Issue 01/06
Quit
Refer to F0001
Cause
—
motor temperature sensor either short-circuited or open-circuit.
—
if it is identified that a signal has been lost, then the temperature monitoring changes-over to monitoring
based on the thermal-motor model.
F0020 Line supply phase missing
Quit
Refer to F0001
Cause
—
a fault is output if one of the three input phases is missing, the pulses are enabled and a load is present
Diagnosis & Remedy
Please check the following:
—
are the power connections ok ?
F0021 Ground fault
Quit
Refer to F0001
Cause
—
the fault occurs if the sum of the phase currents is greater than 5 % of the inverter rated current.
NOTE
—
this fault only occurs for inverters with 3 current sensors (sizes D to F, GX, FX).
Diagnosis & Remedy
Please check the following:
—
are the connections at the motor terminal boxes o.k. ?
—
are the motor cable connections at the inverter o.k. ?
F0022 Hardware monitoring active
Quit
Refer to F0001
Cause
This fault (r0947 = 22 and r0949 = 1) occurs under the following circumstances:
(1) DC link overcurrent condition = IGBT short-circuit
(2) Braking chopper short-circuit
(3) Ground fault
(4) I/O module not correctly inserted
For the following sizes the above faults can occur:
—
size A to C (1),(2),(3),(4)
—
size D to E (1),(2),
—
size F
The following faults only occur in conjunction with sizes FX / GX:
—
UCE faults are identified if r0947 = 22 and the fault value r0949 = 12 or 13 or 14.
—
I2C bus error is identified if r0947 = 22 and the fault value r0949 = 21 (power-down and then power-up
again).
NOTE
All of these faults are assigned to a signal in the power module. This means that it is not possible to
determine which fault actually occurred.
Diagnosis & Remedy
You must first identify as to whether the fault is permanent (i.e. the inverter cannot be started without the
fault occurring) or it sporadically occurs (occasionally occurs or under certain operating conditions).
Permanent fault F0022:
—
check whether the I/O module is correctly inserted (refer to the Operating Instructions).
—
is there a ground fault or short-circuit at the inverter output or at an IGBT?
You can identify this by disconnecting the motor cable.
In the case that the fault occurs, if all of the external cables (with the exception from the line supply
voltage) are disconnected, then with a high degree of probability, the drive unit is defective and must be
repaired.
Sporadic fault F0022:
—
this fault should be treated as «overcurrent». If fault F0022 sporadically occurs, the causes can be as
follows:
—
sudden load changes or mechanical obstructions
—
extremely short ramp-up times (accelerating times)
—
poor optimization of the sensorless closed-loop vector control
—
incorrect braking resistor is installed with an excessively low resistance
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
(4)
(1),(2)
Faults and Alarms
STOP II
STOP II
STOP II
STOP II
309
В процессе работы выходит из строя даже самое надежное промышленное оборудование. В данной статье мы приведем ошибки частотного преобразователя Siemens, а точнее Siemens MICROMASTER 440. Частотники в наше время нашли широкое применения в абсолютно всех сферах промышленности управляя как мини моторами в оргтехнике, так и гигантскими двигателями в горнодобывающей промышленности.
Для простоты общения со столь сложной электроникой все частотные преобразователи оснащены небольшими дисплеями с помощью которых выводятся информационные сообщения с кодами ошибок, расшифровав которые можно сразу же узнать причину ее возникновения. Если учесть распространенность данной промышленной электроники, то появляется острая нужда в расшифровке кодов ошибок частотных преобразователей. В этой статье мы рассмотрим одного из самых известных производителей промышленной электроники имеющему уважение во всем мире, Siemens.
Существует несколько видов ошибок, некоторые из них можно устранить автоматически, а некоторые возможно исправить только, обратившись в специализированный сервисный центр. В таблицах ниже приведены коды ошибок частотного преобразователя Siemens и их расшифровка.
Индикация- статусная панель, устранение неисправностей с помощью статусной панели.
Светодиоды |
Приоритет |
Описание состояния преобразователя |
|
Зеленый |
Желтый |
||
Не горит |
Не горит |
1 |
|
Не горит |
Горит |
8 |
|
Горит |
Не горит |
13 |
|
Горит |
Горит |
14 |
|
Не горит |
Мигает R1 |
4 |
|
Мигает R1 |
Не горит |
5 |
|
Мигает R1 |
Горит |
7 |
|
Горит |
Мигает R1 |
8 |
|
Мигает R1 |
Мигает R1 |
9 |
|
Мигает R1 |
Мигает R1 |
11 |
|
Мигает R1 |
Мигает R2 |
6/10 |
|
Мигает R2 |
Мигает R1 |
12 |
|
Мигает R2 |
Мигает R2 |
2 |
|
Мигает R2 |
Мигает R2 |
3 |
|
R1 – время включенного состояния 900 мС |
|
При появлении неисправности на дисплее частотного преобразователя Siemens MICROMASTER 440 отобразится код ошибки, в таблице ниже приведены все коды ошибок привода Siemens
Код сбоя |
Описание |
Возможные причины |
Диагностика и способы устранения |
F0001 |
Перегрузка по току |
|
|
F0002 |
Перенапряжение |
|
|
F0003 |
Пониженное напряжение |
|
|
F0004 |
Перегрев преобразователя |
Температура окружающей среды выше допустимого предела. Неисправность вентилятора |
|
F0005 |
Превышение по I2t |
|
|
F0011 |
Перегрев двигателя по I2t |
|
|
F0041 |
Ошибка при измерении сопротивления статора |
|
|
F0051 |
Ошибка параметра в EEPROM |
|
|
F0052 |
Ошибка стека |
|
|
F0060 |
Нет ответа от специализированной ASIC – платы. |
|
|
F0070 |
Ошибка задания через плату связи |
|
|
F0071 |
Нет данных по последующему протоколу (RS232) в течение времени ожидания. |
|
|
F0072 |
Нет данных по последующему протоколу (RS485) в течение времени ожидания. |
|
|
F0080 |
Нет входного сигнала на аналоговом входе. |
|
|
F0085 |
Внешний сбой |
|
|
F0101 |
Переполнение стека |
|
|
F0221 |
Обратная связь ПИ- регулятора ниже минимального значения |
|
|
F0222 |
Обратная связь ПИ-регулятора выше максимального значения |
|
|
F0450 (только в сервисном режиме) |
Ошибка при BIST — тестировании |
Значение ошибки:
|
|
Таблица кодов предупреждения частотного преобразователя Siemens MICROMASTER 440
А0501 |
Ограничение тока нагрузки |
|
|
А0502 |
Достигнут верхний предел напряжения питания. |
|
Примечание: |
А0503 |
Достигнут нижний предел напряжения питания. |
|
|
А0504 |
Перегрев преобразователя |
|
|
А0505 |
Превышение по I2t |
|
|
А0506 |
Нагрузочный цикл преобразователя |
|
|
А0511 |
Перегрев двигателя по I2 t |
|
|
А0600 |
Перегрузка операционной системы реального времени. |
|
|
А0700 |
СВ предупреждение 1 |
|
|
А0701 |
СВ предупреждение 2 |
|
|
А0702 |
СВ предупреждение 3 |
|
|
А0703 |
СВ предупреждение 4 |
|
|
А0704 |
СВ предупреждение 5 |
|
|
А0705 |
СВ предупреждение 6 |
|
|
А0706 |
СВ предупреждение 7 |
|
|
А0707 |
СВ предупреждение 8 |
|
|
А0708 |
СВ предупреждение 9 |
|
|
А0709 |
СВ предупреждение 10 |
|
|
А0710 |
Ошибка связи СВ |
|
|
А0711 |
Ошибка конфигурирования СВ |
|
|
А0910 |
Деактивирован регулятор Vdc-max |
|
|
А0911 |
Vdc-max регулятор активен |
|
|
А0920 |
Неправильно установлен параметр аналогового входа |
|
|
А0921 |
Неправильно установлен параметр аналогового выхода |
|
|
А0922 |
К приводу не подключена нагрузка |
|
|
А0923 |
Активны сигналы «Толчок» вправо и «Толчок» влево (JOG) |
|
|
Сброс ошибок и Ремонт частотных преобразователей Siemens в сервисном центре
Компания «Кернел» производит ремонт промышленной электроники и оборудования с 2002 года. За это время мы накопили колоссальный опыт в том числе опыт в ремонте частотных преобразователей Siemens. Ремонт подобной промышленной электроники ответственное и сложное занятие, требующие максимальной отдачи, профессионализма и максимально полной материальной базе.
Специалисты нашего сервисного центра уделяют максимальное внимание к качеству исполнения ремонта, программирования и настройке промышленного преобразователя частоты, не зависимо от производителя данного промышленного оборудования. Именно поэтому мы смело даем гарантию на все выполненные работы шесть месяцев.
Ремонт частотных преобразователей производится исключительно с использованием оригинальных запасных частей, на компонентном уровне с применением высокотехнологичного оборудования, квалифицированным персоналом с инженерным образованием.
Если на вашем производстве появились проблемы с частотным преобразователем, которые вы не можете решить самостоятельно, мы всегда рады вам помочь. Обращайтесь в сервисный центр «Кернел». Специалисты нашей компании в минимальные сроки проведут глубокую диагностику и последующий ремонт частотного преобразователя. Оставьте заказ на ремонт оборудования используя форму на сайте, либо свяжетесь с нашими менеджерами, сделать это очень просто.
Как с нами связаться
У вас остались вопросы, связанные с ремонтом, программированием и настройкой приводов Siemens? Задайте их нашим менеджерам. Связаться с ними можно несколькими способами:
- Заказав обратный звонок (кнопка в правом нижнем углу сайта)
- Посредством чата (кнопка расположена с левой стороны сайта)
- Либо позвонив по номеру: +7(8482) 79-78-54; +7(917) 121-53-01
- Написав на электронную почту: 89171215301@mail.ru
Далеко не полный список производителей промышленной электроники и оборудования, ремонтируемой в нашей компании.
Issue 10/06
7 Displays and messages
MICROMASTER 440
Operating Instructions (Compact)
77
7.2
Fault messages and Alarm messages
Fault Significance
Alarm Significance
F0001 Overcurrent
A0501 Current
Limit
F0002 Overvoltage
A0502 Overvoltage
limit
F0003 Undervoltage
A0503 Undervoltage
Limit
F0004 Inverter
Overtemperature
A0504 Inverter
Overtemperature
F0005 Inverter
I
2
t
A0505
Inverter
I
2
t
F0011
Motor Overtemperature I
2
t
A0506
Inverter
Duty
Cycle
F0012
Inverter temp. signal lost
A0511
Motor Overtemperature I
2
t
F0015
Motor temperature signal lost
A0520
Rectifier Overtemperature
F0020
Mains Phase Missing
A0521
Ambient Overtemperature
F0021
Earth fault
A0522
I2C read out timeout
F0022
HW monitoring active
A0523
Output fault
F0023
Output fault
A0535
Braking Resistor Hot
F0024
Rectifier Over Temperature
A0541
Motor Data Identification Active
F0030
Fan has failed
A0542
Speed Control Optimization Active
F0035
Auto restart after n
A0590
Encoder feedback loss warning
F0040
Automatic Calibration Failure
A0600
RTOS Overrun Warning
F0041
Motor Data Identification Failure
A0700 — CB warning 1
F0042
Speed Control Optimization Failure
…
…
F0051
Parameter EEPROM Fault
A0709
CB warning 9
F0052
Power stack Fault
A0710
CB communication error
F0053
IO EEPROM Fault
A0711
CB configuration error
F0054
Wrong IO Board
A0910
Vdc-max controller de-activated
F0060
Asic Timeout
A0911
Vdc-max controller active
F0070
CB setpoint fault
A0912
Vdc-min controller active
F0071
USS (BOP link) setpoint fault
A0920
ADC parameters not set properly
F0072
USS (COM link) setpoint fault
A0921
DAC parameters not set properly
F0080
ADC lost input signal
A0922
No load applied to inverter
F0085
External Fault
A0923
Both JOG Left and Right are requested
F0090
Encoder feedback loss
A0952
Belt Failure Detected
F0101
Stack Overflow
A0936
PID Autotuning Active
F0221
PID Feedback below min. value
F0222
PID Feedback above max. value
F0450
BIST Tests Failure
(Service mode only)
F0452
Belt Failure Detected
F0001
OverCurrent — Motor power (P0307) does not correspond to the inverter power (r0206)
— Motor lead short circuit
— Earth faults Check the following:
1. Motor power (P0307) must correspond to inverter power (r0206).
2. Cable length limits must not be exceeded.
3. Motor cable and motor must have no shortcircuits or earth faults
4. Motor parameters must match the motor in use
5. Value of stator resistance (P0350) must be correct
6. Motor must not be obstructed or overloaded
— Increase the ramp time
— Reduce the boost level OFF2 F0002
OverVoltage — DC-link voltage (r0026) exceeds trip level (P2172)
— Overvoltage can be caused either by too high main supply voltage or if motor is in regenerative mode. Regenerative mode can be cause by fast ramp downs or if the motor is driven from an active load. Check the following:
1. Supply voltage (P0210) must lie within limits indicated on rating plate .
2. DC-link voltage controller must be enabled (P1240) and parameterized properly.
3. Ramp-down time (P1121) must match inertia of load.
4. Required braking power must lie within specified limits.
NOTE:
Higher inertia requires longer ramp times; otherwise, apply braking resistor. OFF2 F0003
UnderVoltage — Main supply failed.
— Shock load outside specified limits. Check the following:
1. Supply voltage (P0210) must lie within limits indicated on rating plate.
2. Supply must not be susceptible to temporary failures or voltage reductions. OFF2 F0004
Inverter Over
Temperature — Inverter overloaded.
— Duty cycle too demanding.
— Motor power (P0307) exceeds inverter power capability (r0206). Check the following:
1. Load duty cycle must lie within specified limits.
2. Motor power (P0307) must match inverter power (r0206) OFF2 F0011
Motor Over
Temperature — Motor overloaded Check the following:
1. Load duty cycle must be correct
2. Motor nominal overtemperatures (P0626-P0628) must be correct
3. Motor temperature warning level (P0604) must match OFF1 F0012
Inverter temp.
signal lost Wire breakage of inverter temperature (heatsink) sensor OFF2 F0015
Motor temperature
signal lost Open or short circuit of motor temperature sensor. If signal loss is detected, temperature monitoring switches over to monitoring with the motor thermal model. OFF2 F0020
Mains Phase
Missing Fault occurs if one of the three input phases are missed and the pulses are enabled and drive is loaded Check the input wiring of the mains phases OFF2 F0021
Earth fault Fault occurs if the sum of the phase currents is higher than 5 % of the nominal inverter current.
NOTE — Framesizes D to F
This fault only occurs on inverters that have 3 current sensors. OFF2 F0022
Powerstack fault That hardware fault (P0947 = 22 and
P0949 = 1) caused by the following events:
(1) DC-link overcurrent = short circuit of IGBT
(2) Short circuit of chopper
(3) Earth fault
(4) I/O board is not poperly inserted.
— Framesizes A to C (1),(2),(3),(4)
— Framesizes D to E (1),(2),(4)
— FramesizeF(2),(4)
— Since all these faults are assigned to one signal on the power stack, it is not possible to establish which one actually occurred.
— UCE failure was detected, when P0947 = 22 and fault value P0949 =12 or 13 or 14, depending on UCE (for MegaMaster only) Check the I/O board. It has to be fully pressed home. OFF2 F0023
Output fault One phase of output is disconnected OFF2 F0024
Rectifier Over
Temperature — Ventilation inadequate
— Fan inoperative
— Ambient temperature is too high. Check the following:
— Fan must turn when inverter is running
— Pulse frequency must be set to default value
— Ambient temperature could be higher than
specified for the inverter OFF2 F0030
Fan has failed Fan no longer working — Fault cannot be masked while options module
(AOP or BOP) is connected.
— Need a new fan. OFF2 F0035
Auto restart after n Auto restart fault after n-restart try OFF2 F0040
Automatic
Calibration Failure MICROMASTER 440 only OFF2 F0041
Motor Data
Identification
Failure Motor data identification failed.
— Alarm value =0: Load missing
— Alarm value =1: Current limit level reached during identification.
— Alarm value =2: Identified stator resistance less than 0.1% or greater than 100%.
— Alarm value =3: Identified rotor resistance less than 0.1% or greater than 100%.
— Alarm value =4: Identified stator reactance less than 50% and greater than 500%
— Alarm value =5: Identified main reactance less than 50% and greater than 500%
— Alarm value =6: Identified rotor time constant less than 10ms or greater than 5s
— Alarm value =7: Identified total leakage reactance less than 5% and greater than 50%
— Alarm value =8: Identified stator leakage reactance less than 25% and greater than 250%
— Alarm value =9: Identified rotor leakage inductance less than 25% and greater than 250%
— Alarm value = 20: Identified IGBT onvoltage less than 0.5 or greater than 10V
— Alarm value = 30: Current controller at voltage limit
— Alarm value = 40: Inconsistence of identified data set, at least one
identification failed Percentage values based on the impedance Zb = Vmot,nom / sqrt(3) / Imot,nom 0: Check that the motor is connected to the inverter.
1-40: Check if motor data in P304-311 are correct. Check what type of motor wiring is required (star, delta). OFF2 F0042
Speed Control
Optimisation Failure — Motor data identification failed.
— Alarm value =0: Time out waiting for stable speed
— Alarm value =1: Inconsistent readings OFF2 F0051
Parameter EEPROM
Fault — Read or write failure while saving nonvolatile
parameter. — Factory Reset and new parameterization
— Change drive OFF2 F0052
power stack Fault — Read failure for power stack information or invalid data — Change drive OFF2 F0053
IO Eeprom Fault — Read failure for IO EEPROM information or invalid data. — Check data
— Change IO module OFF2 F0054
Wrong IO Board 1. Wrong IO board is connected.
2. No ID detected on IO board, No data. — Check data
— Change IO module OFF2 F0060
Asic Timeout — Internal communications failure — If fault persists, change inverter OFF2 F0070
CB setpoint fault — No setpoint values from CB (communication board) during telegram off time — Check CB and communication partner OFF2 F0071
USS (BOP-link)
setpoint fault — No setpoint values from USS during telegram off time — Check USS master OFF2 F0072
USS (COMM link)
setpoint fault — No setpoint values from USS during telegram off time — Check USS master OFF2 F0080
ADC lost input
signal — Broken wire
— Signal out of limits OFF2 F0085
External Fault — External fault triggered via terminal inputs — Disable terminal input for fault trigger. OFF2 F0090
Encoder feedback
loss — Signal from Encoder lost 1. Check encoder fitted. If encoder not fitted, set P400 = 0 and select SLVC mode (P1300 = 20 or 22)
2. Check connections between encoder and inverter
3. Check encoder not faulty (select P1300 = 0, run at fixed speed, check encoder feedback signal in P66)
Increase encoder loss threshold in P492 OFF2 F0101
Stack Overflow — Software error or processor failure — Run self test routines OFF2 F0221
PID Feedback below
min. value — PID Feedback below min. value P2268 — Change value of P2268.Adjust feedback gain. F0222
PID Feedback above
max. value — PID feedback above max. value P2267. — Change value of P2267.Adjust feedback gain. F0450
BIST Tests Failure Fault value:
1. Some power section tests have failed
2. Some control board tests have failed
4. Some functional tests have failed
8. Some IO module tests have failed. (MM 420 only)
16. Internal RAM failed on power-up check — Drive may run but some features will not work properly.
— Replace drive. F0452
Belt Failure
Detected — Load conditions on motor indicate belt
failure or mechanical fault. Check the following:
1. No breakage, seizure or obstruction of drive train.
1. If using an external speed sensor, check for correct function.Check parameters:
— P0409 (pulse per min at rated speed).
— P2191 (Belt failure speed tolerance).
— P2192 (delay time for permitted deviation)
2. If using the torque envelope, check parameters:
— P2182 (threshold frequency f1)
— P2183 (threshold frequency f2)
— P2184 (threshold frequency f3)
— P2185 (upper torque threshold 1)
— P2186 (lower torque threshold 1)
— P2187 (upper torque threshold 2)
— P2188 (lower torque threshold 2)
— P2189 (upper torque threshold 3
— P2190 (lower torque threshold 3)
— P2192 (delay time for permitted deviation)
4. Apply lubrication if required.
Issue 10/06
7 Displays and messages
MICROMASTER 440
Operating Instructions (Compact)
77
7.2
Fault messages and Alarm messages
Fault Significance
Alarm Significance
F0001 Overcurrent
A0501 Current
Limit
F0002 Overvoltage
A0502 Overvoltage
limit
F0003 Undervoltage
A0503 Undervoltage
Limit
F0004 Inverter
Overtemperature
A0504 Inverter
Overtemperature
F0005 Inverter
I
2
t
A0505
Inverter
I
2
t
F0011
Motor Overtemperature I
2
t
A0506
Inverter
Duty
Cycle
F0012
Inverter temp. signal lost
A0511
Motor Overtemperature I
2
t
F0015
Motor temperature signal lost
A0520
Rectifier Overtemperature
F0020
Mains Phase Missing
A0521
Ambient Overtemperature
F0021
Earth fault
A0522
I2C read out timeout
F0022
HW monitoring active
A0523
Output fault
F0023
Output fault
A0535
Braking Resistor Hot
F0024
Rectifier Over Temperature
A0541
Motor Data Identification Active
F0030
Fan has failed
A0542
Speed Control Optimization Active
F0035
Auto restart after n
A0590
Encoder feedback loss warning
F0040
Automatic Calibration Failure
A0600
RTOS Overrun Warning
F0041
Motor Data Identification Failure
A0700 — CB warning 1
F0042
Speed Control Optimization Failure
…
…
F0051
Parameter EEPROM Fault
A0709
CB warning 9
F0052
Power stack Fault
A0710
CB communication error
F0053
IO EEPROM Fault
A0711
CB configuration error
F0054
Wrong IO Board
A0910
Vdc-max controller de-activated
F0060
Asic Timeout
A0911
Vdc-max controller active
F0070
CB setpoint fault
A0912
Vdc-min controller active
F0071
USS (BOP link) setpoint fault
A0920
ADC parameters not set properly
F0072
USS (COM link) setpoint fault
A0921
DAC parameters not set properly
F0080
ADC lost input signal
A0922
No load applied to inverter
F0085
External Fault
A0923
Both JOG Left and Right are requested
F0090
Encoder feedback loss
A0952
Belt Failure Detected
F0101
Stack Overflow
A0936
PID Autotuning Active
F0221
PID Feedback below min. value
F0222
PID Feedback above max. value
F0450
BIST Tests Failure
(Service mode only)
F0452
Belt Failure Detected
- Все о Simoreg DC Master
- Принцип работы рекуператора
- Оборудование для сети Wi-Fi
F0001 | F0002 | F0003 | F0004 | F0006 | F0011 | F0041 | F0051 | F0052 | F0060 |
F0070 | F0071 | F0072 | F0080 | F0085 | F0101 | F0221 | F0222 | F0450 | A0501 |
A0502 | A0503 | A0504 | A0505 | A0506 | A0511 | A0600 | A0700 | A0701 | A0702 |
A0703 | A0704 | A0705 | A0706 | A0707 | A0708 | A0709 | A0710 | A0711 | A0910 |
A0911 | A0920 | A0921 | A0922 | A0923 |
*Нажав на код интересующей Вас аварии, Вы перейдете на страницу с ее подробным описанием (функция в стадии наладки).
18 декабря 2008 г. — добавлены описания сообщений F0001 и A0501.
19 декабря 2008 г. — добавлено краткое описание сбоя F0002.
12 января 2009 г. — добавлено описание сбоев F0003 и F0004.
15 января 2009 г. — добавлено полное описание сбоя F0002.
21 января 2009 г. — в раздел «Статьи» добавлена статья «Функция компенсации скольжения в Микромастер 440»
- Форум Siemens
- Класс защиты (IP)
- Класс изоляции
- Режимы работы двигателя (S)
- Допустимая длина кабеля для Micromaster
- Управление электроприводами. Башарин, Новиков, Соколовский
- Общий курс электропривода. Чиликин, Сандлер
- Ограничение динамических нагрузок электропривода. Ключев В. И.
- Компенсация скольжения в Micromaster440
- Электромагнитные помехи с ШИМ
- Расчет сетевого фильтра
другие статьи…
- Наладка Profibus
- GSD-файл
- Инструкция по эксплуатации Micromaster 440 (на русск. языке)