User Manual of STC-9200 Thermostat
Refrigeration & Defrosting & Evaporator Fan Controller
The STC-9200 temperature controller controls the power supply status of the connected Refrigeration
device, the defrosting unit, and the Evaporator Fan, typically suited to an oversized freezer room.
1.
Package
Controller: 1PCS
Sensor: 2PCS
2.
Specification
Input Power
220V AC ± 10% 50/60HZ; (12/24/48/110V Option)
Maximum current
8A (Default) under 250V AC
Thermistor / Sensor
NTC, 25°C /10 KΩ, the sensor cable 200cm
Protection Class
IP65 to the front panel
Storage
-10°C ~ 60°C, RH<90%, without condensation
Temperature Range
Measurable: -50.0°C ~ +50.0°C; Controllable: -50.0°C ~ +50.0°C
Resolution
0.1°C
Accuracy
± 1°C from -40°C to +50°C; ± 2°C in other range
Power Consumption
≤ 3W
3.
Environmental Information
The package’s material is 100% recyclable. Just dispose of it through specialized recyclers.
The electro components can be recycled if it is disassembled for specialized companies.
Please do not burn or throw the controllers in domestic garbage. Observe the respective law in your
region concerning the environmentally responsible manner of disposing of its devices.
4.
Appearance & Operation
4.1. Front Panel & Operation
Under normal status, the screen shows room sensor temp.
A.
Hold the
for 3s to enter/exit the user setting
interface, and the user can change the target
temperature and the hysteresis here.
B.
Hold the
key and the
for 10s to lock/unlock the admin menu:
OFF = unlock, editable
ON = locked, only can check the value, not editable.
C.
Hold the
and the
keys for 10s to enter admin interface; Press the
current data, and press the
data and back to menu list; If without operated in 10s, the new data will be auto-saved.
D.
Hold the
for 3s to check the defrost temp.;
E.
Hold the
for 3s to trigger the forced refrigeration mode manually (must past the
compressor delay time); do it again to quit.
F.
Hold the
for 3s to trigger the forced defrosting mode manually (must past the defrost
delay time); do it again to enter defrosting water dripping status.
(Version 21.08.04GEN)
Clips: 2PCS
Manual:1 PCS Waterproof Cover: 1PCS
key at the same time
or
key to change the data; Press the
Haswill Electronics
4.2. Indicator / Character in Display
Indicator
Meaning
On
Hide
Wink
Time Delay
Fast Wink
Manually Refrigeration
4.3. Dimensions & Installation
4.4. Wiring Diagram
A.
10K NTC sensor, need not distinguish + or -.
B.
The input voltage must be within the voltage value marked in the diagram ±10% value.
C.
Suggest Load Power ≤
4.5. Copykey (Optional)
A.
Upload to Controller
1)
Insert the Copykey, Press the
2)
Now Press the
3)
Shut down the controller and then pull out the Copykey.
B.
Download from Controller
to check
1)
Assure controller being shut down and insert the Copykey, then starting up
again to save
2)
The controller will scan the Copykey and download data automatically, shows «DOL»
when downloading, and shows «END» once finished.
3)
Restart the controller; it will work according to the new data.
Attention:
Part of the parameters will be executed in the next cycle; please power off the controller and
power back to start a new cycle for running by the new data without a wait.
If a parameter in the Copykey exists error or in the wrong format, the display shows ERR.
1 / 2
Compressor status
Setting Status
Fan Status
Working
Setting
Working
Stop
Normal
Stop
N/A
Time Delay
N/A
N/A
1)
Mount size: 71*29*85 mm (W*H*D);
2)
Detach the slide fasteners, put the controller
into the hole, and wire it.
3)
Install the fasteners and the waterproof
cover.
Voltage∗ Max current of Relay
Factor
key, the display shows «UPL»;
key to upload data will show «END» once finished;
Defrosting status
Working
Stop
Dripping Water
Manually Defrosting
- Обзoр
- История версий
- Обсуждение
-
Руководство по эксплуатации контроллера STC-9200
Микропроцессор ( холодильный контроллер ) STC 9200 — это электромагнитный пускатель с цифровым дисплеем, способный управлять однофазным компрессором мощностью ≤1/2л.с.
В контроллере все программы сохраняются на флеш-карту, чем и обусловлены быстрые запуск и работа устройства. Объем интегрированной памяти ограниченный. Микропроцессор же использует внешнюю энергонезависимую память.
Контроллер имеет интегрированный регулятор напряжения, поэтому для нормальной работы ему понадобится только одно значение – внешнее напряжение. А для микропроцессора необходимо несколько значений – напряжения для периферии, ядра устройства, портов и др.
5.
Configurations
5.1. Code and Function Menu
Hold the
+
keys at the same time for 10s to enter the Admin Interface;
The codes SET and HY (F1 and F2) are user menu; others are admin menu, ref 4.1 A & C
Cate.
EN
F
Function
SET
Temp.
SP (Temperature Set-Point)
F1
HY
Temperature Hysteresis / Return Difference
F2
US
Upper limit for SP
F3
LS
Lower limit for SP
F4
Delay Time for Compressor
AC
F5
Delay Time for Defrosting (only for hot gas TDF/F10)
IDF
Defr.
Cycle / Interval Time
F6
MDF
Lasting Time
F7
Defrost
DTE
Stop Temperature
F8
FDT
Water dripping Time
F9
TDF F10
Defrosting Mode:
EL/0
Electric-Heating.
HTG/1
Hot Gas from the compressor.
DCT F11
Count mode of defrost cycle:
RT/0
Cumulative time from the controller power on;
COH/1
Cumulative time of the compressor working.
DFD F12
Display mode when defrosting:
RT/0
Shows the room sensor temperature display;
Shows the evaporator sensor temp. (continue
IT/1
showing 10 minutes once defrosting over)
FNC F13
Fan
Fan output modes when
Fan Starts by F14/FOT, Stop by F16/FST;
CTR/0
continuous working except defrosting begins;
O-N/1
FOD is when the fan starts later than the
C-N/2
compressor; the fan stops if defrosting begins.
FOT F14
Defrost sensor Temperature for Fan Starts
FOD F15
Time delay seconds for fan
is the period for the fan to start earlier than
< 0
FOD
the compressor starts; the fan stops if defrosting
begins.
≥ 0
The fan was controller by F13/FNC
F5T F16
Defrost sensor Temperature for Fan Stops
ALU F17
Alarm
Room sensor Temperature
ALL F18
to Trigger Alarm
ALD F19
Cali.
OT
F20
Temperature Calibration = Real Temperature — Measured
The EN code menu and the F code menu are same, just for satisfy different clients.
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z 1 2 3 4 5 6 7 8 9 °C
Min
Max
LS
US
1.0
25.0
F01
50.0
-50.0
F01
0
50
0
120
0
255
-50.0
50.0
0
10.0
EL/0
HTG/1
RT/0
COH/1
RT/0
IT/1
≥ 0
FOD
CTR/0
C-N/2 CTR/0
-50.0
F5T/F16
-255
255
FOT/F14
50.0
Upper Limit
ALL
50.0
Lower Limit
-50.0
ALU
0
Time delay
99
-10.0
10.0
Haswill Electronics
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z 1 2 3 4 5 6 7 8 9 °C
5.2. When will the Defrosting Starts / Stops?
A. Defrost relay will close/on when reaching all the below conditions
The time should later than: the compressor last stops moment + AC/F5 if the defrosting
Default Unit
Mode was thermal air / Hot Gas (TDF/F10 = HTG).
°C
-5.0
The defrost sensor temperature < Defrost stop temperature (in DTE/F8)
°C
2.0
Time passed the defrosting cycle time (IDF/F6) or forced defrosting beginning
°C
B.
Defrost relay will open/off when reaching any one of the below conditions
20.0
The defrost sensor temperature ≥ Defrost stop temperature (in DTE/F8)
°C
-20.0
Passed the defrosting Lasting Time (MDF/F7)
Min
3
5.3. When will the Compressor Starts / Stop?
Hour
6
The room temperature was supposed to keep at the range from «F1(SET)» to «F1+F2 (SET+HY).»
First, Time Conditions
Min
30
A. When FOD/F15 > 0s, the time should be later than:
°C
10.0
•
Min
2
B.
When FOD/F15 < 0s (the fan startup earlier than the compressor), the time later than:
•
•
N/A
EL/1
And Temperature Conditions
A. If TDF/F10 = EL/0 (like an electric heating wire wound around the evaporator)
Controller Status
N/A
RT/0
Manual turn on the forced cooling Room Temp ≥ SET/F1
Not in Defrosting
B. If TDF/f10 = HTG/1 (Hot Gas from the compressor Reverse Rotary), exist an extra
N/A
RT/1
option than A
Controller Status
Manual turn on the forced cooling Room Temp ≥ SET/F1
Not in Defrosting
In defrosting
N/A
5.4. When will the Alarming Starts / Stop?
Once alarming, the readout flashing and buzzer screaming press any key to stop the buzzer ticktack, but the
error code in the display will not disappear until all errors have been fixed.
°C
-50.0
Code
E01
S
E02
60
HHH
LLL
Readout flash
°C
50.0
buzzer screams
°C
50.0
5.5. When will the Fan Works/Stops?
°C
-50.0
Please check the conditions from FOD/F15 & FNC/F13 from the menu list.
Min
15
°C
0.0
2 / 2
The moment of the compressor recent stops + AC/F5
The moment of the compressor recent stops + AC/F5, and
The fan starts moment + FOD/F15
Working Condition
Room Temp ≥ SET/F1 + HY/F2
Working Condition
Room Temp ≥ SET/F1 + HY/F2
Evaporation Temp > DTE/F8
Troublesome From
Room Sensor
Defrost Sensor
Room or Defrost Sensor
Room Sensor
Haswill Electronics
https://www.thermo-hygro.com
Copyright Haswill-Haswell All Rights Reserved
Stops Condition
Room Temp < SET/F1
or defrost beginning
or forced refrigeration is over.
Stops Condition
Room Temp < SET/F1
or defrosting is over
or forced refrigeration over
and won’t defrost at once.
Reason
Open or short
Open or short
> Max measurable limits
< Min measurable limits
-50°C < temp. < ALU/F17
or
Текущее время: 11:03. Часовой пояс GMT +3.
Powered by vBulletin® Version 4.2.3
Copyright © 2023 vBulletin Solutions, Inc. All rights reserved.
Перевод: zCarot
Все материалы на сайте представлены исключительно для ознакомления и не могут быть использованы в коммерческих целях.
Все авторские права принадлежат их владельцам. Если владелец авторских прав не желает, чтобы его произведения были доступны через этот сайт, ему достаточно сообщить нам об этом по электронной почте указанной на странице контактов домена. HolodForum.ru 2008-2021
Спонсор форума: ремонт-холодильников.com
Термостат Haswill Electronics STC-9200
информация о продукте
Термостат STC-9200 от Haswill Electronics представляет собой контроллер охлаждения, разморозки и вентилятора испарителя. Он предназначен для управления состоянием электропитания подключенного холодильного устройства, устройства оттаивания и вентилятора испарителя, что делает его идеальным для использования в морозильных камерах большого размера. Продукт поставляется с одним контроллером, двумя датчиками, двумя зажимами, одним руководством и одним водонепроницаемым чехлом.
Индикатор/символ на дисплее
На дисплее отображаются четыре различных индикатора: состояние компрессора (работает или остановлен), состояние настройки (нормальное или в режиме настройки), состояние вентилятора (работает или остановлен) и состояние размораживания (работает или остановлен).
спецификации продукта
- Входная мощность: максимальный ток 8 А (по умолчанию) при 250 В переменного тока
- Класс защиты: IP65 на передней панели
- Задержка подмигивания: нет данных
- Быстрое охлаждение вручную: N/A
Размеры и установка
Размеры изделия не указаны в руководстве пользователя. Тем не менее, рекомендуется устанавливать изделие с помощью зажимов, входящих в комплект поставки. Передняя панель защищена по стандарту IP65, что делает ее пригодной для наружной установки.
Инструкции по использованию продукта
- Подключите холодильное устройство, блок разморозки и вентилятор испарителя к термостату STC-9200 в соответствии со схемой подключения, приведенной в руководстве.
- Включите термостат, подключив его к источнику питания.
- На дисплее отобразится текущее состояние компрессора, вентилятора и блока оттаивания.
- Чтобы изменить настройки, нажмите кнопку SET и используйте кнопки ВВЕРХ и ВНИЗ для навигации по списку меню.
- Дисплей покажет текущее состояние настройки в режиме настройки.
- Чтобы проверить, когда вентилятор будет работать или останавливаться, обратитесь к условиям FOD/F15 и FNC/F13 в списке меню.
- Продукт поставляется с водонепроницаемым чехлом, который можно использовать для защиты от влаги и пыли при наружной установке.
Контроллер вентилятора охлаждения, разморозки и испарителя
(Версия 22.11.07GEN) Контроллер температуры STC-9200 управляет состоянием питания подключенного холодильного устройства, блока размораживания и вентилятора испарителя, что обычно подходит для больших морозильных камер.
Упаковка
- контроллер: 1PCS
- Сенсор: 2PCS
- клипы: 2PCS
- Руководство: 1 PCS
- Водонепроницаемая крышка: 1PCS
Спецификация
- Входная мощность 220 В переменного тока ± 10% 50/60 Гц; (опция 12/24/48/110 В)
- Максимальный ток 8A (по умолчанию) при 250 В переменного тока
- Термистор/датчик NTC, 25°C/10 кОм, кабель датчика 200см
- Класс защиты IP65 на передней панели
- Хранилище -10°C ~ 60°C, относительная влажность <90%, без конденсации
- Диапазон температур Измеряемый: -50.0°C ~ +50.0°C; Контролируемый: -50.0°C ~ +50.0°C
- Постановления 0.1 ° C
- точность ± 1°С от -40°С до +50°С; ± 2°C в другом диапазоне
- потребляемая мощность ≤ 3 Вт
Экологическая информация
Материал упаковки на 100% подлежит вторичной переработке. Просто утилизируйте его через специализированных переработчиков. Электрокомпоненты могут быть переработаны, если они разобраны для специализированных компаний. Пожалуйста, не сжигайте и не выбрасывайте контроллеры в бытовой мусор. Соблюдайте соответствующий закон в вашем регионе, касающийся экологически ответственного способа утилизации его устройств.
Внешний вид и работа
Передняя панель и управление
В нормальном состоянии на экране отображается температура датчика комнатной температуры.
- А. Держите набор в течение 3 с, чтобы войти/выйти из интерфейса настройки пользователя, чтобы проверить и изменить уставку и гистерезис здесь.
- Б. Держите
ключ и
нажмите одновременно на 10 секунд, чтобы заблокировать/разблокировать меню администратора: ВЫКЛ.
= разблокировано, доступно для редактирования ВКЛ = заблокировано, можно только проверить значение, не редактируется. - С. Держите набор
ключи на 10 секунд для входа в админку; нажмите набор для проверки текущих данных и нажмите кнопку
ключ для изменения данных; нажмите набор еще раз, чтобы сохранить данные и вернуться к списку меню; Если без работы в течение 10 секунд, новые данные будут автоматически сохранены.
- Д. Держите
в течение 3 с для проверки температуры датчика разморозки;
- Е. Держите
на 3 с для запуска принудительного режима охлаждения вручную (условия 5.3); сделать это снова, чтобы выйти.
- Ф. Держите
на 3 с для ручного запуска режима принудительной разморозки (условия в 5.2); сделайте это еще раз, чтобы войти в состояние капания размораживающей воды.
Индикатор/символ на дисплее
Размеры и установка
- Размер крепления: 71*29*85 мм (Ш*В*Г);
- Отсоедините застежки-молнии, вставьте контроллер в отверстие и подключите его.
- Установите крепления и водонепроницаемую крышку.
Схема подключения
- A. Датчик 10K NTC, не нужно различать + или -.
- B. Входной объемtage должен быть в пределах объемаtage значение, отмеченное на диаграмме ±10% значение.
- C. Рекомендуемая мощность нагрузки ≤ Voltage∗ Максимальный ток коэффициента реле
Копирующий ключ (необязательно)
- A. Загрузить в контроллер
- Вставьте ключ копирования, нажмите кнопку, на дисплее появится надпись «UPL»;
- Теперь нажмите клавишу, чтобы загрузить данные, после завершения отобразится «END»;
- Выключите контроллер, а затем вытащите Copykey.
- Скачать с контроллера
- Убедитесь, что контроллер выключен, и вставьте ключ копирования, а затем запустите
- Контроллер автоматически сканирует Copykey и загружает данные, показывает «DOL» при загрузке и показывает «END» после завершения.
- Перезагрузите контроллер; он будет работать по новым данным.
Внимание:
- Часть параметров будет выполнена в следующем цикле; пожалуйста, выключите контроллер и снова включите питание, чтобы начать новый цикл для работы с новыми данными без ожидания.
- Если параметр в Copykey существует с ошибкой или имеет неверный формат, на дисплее отображается ERR.
Конфигурации
Меню кодов и функций
Удерживайте кнопку УСТАНОВКА+ клавиши одновременно на 10 секунд для входа в интерфейс администратора; Коды S ET и HY (F 0 1 и F 0 22) — меню пользователя; другие — меню администратора, ссылка 4.1 A и C
Когда начнется/остановится разморозка?
- Реле разморозки закроется/включится при достижении всех перечисленных ниже условий.
- Реле разморозки будет открываться/выключаться при достижении любого из следующих условий
Когда компрессор запустится/остановится?
Температуру в помещении предполагалось поддерживать в пределах от
Во-первых, временные условия
- После появления
, время должно быть позже, чем:
И температурный режим
Сигнал тревоги и код ошибки
После подачи сигнала тревоги, показания мигают и звучит зуммер, нажмите любую клавишу, чтобы остановить тиканье зуммера, но код ошибки на дисплее не исчезнет, пока все ошибки не будут исправлены.
Когда вентилятор заработает/остановится?
Пожалуйста, проверьте условия FOD/F15 и FNC/F13 в списке меню.
- Видео на YouTube
- Хасвилл Электроникс
- https://www.thermo-hygro.com
- Copyright Haswill-Haswell Все права защищены