправности труб, датчик T- ненормальный.
Сигнала от датчика нет, замыкание.
Горит лампочка светодиода P4
Датчика Drain ненормальный, выбросить в мусорное ведро.
Горит лампочка светодиода P5
Неисправное соединение, — утечка переполнения защиты механизма.
Сигнала нет, замыкание.
Горит лампочка светодиода P6
Диагностика неисправности Abnomality датчик обморожения / защита от перегрева режиме.
Сигнала нет, замыкание.
Горит лампочка светодиода P3
Диагностика неисправности системной ошибки (передача / прием сигнала).
Сигнала нет, замыкание.
Горит лампочка светодиода P7
Диагностика неисправностей Системная ошибка (адрес)
Сигнала нет, замыкание.
Горит лампочка светодиода P8
Диагностика неисправности Открытый неисправности блок
Обрыв цепи.
Подробнее: Ошибки P1, P2, P3, P4, P5, P6
Mitsubishi Electric. — Mr.Slim K-контроль PUH-EK

Наружный блок
LED ON статус операции =
Светодиодная вспышка = Проверка кода diplay
Горит лампочка светодиода LD1
LED ON Компрессор директивы
Светодиодная вспышка последовательности фаз обнаружить
Горит лампочка светодиода Mitsubishi Electric LD2
LED ON Отопление директивы
Светодиодная вспышка Открытая фаза обнаружения
Горит лампочка светодиода LD3
LED ON Во время операции 63H1
Светодиодная вспышка трубы датчика короткий / открытые
Горит лампочка светодиода LD4
LED ON компрессора
Светодиодная вспышка высокого давления swicth (63H2) операции.
Горит лампочка светодиода lD5
LED ON Открытый вентилятор включаются
Светодиодная вспышка от перегрузки по току реле (51 см) операции.
Горит лампочка светодиода LD6
LED ON 4-ходовой клапан ON
Светодиодная вспышка тепловых swicth- светодиодов (26C) операции.
Горит лампочка светодиода LD7
LED ON Перепускной клапан Mitsubishi Electric ON
Светодиодная вспышка Термистор (TH3) защита от перегрева.
Горит лампочка светодиода LD8
LED ON Нагреватель картера ON
Светодиодная вспышка Mitsubishi Electric, — пассивный ввод.

С более подробным описанием параметров систем кондиционирования Mitsubishi Electric вы можете ознакомиться в этой статье.

«Если у вас есть возможность явить милосердие, не пропускайте вперед даже учителя.

Понравилась статья? Поделить с друзьями:
  • Mitsubishi ошибка 0304
  • Mitsubishi tu85sa коды ошибок
  • Mitsubishi srk40hg коды ошибок
  • Mitsubishi srk28hg ошибки
  • Mitsubishi pajero ошибка p0174